Plan Review Details - Permit 15050133
| Plan Review Stops For Permit 15050133 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2015-06-02 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2015-06-03 |
Time |
12:59 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2015-06-02 |
Time |
08:54 |
Sent To |
|
|
| Notes |
| 2015-06-02 14:10:32 | THE DRAWINGS WERE CORRECTED AND APPLICATION WAS | | | APPROVED. THIS WAS ROUTED TO FIRE FOR THEIR REVIEW. | | 2015-06-02 10:00:34 | THE SUBMITTED DRAWINGS & DIAGRAM WERE INCONCLUSIVE. THE | | | SERVICE AND/OR GENERATOR PHASING WAS NOT IDENTIFIED. I | | | SPOKE WITH BILL PORTER WHO REALIZED THE PROBLEM AND | | | WOULD GET BACK TO ME WITH A CORRECTION. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2015-05-26 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2015-05-26 |
Time |
14:45 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2015-05-26 |
Time |
14:34 |
Sent To |
FIRE |
|
| Notes |
| 2015-05-26 14:49:39 | YOU SHALL SUBMITT DATA/SPEC SHEET FOR THE PROPOSED | | | GENERATOR ALONG WITH A BETTER DETAILED WIRING DIAGRAM. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2015-06-03 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2015-06-03 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2015-06-03 |
Time |
12:55 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2015-05-27 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2015-05-27 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2015-05-27 |
Time |
16:41 |
Sent To |
PC |
|
| Notes |
| 2015-05-27 16:49:59 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) NO GENERATOR DETAIL PROVIDED, INCLUDING TYPE AND | | | SIZE, FUEL SOURCE, EXHAUST LOCATION. | | | | | | 2) PROVIDE DETAILED AND ACCURATE DIMENSIONS FROM | | | PROPERTY LINE, BUILDING LINE, ADJACENT IMPORTANT | | | STRUCTURES, NEAREST OPENINGS TO ANY BUILDINGS. | | | | | | 3) PROVIDE NOTE INDICATING IF THIS SUPPLIES EMERGENCY | | | POWER TO THE LIFE SAFETY FIRE ALARM SYSTEM. IF SO, IT | | | SHALL COMPLY WITH ALL APPROPRIATE NFPA CODES. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2015-06-03 |
|
|
Cont ID |
|
| Sent By |
malbarra |
Date |
2015-06-03 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2015-05-29 |
Time |
|
Sent To |
E |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2015-05-27 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2015-05-27 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2015-05-05 |
Time |
16:31 |
Sent To |
|
|
| Notes |
| 2015-05-05 16:31:47 | SENT TO ZONING SHELF FOR REVIEW. JG. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2015-05-08 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2015-05-08 |
Time |
11:43 |
Rev Time |
0.00 |
| Received By |
sgraham |
Date |
2015-05-08 |
Time |
11:43 |
Sent To |
E |
|
| Notes |
|
|
|