Plan Review Details - Permit 15050095
Plan Review Stops For Permit 15050095
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-07-05 Cont ID  
Sent By shill Date 2015-07-05 Time 16:09 Rev Time 0.00
Received By shill Date 2015-07-05 Time 16:09 Sent To  
Notes
2015-07-05 16:11:41****PROVISO****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 AS A LEGIBLE PLAN WITH ALL REQUIRED INFORMATION WAS NOT
 PROVIDED, THIS PLAN REVIEW IS PASSED WITH PROVISO, AT
 CONTRACTOR'S RISK. COMPLIANCE WILL BE FIELD VERIFIED.
  
 PER CONTRACTOR, THERE IS ONLY ONE ACCESSIBLE
 ENTRANCE/EXIT FOR THIS HOTEL (MAIN ENTRANCE) AND ALL
 OTHER ENTRANCES/EXITS ARE NOT ACCESSIBLE.
  
 FBC 2010 ACCESSIBLITY 202.3 (ALTERATIONS), 208.2
 (PARKING SPACES), 502 (PARKING SPACES), 206 (ACCESSIBLE
 ROUTE)
  
 1. ALL ACCESSIBLE SPACES APPEAR TO BE IN ONE LOCATION.
 SEE FBC 2010 ACCESSIBILITY 208.3.1:
  
 WHERE PARKING SERVES MORE THAN ONE ACCESSIBLE ENTRANCE,
 PARKING SPACES COMPLYING WITH 502 SHALL BE DISPERSED
 AND LOCATED ON THE SHORTEST ACCESSIBLE ROUTE TO THE
 ACCESSIBLE ENTRANCES.
  
 ALL SEVEN REQUIRED SPACES ARE IN ONE LOCATION, BUT THE
 WORK AREA COVERS SEVERAL PARKING AREAS. MORE
 INFORMATION IS REQUIRED TO DETERMINE COMPLIANCE. REVISE
 PLAN TO SHOW ALL ACCESSIBLE ENTRANCES.
  
 **PER CONTRACTOR, THERE IS ONLY ONE ACCESSIBLE
 ENTRANCE/EXIT**
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-06-03 Cont ID  
Sent By shill Date 2015-06-03 Time 13:36 Rev Time 0.00
Received By shill Date 2015-06-03 Time 13:36 Sent To  
Notes
2015-06-03 14:04:01****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC 2010 ACCESSIBLITY 202.3 (ALTERATIONS), 208.2
 (PARKING SPACES), 502 (PARKING SPACES), 206 (ACCESSIBLE
 ROUTE)
  
 1. ALL ACCESSIBLE SPACES APPEAR TO BE IN ONE LOCATION.
 SEE FBC 2010 ACCESSIBILITY 208.3.1:
  
 WHERE PARKING SERVES MORE THAN ONE ACCESSIBLE ENTRANCE,
 PARKING SPACES COMPLYING WITH 502 SHALL BE DISPERSED
 AND LOCATED ON THE SHORTEST ACCESSIBLE ROUTE TO THE
 ACCESSIBLE ENTRANCES.
  
 ALL SEVEN REQUIRED SPACES ARE IN ONE LOCATION, BUT THE
 WORK AREA COVERS SEVERAL PARKING AREAS. MORE
 INFORMATION IS REQUIRED TO DETERMINE COMPLIANCE. REVISE
 PLAN TO SHOW ALL ACCESSIBLE ENTRANCES.
  
 2. PLAN MAKES REFERENCE TO ONE VAN ACCESSIBLE SPACE.
 ALL ARE REQUIRED TO MEET THE WIDTH DIMENSIONS OF VAN
 ACCESSIBLE SPACES, SECTION 502.2.
  
 3. THE INDIVIDUAL TAKING RESPONSIBILITY FOR THE DESIGN
 AND INFORMATION IS TO PROVIDE THEIR WRITTEN NAME AND
 SIGNATURE ON THE PLAN, FBC 107.
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2015-05-19 Cont ID  
Sent By cranford Date 2015-05-19 Time 15:54 Rev Time 0.00
Received By cranford Date 2015-05-19 Time 15:44 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-07-05 Cont ID  
Sent By shill Date 2015-07-05 Time 16:12 Rev Time 0.00
Received By shill Date 2015-06-25 Time 13:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-06-03 Cont ID  
Sent By shill Date 2015-06-03 Time 14:04 Rev Time 0.00
Received By shill Date 2015-06-03 Time 14:04 Sent To  
Notes
2015-05-05 11:30:37ROUTED TO ZONING

Review Stop Z ZONING
Rev No 1 Status P Date 2015-05-08 Cont ID  
Sent By sgraham Date 2015-05-08 Time 11:49 Rev Time 0.00
Received By sgraham Date 2015-05-08 Time 11:48 Sent To ENG
Notes
***NONE***