Plan Review Details - Permit 15050048
Plan Review Stops For Permit 15050048
Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2015-05-25 Cont ID  
Sent By Mgonzale Date 2015-05-25 Time   Rev Time 1.00
Received By mgonzale Date 2015-05-25 Time   Sent To I
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2015-05-07 Cont ID  
Sent By cranford Date 2015-05-07 Time 09:03 Rev Time 0.00
Received By cranford Date 2015-05-07 Time 07:45 Sent To  
Notes
2015-05-07 09:02:58PUBLIC WORKS DEPT.
 LAND DEVELOPMENT
  
 1. PLEASE SHOW WHERE THE GREASE TRAP(S) WILL BE
 LOCATED.
  
 2. THE ORIGINAL BUILDING PERMIT (04060338) INDICATES
 THAT TWO 1250 GALLON, GRAVITY INTERCEPTORS IN SERIES
 ARE REQUIRED FOR THE 135 SEATS. PLEASE INDICATE WHAT
 SIZE AND TYPE OF INTERCEPTORS ARE PROPOSED FOR THE
 REPLACEMENT.
  
 3. PLEASE INDICATE THE LOCATION OF THE SAMPLE PORT.
  
 KELLY CRANFORD, P.E.
 LAND DEVELOPMENT ENGINEER
 PUBLIC WORKS DEPARTMENT
 CITY OF WEST PALM BEACH
 [email protected]
 561-494-1098 (OFFICE)
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-05-26 Cont ID  
Sent By andrian Date 2015-05-26 Time 08:26 Rev Time 0.00
Received By andrian Date   Time   Sent To  
Notes
2015-05-26 08:27:22CUSTOMER CONTACTED TO PICK UP PERMIT.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By jgomez Date 2015-05-19 Time 14:45 Sent To  
Notes
2015-05-19 14:46:25RE-SUBMITTAL SENT TO PLUMBING SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-05-07 Cont ID  
Sent By cranford Date 2015-05-07 Time 09:04 Rev Time 0.00
Received By cranford Date 2015-05-04 Time 11:24 Sent To  
Notes
2015-05-04 11:25:07ROUTED TO PLUMBING OVER 5K

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-05-21 Cont ID  
Sent By tklarge Date 2015-05-21 Time 07:22 Rev Time 0.00
Received By tklarge Date 2015-05-21 Time 06:13 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-05-05 Cont ID  
Sent By tklarge Date 2015-05-05 Time 06:03 Rev Time 0.00
Received By tklarge Date 2015-05-05 Time 05:40 Sent To  
Notes
2015-05-05 05:53:051) SUBMIT A SITE PLAN SHOWING THE LOCATION OF THE
 INTERCEPTOR TO BE REPLACED. PLAN CAN BE HAND DRAWN.WPB
 AMEND. TO 2010 FBC SEC. 107.2.1.
 2) SUBMIT DETAIL OF THE TYPE OF INTERCEPTOR TO BE
 INSTALLED. 2010 FPC 1003.2. SEE 2010 FPC SECS.
 1003.5.2, 1003.5.3 FOR CONSTRUCTION REQUIREMENTS.
 3) SUBMIT INTERCEPTOR SIZING CALCULATIONS TO ENSURE
 THAT THE INTERCEPTOR BEING INSTALLED, ALTHOUGH AN EXACT
 REPLACEMENT, IS SIZED CORRECTLY. THE EXISTING UNIT MAY
 NOT HAVE BEEN SIZED CORRECTLY AND NOW IS THE TIME TO
 CORRECT ANY ISSUES. 2010 FPC SEC.1003.5.1 AND TABLE
 1003.5.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  
  