Plan Review Details - Permit 15050015
Plan Review Stops For Permit 15050015
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2015-05-15 Cont ID  
Sent By   Date 2015-05-15 Time 06:29 Rev Time 0.00
Received By jwitmer Date 2015-05-15 Time 05:55 Sent To E
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-06-22 Cont ID  
Sent By R Lecky Date 2015-06-22 Time 11:35 Rev Time 0.00
Received By dhayes Date 2015-06-22 Time 11:28 Sent To  
Notes
2015-06-22 11:43:22APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN APPROVED
 PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED
 INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION
 FEE(S).
  
 1) PROVIDE A VOLTAGE DROP CALCULATION TO THE INSPECTOR
 UPON 1ST INSPECTION IN THE FIELD INDICATING THE FEEDER
 CONDUCTORS SHALL HAVE AN AMPACITY NOT LESS THAN
 REQUIRED TO SUPPLY THE LOAD AS CALCULATED NEC 215.2
 (A)(1). MINIMUM RATING AND SIZE.
  
 2) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 ARE REQUIRED FOR FIRE ALARM, ACCESS CONTROL SYSTEM,
 POS,SECURITY, CCTV, AUDIO/VIDEO, NETWORK, DATA, AND,
 COMMUNICATION AS NEEDED.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-05-28 Cont ID  
Sent By rlecky Date 2015-05-28 Time 13:05 Rev Time 0.00
Received By rlecky Date 2015-05-28 Time 11:06 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-05-04 Cont ID  
Sent By scaldero Date 2015-05-04 Time 15:28 Rev Time 0.00
Received By jwitmer Date 2015-05-04 Time 15:01 Sent To  
Notes
2015-05-04 15:25:05PERMIT # 15050015
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVISO:
  
 1) THIS PROPERTY IS EQUIPPED WITH A COMMON FIRE ALARM
 SYSTEM. AS PREVIOUSLY DISCUSSED WITH PROPERTY
 MANAGERMENT, ALL TENANT SPACES MUST HAVE PROPER
 NOTIFICATION IN THE EVENT OF A FIRE EMERGENCY. PROVIDE
 VISUAL AND AUDIBLE NOTIFICATION APPLIANCE IN ALL PUBLIC
 AND COMMON USE SPACES, AS REQUIRED BY NFPA 101: CHAPTER
 9, SECTION 9.6: FIRE DETECTION, ALARM. AND
 COMMUNICATION SYSTEMS. 9.6.3.6.1: THE GENERAL
 EVACUATION ALARM SIGNAL SHALL OPERATE THROUGHOUT THE
 ENTIRE BUILDING.
  
 2) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
 COMMENTS:
  
 1) THIS PERMIT IS BEING PROVISIONALLY APPROVED PENDING
 COMPLIANCE WITH ALL ITEMS ABOVE.
  
 2) UPDATE THE CODE LIST TO REFERENCE THE 5TH EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2012 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
  
 SUE ELLEN CALDERON
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 644-7326
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-06-22 Cont ID  
Sent By dhayes Date 2015-06-22 Time 11:35 Rev Time 0.00
Received By dhayes Date 2015-06-10 Time   Sent To  
Notes
2015-06-11 10:16:15SENT TO B 30.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-05-31 Cont ID  
Sent By tklarge Date 2015-05-31 Time 06:35 Rev Time  
Received By tklarge Date 2015-05-01 Time   Sent To  
Notes
2015-05-01 17:56:37B31

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2015-05-15 Cont ID  
Sent By jwitmer Date 2015-05-15 Time 06:29 Rev Time 0.00
Received By jwitmer Date 2015-05-15 Time 06:29 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-06-17 Cont ID  
Sent By C COLE Date 2015-06-17 Time 14:20 Rev Time 0.00
Received By ccole Date 2015-06-17 Time 14:20 Sent To E
Notes
2015-06-17 14:30:31PROVISIO:
 SITE SPECIFIC WIND LOAD ENGINEERING FOR TIE-DOWN OF THE
 RTU AND RTU CURB SHALL BE ON SITE AT TIME OF
 INSPECTION.
 STRUCTURAL REVISION WILL BE REQUIRED FOR ANY
 MODIFICATIONS TO THE EXISTING ROOF STRUCTURE.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-05-28 Cont ID  
Sent By ccole Date 2015-05-28 Time 09:12 Rev Time 0.00
Received By ccole Date 2015-05-28 Time 09:12 Sent To E
Notes
2015-05-28 09:13:571ST REVIEW: FBC 2010 MECHANICAL
  
 1) PROVIDE A VENTILATION CALCULATION FOR THE PROPOSED
 OCCUPANCY PER TABLE 403.3 FMC-10.
 INDICATE HOW MUCH AIR WILL BE PROVIDED BY THE NEW
 RTU-1.
 2) PROVIDE AC LOAD CALCULATIONS FOR RTU-1 IN ACCORDANCE
 WITH PROCEDURES DESCRIBED IN ASHRAE/ACCA STANDARD 183
 OR ACCA MANUAL N- SECTION 503.2.1 FBC-10 ENERGY.
 3) SHEET M-1: AUTOMATIC SHUTOFF DAMPERS AND CONTROLS
 FOR THE O/A SUPPLIES ARE REQUIRED FOR THE TWO AC
 SYSTEMS IN COMPLIANCE WITH SECTION 503.2.4.4 FBC-10
 ENERGY. PROVIDE DETAILS AND OPERATION SEQUENCE ON THE
 PLAN.
 4) M-1: RETURN AIR IS BEING TRANSFERRED FROM THE BREAK
 ROOM AND OTHER ROOMS AND OFFICES INTO THE CORRIDORS,
 HOWEVER A CORRIDOR CANNOT BE USED TO RETURN AIR TO THE
 UNIT- SECTION 601.2 FMC-10. PROVIDE DUCTED RETURNS FROM
 THESE ROOMS.
 5) M-1: SHOW THE DUCT SMOKE DETECTOR TEST STATIONS AND
 DESCRIBE FAN SHUT DOWN PROCEDURE OR SEQUENCE OF
 OPERATION.
 6) M-2: WIND LOAD DESIGN CRITERIA- THE ENGINEER OF
 RECORD SHALL VERIFY THE RTU AND FAN ROOF TIE-DOWN
 DETAILS WILL WITHSTAND 170 MPH WIND LOAD AND ASSOCIATED
 LATERAL AND UPLIFT PRESSURES.
 7) M-2: PROVIDE TWO COPIES OF A MIAMI-DADE NOA OR FL.
 PRODUCT APPROVAL FOR THE EXHAUST FAN ON THE ROOF.
 8) M-2: PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE NEW
 RTU: SHOW TYPE AND SIZE OF PIPING, PIPING RUN, PIPING
 SUPPORT, PIPING PROTECTION FROM EXPOSURE, AND DISCHARGE
 LOCATION.
 9) M-2: INDICATE THE THICKNESS AND R-VALUE OF DUCT
 INSULATION- TABLE 503.2.7.1 FBC-10 ENERGY.
  
 CHRISTOPHER COLE
 MECHANICAL PLANS EXAMINER
 (561) 805-6719
 [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-05-31 Cont ID  
Sent By tklarge Date 2015-05-31 Time 06:34 Rev Time 0.00
Received By tklarge Date 2015-05-31 Time 05:20 Sent To  
Notes
***NONE***