| 2015-06-06 16:01:27 | BUILDING PLAN REVIEW |
| | SUBMITTAL : 15041155 |
| | PERMIT: 14080059 |
| | ADD: 5660 N MILITARY TRL. |
| | CONT: SISCA |
| | TEL: (561)228-7503 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2ND REVIEW |
| | DATE: SAT. JUNE 06/ 2015 |
| | ACTION: DENIED |
| | |
| | NOTES FROM PERMIT : 14080059/ PROVISO: DEFERRED |
| | SUBMITTALS: FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS |
| | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(A) EXTERIOR DOOR/ STOREFRONT |
| | (B) WINDOWS/ STOREFRONT |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES , 3 FT. PARAPET, |
| | MAY REQUIRE ENHANCED FASTENING IN ROOF ZONES 2 -63.8 |
| | PSF @ 15 FT. (NO ZONE 3 / 3 FT PARAPET). |
| | ******************************************************* |
| | ******************************************************* |
| | ****************************************************** |
| | |
| | NOTICE: CHAPTER 553.80(2)(B) FLORIDA STATUTES STATES |
| | THAT A LOCAL GOVERNMENT SHALL IMPOSE A FEE OF FOUR |
| | TIMES THE FEE FOR PLAN REVIEW, IF PLANS ARE REJECTED |
| | (3) OR MORE TIMES FOR REPEATED FAILURE TO CORRECT A |
| | CODE VIOLATION. |
| | |
| | |
| | |
| | DENIED COMMENT # 1/ REPEAT |
| | 1) THE PRODUCT APPROVALS HAVE NOT BEEN SUBMITED TO |
| | DATE. |
| | (2) COPIES OF SHOP DRAWINGS FOR US ALUMINUM IG500 |
| | SUBMITTED BUT NO PRODUCT APPROVALS!!!! |
| | (1) COPY OF SHOP DRAWINGS STORE FRONT US ALULINUM |
| | IG500/ IG600 SERIE, NO PRODUCT APPROVALS!!!!!!! |
| | |
| | DENIED COMMENT # 2/ REPEAT |
| | 2) ROOFING APPROVALS SUBMITTED: |
| | BILCO ROOF HATCH NOA:14-0708.07 THERE ARE 10 TECHNICAL |
| | SHEETS FOR THIS PRODUCT APPROVAL, ONLY SHEET 6 OF 10 |
| | WAS SUBMITTED, AND THAT SHEET DOES NOT HAVE THE |
| | PRESSURE RATING FOR THIS UNIT. |
| | |
| | DENIED COMMENT # 3/ REPEAT |
| | ROOFING: FL9930-R6 JOHN MANVILLE SINGLE PLY APPENDIX |
| | SHEET 1 SUB-SYSTEM 2C-1 HIGHLIGHTED, SHEET 10 |
| | SUB-SYSTEM S-38 MAXIMUM DESIGN PRESSURE -45.0. |
| | SEE PROVISO FROM ISSUED PERMIT 14080059, THE PRESSURES |
| | IN ZONE # 2 & 3 REQUIRE -63.8. SEE PAGE 2 OF THE |
| | APPENDIX ROOFING REPORT NOTE # 9 FOR MECHANICALLY |
| | ATTACHED COMPONENTS. REQUIRES CALCULATIONS FROM AN |
| | ARCHITECT OR ENGINEER. |
| | |
| | JAMES WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: (561) 805-6715 |
| | FAX: (561)805-6676 |
| | E-MAIL: [email protected] |
| | DEVELOPMENT SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | |
| | |