| | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15041121 |
| | ADD: 1616 N FLORIDA MANGO |
| | CONT: MARYJULI |
| | TEL: ( 561)386-6032 |
| | E-MAIL: [email protected] |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: |
| | ACTION: DENIED |
| | |
| | 1) SHEET A1 PLEASE SHOW COMPLIANCE WITH 2010 FBC-B |
| | 416.7 SPRAY ROOMS SHALL BE SEPARATED BY 1 HOUR |
| | SEPARATION FIRE BARRIERS. |
| | |
| | 2) SHEET A1 PLEASE SHOW COMPLIANCE WITH 2010 FBC-B |
| | 416.7 SPRAY ROOMS. FLOORS SHALL BE WATER-PROOFED AND |
| | DRAINED IN AN APPROVED MANNER. |
| | |
| | 3) SHOW COMPLIANCE WITH FBC-B 416.3 SPRAYING SURFACES. |
| | SPRAYING SPACES SHALL BE VENTILATED WITH AN EXHAUST |
| | SYSTEM TO PREVENT THE ACCUMULATION OF FLAMMABLE MIST OR |
| | VAPORS IN ACCORDANCE WITH THE FBC-MECHANICAL CODE. |
| | |
| | 4) SHOW COMPLIANCE WITH 416.4 SPRAY BOOTHS SHALL BE |
| | DESIGNED, CONSTRUCTED AND OPERATED IN ACCORDANCE THE |
| | FLORIDA FIRE PREVENTION CODE. NFPA 33. |
| | |
| | 5) THE PLANS NEED TO SHOW COMPLIANCE WITH: FBC-B 416.5. |
| | A AUTOMATIC FIRE EXTINGUISHING SYSTEM. |
| | |
| | 6) THE PLANS WILL NEED TO SHOW COMPLIANCE WITH HOW THE |
| | ROOFTOP VENTS WILL BE ATTACHED/ ANCHORED TO RESIST THE |
| | MOMENT OF OVERTURNING IN A 170 VULT MPH/ 3 SECOND GUST |
| | WIND. THE ROOFTOP EXHAUST IS CONSIDERED COMPONENTS AND |
| | CLADDING. |
| | 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN- |
| | CHAPTER 6 OF ASCE 7-10. |
| | 1609.3 BASIC WIND SPEED FIGURE 1609.A-C |
| | 1609.3 WIND SPEED CONVERSION |
| | |
| | 6.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.3.1 & ASCE 7-10 |
| | |
| | 6.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10. |
| | |
| | 6.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.4 & ASCE 7-10 |
| | |
| | 6.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * |
| | SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10. |
| | |
| | 6.5) COMPONENTS & CLADDING PRESSURES POSITIVE & |
| | NEGATIVE TABLE 1609.2(2) . |
| | |
| | 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |