Plan Review Details - Permit 15041105
Plan Review Stops For Permit 15041105
Review Stop E ELECTRICAL
Rev No 1 Status N Date 2015-05-01 Cont ID  
Sent By plumbing Date 2015-05-01 Time 10:49 Rev Time 0.00
Received By dhayes Date 2015-05-01 Time 10:49 Sent To G
Notes
2015-05-01 10:59:50NO ELECTRICAL PLAN HAS BEEN INCLUDED IN THE SUBMITTAL
 PACKAGE. NO ELECTRICAL REVIEW HAS BEEN PERFORMED AT
 THIS TIME. AN ELECTRICAL PERMIT IS REQUIRED FOR AN
 ELECTRICAL CONTRACTOR TO COMPLETE THE ELECTRICAL WIRING
 REQUIRED FOR THE IGNITER CIRCUIT IN GAS APPLIANCES.
  
 1) PROVIDE AN ELECTRICAL PERMIT APPLICATION WITH A
 FLOOR PLAN AND A PANEL SCHEDULE INDICATING THE
 ELECTRICAL CIRCUITS AND DISCONNECTS REQUIRED FOR THE
 NEW GAS APPLIANCES WITH ELECTRONIC IGNITER CIRCUITS.
 NEC 422.31
  
 2) PROVIDE ADDITIONAL INFORMATION ON THE FLOOR PLAN AND
 PANEL SCHEDULE THAT INDICATE THE DEMOLITION OF THE
 ASSUMED PREVIOUSLY EXISTING STORAGE WATER HEATER. WPB
 AMENDMENTS TO THE FBC 107.3.2
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2015-05-03 Cont ID  
Sent By tklarge Date 2015-05-03 Time 04:32 Rev Time 0.00
Received By tklarge Date 2015-05-03 Time 04:07 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-05-03 Cont ID  
Sent By tklarge Date 2015-05-03 Time 04:32 Rev Time 0.00
Received By tklarge Date 2015-04-29 Time 10:49 Sent To  
Notes
***NONE***