Plan Review Details - Permit 15041065
Plan Review Stops For Permit 15041065
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-06-05 Cont ID  
Sent By jwitmer Date 2015-06-05 Time 06:25 Rev Time 0.00
Received By jwitmer Date 2015-06-04 Time 12:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-05-27 Cont ID  
Sent By jwitmer Date 2015-05-27 Time 09:34 Rev Time 0.00
Received By jwitmer Date 2015-05-27 Time 09:33 Sent To  
Notes
2015-05-27 09:43:07BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15041065
 ADD: 529 S. FLAGLER DR. SUITE # 18-H
 CONT: CAMBRIDGE CONSTRUCTION
 TEL: (561)784-3722
 E-MAIL:[email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
  
  
 NOTICE:!!!!!!!!!!!!!!!!!!!!!!!!!! CHAPTER 553.80(2)(B)
 FLORIDA STATUTES STATES THAT A LOCAL GOVERNMENT SHALL
 IMPOSE A FEE OF FOUR TIMES THE FEE FOR PLAN REVIEW, IF
 PLANS ARE REJECTED (3) OR MORE TIMES FOR REPEATED
 FAILURE TO CORRECT A CODE VIOLATION.
  
  
  
 2ND REVIEW
 DATE: MON. MAY 27/2015
 ACTION: DENIED
  
 1) 2ND REQUEST. A NEW FLOOR PLANS WAS SUBMITTED WITH
 THE ARCHITECT OF RECORDS OWN SEAL, BUT THE SHEETS 1 OF
 2 FOR WINDOW PLACEMENT, CUSTOM MULLION AND WIND DESIGN
 NOT REPLACED, STILL HAS THE CERTIFICATE OF
 AUTHORIZATION SEAL. L DESIGN FOR WIND BY RAYOMND
 CHLADNY ARCHITECT, NOTE THE DESIGNER OF RECORD SEALED
 THE PLANS WITH HIS AA CERTIFICATE OF AUTHORITY SEAL. 61
 G 1-16.003 USES OF SEAL. EFFECTIVE 04/18/2000 THE
 PERSONAL SEAL, SIGNATURE AND DATE OF THE ARCHITECT OR
 INTERIOR DESIGNER SHALL APPEAR ON ALL ARCHITECTURAL OR
 INTERIOR DESIGN DOCUMENTS TO BE FILED FOR PUBLIC RECORD
 AND SHALL BE CONSTRUED TO OBLIGATE HIS PARTNERS OR HIS
 CORPORATION. A CORPORATE SEAL ALONE IS INSUFFICIENT.
 DOCUMENTS SHALL BE SIGNED PERSONALLY AND SEALED BY THE
 RESPONSIBLE ARCHITECT
  
 2) 2ND REQUEST. PLEASE NOTE THE WIND DESIGGN CRITERIA
 WAS PROVIDED, WHAT WAS NOT PROVIDED WAS THE SIZE OF THE
 WINDOWS AND DOORS NOR WHERE ZONE 4 AND 5 START AND END.
 THE PRESSUES NEED TO ALIGN WITH THE SIZE OF OPENING AND
 ZONE EITHER 4 OR 5. PLEASE PROVIDE THE ACTUAL SIZES OF
 THE WINDOWS AND SLIDERS TO BE INSTALLED. NOTE, FOR THE
 SLIDDING GLASS DOORS, IDENTIFY THE SIZES OF PANELS
 LOCATED ON SHEET 7 OF THE PRODUCT APPROVAL. CIRCLE THE
 SIZE OF THE PANEL, TYPE OF GLAZING, AND SILL HEIGHT
 THAT GOVERNS EACH CHART.
  
  
 3) 2ND REQUEST. 2010 FBC 107.3.4.1 PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE
 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 4) 2ND REVIEW SUPER SAM 125 SALES BROCHURE WAS
 SUBMITTED, NO TESTING, SUPER SAM 125 HAS A IIC RATING
 OF 49, MINIMUM REQUIRED IS 50. PLEASE PROVIDE TESTING
 FOR CODE COMPLIANCE FOR FLOOR INSULATION: BLDG TYPE:
 TYPE I/ TYPE II FLOOR INSULATION
  
 4A) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 4B) FBC-B 2010 1207.2 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 5) FLAME SPREAD- FBC-B 2010 603.1.2 EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 703.4 NONCOMBUSTIBILITY TESTS.
 THE TESTS INDICATED IN SECTIONS 703.4.1 AND 703.4.2
 SHALL SERVE AS CRITERIA FOR ACCEPTANCE OF BUILDING
 MATERIALS AS SET FORTH IN SECTIONS 602.2, 602.3 AND
 602.4 IN TYPE I, II, III AND IV CONSTRUCTION. THE TERM
 ?NONCOMBUSTIBLE? DOES NOT APPLY TO THE FLAME SPREAD
 CHARACTERISTICS OF INTERIOR FINISH OR TRIM MATERIALS. A
 MATERIAL SHALL NOT BE CLASSIFIED AS A NONCOMBUSTIBLE
 BUILDING CONSTRUCTION MATERIAL IF IT IS SUBJECT TO AN
 INCREASE IN COMBUSTIBILITY OR FLAME SPREAD BEYOND THE
 LIMITATIONS HEREIN ESTABLISHED THROUGH THE EFFECTS OF
 AGE, MOISTURE OR OTHER ATMOSPHERIC CONDITIONS.
  
 703.4.1 ELEMENTARY MATERIALS.
 MATERIALS REQUIRED TO BE NONCOMBUSTIBLE SHALL BE TESTED
 IN ACCORDANCE WITH ASTM E 136.
  
 703.4.2 COMPOSITE MATERIALS.
 MATERIALS HAVING A STRUCTURAL BASE OF NONCOMBUSTIBLE
 MATERIAL AS DETERMINED IN ACCORDANCE WITH SECTION
 703.4.1 WITH A SURFACING NOT MORE THAN 0.125 INCH (3.18
 MM) THICK THAT HAS A FLAME SPREAD INDEX NOT GREATER
 THAN 50 WHEN TESTED IN ACCORDANCE WITH ASTM E 84 OR UL
 723 SHALL BE ACCEPTABLE AS
 NONCOMBUSTIBLE MATERIALS.
  
 6) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 107.3.5
 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. THE
 EXAMINATION OF THE DOCUMENTS BY THE BUILDING OFFICIAL
 SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA AND
 DOCUMENTS: A FLOOR PLAN.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-05-04 Cont ID  
Sent By jwitmer Date 2015-05-04 Time 15:55 Rev Time  
Received By jwitmer Date 2015-05-04 Time   Sent To  
Notes
2015-05-04 15:55:33BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15041065
 ADD: 529 S. FLAGLER DR. SUITE # 18-H
 CONT: CAMBRIDGE CONSTRUCTION
 TEL: (561)784-3722
 E-MAIL:[email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. MAY 04/2015
 ACTION: DENIED
  
 IMPORTANT NOTICE: EFFECTIVE JUNE 01, 2015
 ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED
 ELECTRONICALLY
 UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS
 SUBMISSION OPTIONS ARE AS FOLLOWS:
 1 UPLOAD VIA THE PROJECT DOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL
 SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED
 NAMING CONVENTION FOR EACH DOCUMENT
 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER
 DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE
 REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT
 TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS
 ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES
 AVAILABLE.
  
 1) DESIGN FOR WIND BY RAYOMND CHLADNY ARCHITECT, NOTE
 THE DESIGNER OF RECORD SEALED THE PLANS WITH HIS AA
 CERTIFICATE OF AUTHORITY SEAL. 61 G 1-16.003 USES OF
 SEAL. EFFECTIVE 04/18/2000 THE PERSONAL SEAL, SIGNATURE
 AND DATE OF THE ARCHITECT OR INTERIOR DESIGNER SHALL
 APPEAR ON ALL ARCHITECTURAL OR INTERIOR DESIGN
 DOCUMENTS TO BE FILED FOR PUBLIC RECORD AND SHALL BE
 CONSTRUED TO OBLIGATE HIS PARTNERS OR HIS CORPORATION.
 A CORPORATE SEAL ALONE IS INSUFFICIENT. DOCUMENTS SHALL
 BE SIGNED PERSONALLY AND SEALED BY THE RESPONSIBLE
 ARCHITECT
  
 2) PLEASE NOTE THE WIND DESIGGN CRITERIA WAS PROVIDED,
 WHAT WAS NOT PROVIDED WAS THE SIZE OF THE WINDOWS AND
 DOORS NOR WHERE ZONE 4 AND 5 START AND END.
 THE PRESSUES NEED TO ALIGN WITH THE SIZE OF OPENING AND
 ZONE EITHER 4 OR 5.
  
  
 3) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 4) PLEASE PROVIDE TESTING FOR CODE COMPLIANCE FOR FLOOR
 INSULATION: BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION
  
 4A) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 4B) FBC-B 2010 1207.2 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 5) FLAME SPREAD- FBC-B 2010 603.1.2 EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 703.4 NONCOMBUSTIBILITY TESTS.
 THE TESTS INDICATED IN SECTIONS 703.4.1 AND 703.4.2
 SHALL SERVE AS CRITERIA FOR ACCEPTANCE OF BUILDING
 MATERIALS AS SET FORTH IN SECTIONS 602.2, 602.3 AND
 602.4 IN TYPE I, II, III AND IV CONSTRUCTION. THE TERM
 ?NONCOMBUSTIBLE? DOES NOT APPLY TO THE FLAME SPREAD
 CHARACTERISTICS OF INTERIOR FINISH OR TRIM MATERIALS. A
 MATERIAL SHALL NOT BE CLASSIFIED AS A NONCOMBUSTIBLE
 BUILDING CONSTRUCTION MATERIAL IF IT IS SUBJECT TO AN
 INCREASE IN COMBUSTIBILITY OR FLAME SPREAD BEYOND THE
 LIMITATIONS HEREIN ESTABLISHED THROUGH THE EFFECTS OF
 AGE, MOISTURE OR OTHER ATMOSPHERIC CONDITIONS.
  
 703.4.1 ELEMENTARY MATERIALS.
 MATERIALS REQUIRED TO BE NONCOMBUSTIBLE SHALL BE TESTED
 IN ACCORDANCE WITH ASTM E 136.
  
 703.4.2 COMPOSITE MATERIALS.
 MATERIALS HAVING A STRUCTURAL BASE OF NONCOMBUSTIBLE
 MATERIAL AS DETERMINED IN ACCORDANCE WITH SECTION
 703.4.1 WITH A SURFACING NOT MORE THAN 0.125 INCH (3.18
 MM) THICK THAT HAS A FLAME SPREAD INDEX NOT GREATER
 THAN 50 WHEN TESTED IN ACCORDANCE WITH ASTM E 84 OR UL
 723 SHALL BE ACCEPTABLE AS
 NONCOMBUSTIBLE MATERIALS.
  
 6) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 107.3.5
 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. THE
 EXAMINATION OF THE DOCUMENTS BY THE BUILDING OFFICIAL
 SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA AND
 DOCUMENTS: A FLOOR PLAN.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2015-05-19 Cont ID  
Sent By rlecky Date 2015-05-19 Time 13:13 Rev Time 0.00
Received By rlecky Date 2015-05-19 Time 13:10 Sent To  
Notes
2015-05-19 13:14:12NO ELECTRICAL PROPOSED IN SCOPE OF WORK

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-05-15 Cont ID  
Sent By pleduc Date 2015-05-15 Time   Rev Time 0.00
Received By pleduc Date 2015-05-15 Time 15:00 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-05-05 Cont ID  
Sent By pleduc Date 2015-05-05 Time   Rev Time 0.00
Received By pleduc Date 2015-05-05 Time 15:15 Sent To  
Notes
2015-05-05 15:24:23THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THERE IS INSUFFICIENT DETAIL TO DETERMINE IF THE
 PROPOSED PROJECT WILL AFFECT THE EXISTING FIRE
 SPRINKLERS OR FIRE ALARM DEVICES.
  
 PROVIDE A NOTE AND DRAWNING INDICATING A REVIEW OF EACH
 ROOM/SPACE AND THE LOCATION OF THE LIFE SAFETY DEVICE.
 ALL DEVICES SHALL BE PROTECTED FROM DMAGE AND/OR PAINT
 OVERSPRAY.
  
 ADDRESS BUILDING DEPARTMENT COMMENTS.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-06-05 Cont ID  
Sent By jwitmer Date 2015-06-05 Time 06:25 Rev Time 0.00
Received By jwitmer Date 2015-05-29 Time   Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-05-27 Cont ID  
Sent By jwitmer Date 2015-05-27 Time 09:34 Rev Time 0.00
Received By jwitmer Date 2015-05-27 Time 08:50 Sent To  
Notes
2015-05-27 08:50:36TO JW DESK.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-05-26 Cont ID  
Sent By tklarge Date 2015-05-26 Time 12:58 Rev Time 0.00
Received By tklarge Date 2015-04-29 Time 07:43 Sent To  
Notes
2015-04-30 07:42:31B23
 TRAVELLING WITH 15041067

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-05-26 Cont ID  
Sent By tklarge Date 2015-05-26 Time 12:57 Rev Time 0.00
Received By tklarge Date 2015-05-26 Time 12:41 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2015-05-07 Cont ID  
Sent By ajones Date 2015-05-07 Time 16:31 Rev Time 0.00
Received By ajones Date 2015-05-07 Time 16:31 Sent To  
Notes
***NONE***