| 2015-05-28 20:11:50 | 5/28/2015 |
| | PROJECT: GLUE PRODUCTS |
| | PERMIT#: 15041011 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1. PROVIDE THE CIRCUITRY ON THE FLOOR PLAN TO COINCIDE |
| | WITH THE REQUIRED PANEL SCHEDULE AS WELL AS A RISER |
| | DIAGRAM AND LOAD CALCULATION. FBC 107.3.5 ELECTRICAL |
| | |
| | 2. PROVIDE COMPLETE CIRCUIT DIRECTORIES FOR ELECTRICAL |
| | PANELS. EVERY CIRCUIT SHALL BE LEGIBLY IDENTIFIED AS TO |
| | ITS CLEAR, EVIDENT, AND SPECIFIC PURPOSE OR USE. NEC |
| | 408.4 |
| | |
| | 3. INDICATE THE REQUIRED LIGHTING CONTROLS FOR INTERIOR |
| | AND EXTERIOR ILLUMINATION. LIGHTING SYSTEMS SHALL BE |
| | PROVIDED WITH CONTROLS AS REQUIRED IN FBC-ENERGY |
| | CONSERVATION SECTIONS 505 ELECTRICAL POWER & LIGHTING |
| | SYSTEMS (MANDATORY). |
| | |
| | 4. INDICATE THE REQUIRED LIGHTING ABOUT ELECTRICAL |
| | EQUIPMENT. ILLUMINATION SHALL BE PROVIDED FOR ALL |
| | WORKING SPACES ABOUT ELECTRICAL PANELS AND EQUIPMENT. |
| | NEC 110.26 (D) |
| | |
| | 5. VERIFY SAFETY LABELING FOR ARC FLASH PROTECTION FOR |
| | THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC |
| | 110.16 |
| | |
| | 6. INDICATE ALL REQUIRED EMERGENCY ILLUMINATION. |
| | EMERGENCY ILLUMINATION SHALL INCLUDE ALL REQUIRED MEANS |
| | OF EGRESS LIGHTING, ILLUMINATED EXIT SIGNS, AND ALL |
| | OTHER LIGHTS SPECIFIED AS NECESSARY TO PROVIDE REQUIRED |
| | ILLUMINATION. NEC 700.16(F) |
| | |
| | 7. PROVIDE THE LOCATION OF ALL MECHANICAL EQUIPMENT |
| | WITH ASSOCIATED REQUIRED DISCONNECTS AND GFI OUTLETS. |
| | NEC 210.63, 210.8(A)(3), NEC 440.14 |
| | |
| | 8. INDICATE PROVISIONS FOR THE REQUIRED SIGN CIRCUIT |
| | AND SHOW WINDOW LIGHTING. NEC 210.62, 600.5(A) |
| | |
| | SEPARATE ELECTRICAL PERMIT ACCOMPANIED BY |
| | MANUFACTURER'S EQUIPMENT SUBMITTALS REQUIRED FOR |
| | ELECTRICAL WORK |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | |
| | MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER, PX3353, |
| | 561-805-7943 OR [email protected] |
| | |