Plan Review Details - Permit 15041010
Plan Review Stops For Permit 15041010
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-06-25 Cont ID  
Sent By jwitmer Date 2015-06-25 Time 13:14 Rev Time 0.00
Received By jwitmer Date 2015-06-25 Time 12:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-06-12 Cont ID  
Sent By jwitmer Date 2015-06-12 Time 09:02 Rev Time 0.00
Received By jwitmer Date 2015-06-12 Time 07:15 Sent To Z
Notes
2015-06-12 08:33:09BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15041010
 ADD: 4015 GEOGIA AVE
 CONT: FLORIDA FILTRATION & SPRAY BOOTH
 TEL: (561)582-5543
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. JUNE 12/ 2015
 ACTION: DENIED
  
 1) DISCREPANCY IN PLANS. THE PERMIT APPLICATION
 INDICATES THE WORK DESCRIBED UNDER THIS PREMIT AS THE
 INSTALATION OF A PAINT SPRAY BOOTH. NOTE THE PLANS
 INDICATE THE INSTALATION OF A MIXING ROOM. PLEASE
 CORRECT THE DISCREPANCY. FOR THIS REVIEW, I WILL BE
 REVIEWING THE PLANS AS INDICATED UNDER THE PERMIT
 DESCIPTION, A SPRAY BOOTH.
  
 2) SHEET B-2 SHOWS A ROOF PENETRATION BUT THERE IS NO
 DETAIL OF THE ADDITIONAL FRAMING AROUND THE NEW
 OPENING, ROOF CURB OR FLASHING DETAILS, PLANS INDICATE
 THE ROOF TOP EXHAUST IS GOOD FOR 170 MPH, NO ADDITIONAL
 SUPPORT IS REQUIRED. FBC-B 1609.4.2.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2015-07-13 Cont ID  
Sent By albarran Date 2015-07-13 Time 19:06 Rev Time 0.00
Received By albarran Date 2015-07-13 Time 18:32 Sent To I
Notes
2015-07-13 19:08:41AFTER DISCUSSING THE SCOPE OF WORK W/LIGHTNING
 ELECTRIC, NOT ALL OF THE PRIOR PLAN REVIEW COMMENTS ARE
 APPLICABLE. ALL THAT WAS REQUIRED WAS PRESENTED AND
 APPROVED TODAY.

Review Stop E ELECTRICAL
Rev No 3 Status N Date 2015-06-30 Cont ID  
Sent By albarran Date 2015-06-30 Time 14:27 Rev Time 0.00
Received By albarran Date 2015-06-30 Time 13:53 Sent To Z
Notes
2015-06-30 14:30:32PER A TELEPHONE CONVERSATION WITH TOM DRAKE OF
 LIGHTNING ELECTRIC, THIS PERMIT IS BEING ISSUED WITHOUT
 ELECTRIC SO THAT THE STRUCTURAL CAN PROCEED. EC WILL
 SUBMIT FOR THE ELECTRIC PRIOR TO COMMENCEMENT OF ANY
 ELECTRICAL WORK.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-06-23 Cont ID  
Sent By albarran Date 2015-06-23 Time 10:10 Rev Time 0.00
Received By albarran Date 2015-06-23 Time 08:54 Sent To  
Notes
2015-06-23 09:47:536/23/2015
 PROJECT: GLUE PRODUCTS
 PERMIT#: 15041010
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC,
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 2ND ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 BELOW IS THE LIST OF ITEMS REQUESTED ON THE FIRST
 REVIEW ALONG WITH THE ITEMS PROVIDED ON YOUR
 RE-SUBMITTAL. AS NOTED, THERE IS A DEFICIENCY AND NOT
 UNTIL ALL ITEMS ARE PROVIDED WILL THIS PERMIT BE
 APPROVED. THE RISER DIAGRAM YOU PROVIDED DOES NOT MATCH
 THE ONE ON THE PLANS. IF THE ONE ON THE PLANS IS
 INCORRECT, PLEASE CROSS IT OUT. PER NEC REQUIREMENTS
 YOU SHALL PROVIDE A LOAD CALC OF THE4 EXISTING TO
 ASCERTAIN THAT THE SERVICE WILL ABSORB THE ADDED LOAD
 PROPERLY.
  
  
 MISSING 1. PROVIDE THE CIRCUITRY ON THE FLOOR PLAN TO
 COINCIDE WITH THE REQUIRED PANEL SCHEDULE AS WELL AS A
 RISER DIAGRAM AND LOAD CALCULATION. FBC 107.3.5
 ELECTRICAL
  
 MISSING 2. PROVIDE COMPLETE CIRCUIT DIRECTORIES FOR
 ELECTRICAL PANELS. EVERY CIRCUIT SHALL BE LEGIBLY
 IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND SPECIFIC
 PURPOSE OR USE. NEC 408.4
  
 MISSING 3. INDICATE THE REQUIRED LIGHTING CONTROLS FOR
 INTERIOR AND EXTERIOR ILLUMINATION. LIGHTING SYSTEMS
 SHALL BE PROVIDED WITH CONTROLS AS REQUIRED IN
 FBC-ENERGY CONSERVATION SECTIONS 505 ELECTRICAL POWER &
 LIGHTING SYSTEMS (MANDATORY).
  
 MISSING 4. INDICATE THE REQUIRED LIGHTING ABOUT
 ELECTRICAL EQUIPMENT. ILLUMINATION SHALL BE PROVIDED
 FOR ALL WORKING SPACES ABOUT ELECTRICAL PANELS AND
 EQUIPMENT. NEC 110.26 (D)
  
 MISSING 5. VERIFY SAFETY LABELING FOR ARC FLASH
 PROTECTION FOR THE PANEL BOARDS AND MAIN DISCONNECTING
 MEANS. NEC 110.16
  
 MISSING 6. INDICATE ALL REQUIRED EMERGENCY
 ILLUMINATION. EMERGENCY ILLUMINATION SHALL INCLUDE ALL
 REQUIRED MEANS OF EGRESS LIGHTING, ILLUMINATED EXIT
 SIGNS, AND ALL OTHER LIGHTS SPECIFIED AS NECESSARY TO
 PROVIDE REQUIRED ILLUMINATION. NEC 700.16(F)
  
 INCOMPLETE 7. PROVIDE THE LOCATION OF ALL MECHANICAL
 EQUIPMENT WITH ASSOCIATED REQUIRED DISCONNECTS AND GFI
 OUTLETS. NEC 210.63, 210.8(A)(3), NEC 440.14, THE FIRE
 PLAN DOES HAVE AN INDICATION OF THE LOCATION, BUT IT
 DOES NOT COMPLY WITH THE ELECTRICAL REQUIREMENTS.
  
 MAY NOT BE NECESSARY AS ONLY THE MIX ROOMS ARE BEING
 ADDED TO THE EXISTING LOCATION 8. INDICATE PROVISIONS
 FOR THE REQUIRED SIGN CIRCUIT AND SHOW WINDOW LIGHTING.
 NEC 210.62, 600.5(A)
  
 COMPLETE (15060821) 9. SEPARATE ELECTRICAL PERMIT
 ACCOMPANIED BY MANUFACTURER?S EQUIPMENT SUBMITTAL
 REQUIRED, FOR ELECTRICAL WORK
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER, PX3353,
 561-805-7943 OR [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-05-28 Cont ID  
Sent By albarran Date 2015-05-28 Time 20:07 Rev Time 0.00
Received By albarran Date 2015-05-28 Time 19:04 Sent To B
Notes
2015-05-28 20:08:315/28/2015
 PROJECT: GLUE PRODUCTS
 PERMIT#: 15041010
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1. PROVIDE THE CIRCUITRY ON THE FLOOR PLAN TO COINCIDE
 WITH THE REQUIRED PANEL SCHEDULE AS WELL AS A RISER
 DIAGRAM AND LOAD CALCULATION. FBC 107.3.5 ELECTRICAL
  
 2. PROVIDE COMPLETE CIRCUIT DIRECTORIES FOR ELECTRICAL
 PANELS. EVERY CIRCUIT SHALL BE LEGIBLY IDENTIFIED AS TO
 ITS CLEAR, EVIDENT, AND SPECIFIC PURPOSE OR USE. NEC
 408.4
  
 3. INDICATE THE REQUIRED LIGHTING CONTROLS FOR INTERIOR
 AND EXTERIOR ILLUMINATION. LIGHTING SYSTEMS SHALL BE
 PROVIDED WITH CONTROLS AS REQUIRED IN FBC-ENERGY
 CONSERVATION SECTIONS 505 ELECTRICAL POWER & LIGHTING
 SYSTEMS (MANDATORY).
  
 4. INDICATE THE REQUIRED LIGHTING ABOUT ELECTRICAL
 EQUIPMENT. ILLUMINATION SHALL BE PROVIDED FOR ALL
 WORKING SPACES ABOUT ELECTRICAL PANELS AND EQUIPMENT.
 NEC 110.26 (D)
  
 5. VERIFY SAFETY LABELING FOR ARC FLASH PROTECTION FOR
 THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC
 110.16
  
 6. INDICATE ALL REQUIRED EMERGENCY ILLUMINATION.
 EMERGENCY ILLUMINATION SHALL INCLUDE ALL REQUIRED MEANS
 OF EGRESS LIGHTING, ILLUMINATED EXIT SIGNS, AND ALL
 OTHER LIGHTS SPECIFIED AS NECESSARY TO PROVIDE REQUIRED
 ILLUMINATION. NEC 700.16(F)
  
 7. PROVIDE THE LOCATION OF ALL MECHANICAL EQUIPMENT
 WITH ASSOCIATED REQUIRED DISCONNECTS AND GFI OUTLETS.
 NEC 210.63, 210.8(A)(3), NEC 440.14
  
 8. INDICATE PROVISIONS FOR THE REQUIRED SIGN CIRCUIT
 AND SHOW WINDOW LIGHTING. NEC 210.62, 600.5(A)
  
 SEPARATE ELECTRICAL PERMIT ACCOMPANIED BY
 MANUFACTURER?S EQUIPMENT SUBMITTALS REQUIRED, FOR
 ELECTRICAL WORK
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER, PX3353,
 561-805-7943 OR [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2015-06-29 Cont ID  
Sent By Lindow Date 2015-06-29 Time   Rev Time 0.00
Received By   Date 2015-06-29 Time   Sent To E
Notes
2015-06-29 15:26:50C9

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-06-09 Cont ID  
Sent By Lindow Date 2015-06-09 Time   Rev Time 0.00
Received By rlindow Date 2015-06-09 Time   Sent To M
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-05-13 Cont ID  
Sent By rlindow Date 2015-05-13 Time 11:29 Rev Time 0.00
Received By rlindow Date 2015-05-13 Time 11:28 Sent To  
Notes
2015-05-13 11:28:40PROVIDE QUANTITY AND CLASS OF FLAMMABLE LIQUIDS TO BE
 STORED IN MIXING ROOMS.
 PLAN SHOWS 3 DIFFERENT ROOMS, ADDRESS ALL 3.
 PROVIDE QUANTITY OF LARGEST CONTAINER(S) IN EACH ROOM.
  
 SHOW LOCATION OF SPRAY BOOTH IN THIS BUILDING.

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2015-07-13 Cont ID  
Sent By albarran Date 2015-07-13 Time 19:09 Rev Time 0.00
Received By albarran Date   Time   Sent To  
Notes
2015-07-13 19:13:017/13/15 - PASSED ELECTRICAL REVIEW AS NOTE4D.
 CONTRACTOR NOTIFIED VIA EMAIL. SENT TO SMALL READY BIN
 "F". MA

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2015-07-08 Cont ID  
Sent By albarran Date 2015-07-08 Time 08:45 Rev Time 0.00
Received By albarran Date   Time   Sent To  
Notes
2015-07-08 08:59:43ELECTRICAL PROVISO:
 IN AN EFFORT TO EXPEDITE THE CONSTRUCTION OF THIS
 PROJECT, THE PERMIT WAS ISSUED PENDING AN ELECTRICAL
 PERMIT. A REVISION TO THESE DRAWINGS, ADDRESSING ALL
 ELECTRICAL REQUIREMENTS PREVIOUSLY STATED TO BE
 SUBMITTED AT THE TIME OF ELECTRICAL PERMIT APPLICATION.
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2015-07-01 Cont ID  
Sent By skennedy Date 2015-07-01 Time 16:00 Rev Time 0.00
Received By skennedy Date 2015-06-24 Time 18:32 Sent To  
Notes
2015-06-30 14:25:59PULEED FROM B15 AND ROUTED TO M. ALBARRAN'S DSK FOR
 ELECTRICAL REVIEW.
2015-06-24 18:34:26TRAVELING W/ 15041011 SENT TO B15
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-06-23 Cont ID  
Sent By albarran Date 2015-06-23 Time 10:08 Rev Time 0.00
Received By skennedy Date 2015-06-23 Time 19:08 Sent To  
Notes
2015-06-23 10:10:40I CALLED FLORIDA FILTRATION AND LEFT A MESSAGE, ALSO
 SPOKE W/LENEE OF LIGHTNING ELECTRIC. EC WILL WORK ON
 THEIR SUBMITTAL, BUT I SEE THEY ARE STILL MISSING
 ZONING REQUIREMENTS SO I RETURNED THIS TO SMALL DENIED
 "F"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-06-12 Cont ID  
Sent By   Date 2015-06-12 Time   Rev Time 0.00
Received By shill Date 2015-05-28 Time 18:32 Sent To  
Notes
2015-05-28 18:32:31B02
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-05-28 Cont ID  
Sent By shill Date 2015-05-13 Time 18:03 Rev Time 0.00
Received By shill Date 2015-04-27 Time   Sent To  
Notes
2015-04-27 15:38:11MECHANICAL OVER 5K

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-06-10 Cont ID  
Sent By ccole Date 2015-06-10 Time 13:41 Rev Time 0.00
Received By ccole Date 2015-06-10 Time 13:41 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-05-07 Cont ID  
Sent By hmoser Date 2015-05-07 Time 15:28 Rev Time 0.00
Received By hmoser Date 2015-05-07 Time 14:33 Sent To  
Notes
2015-05-07 15:28:27PLAN DENIED
 EXHAUST DUCT SHALL TERMINATE 6 FT. ABOVE THE ROOF.
 PER NFPA 33 AND 501.2.1 LOCATION OF EXHAUST OUTLETS.
 2010 FBC (M)
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  

Review Stop Z ZONING
Rev No 2 Status P Date 2015-07-01 Cont ID  
Sent By sgraham Date 2015-07-01 Time 15:00 Rev Time 0.00
Received By sgraham Date 2015-07-01 Time 15:00 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2015-06-12 Cont ID  
Sent By sgraham Date 2015-06-12 Time 10:22 Rev Time 0.00
Received By sgraham Date 2015-06-12 Time 10:22 Sent To  
Notes
2015-06-12 10:23:116/12/15 ZONING FAILED
  
 1. SUBMIT TWO UP TO DATE SURVEYS SHOWING THE LOCATION
 OF THE SPRAY BOOTH