| Plan Review Stops For Permit 15041010 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2015-06-25 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2015-06-25 |
Time |
13:14 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2015-06-25 |
Time |
12:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2015-06-12 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2015-06-12 |
Time |
09:02 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2015-06-12 |
Time |
07:15 |
Sent To |
Z |
|
| Notes |
| 2015-06-12 08:33:09 | BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 15041010 | | | ADD: 4015 GEOGIA AVE | | | CONT: FLORIDA FILTRATION & SPRAY BOOTH | | | TEL: (561)582-5543 | | | E-MAIL: [email protected] | | | | | | 2010 FLORIDA BUILDING CODE W | | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | 1ST REVIEW | | | DATE: FRI. JUNE 12/ 2015 | | | ACTION: DENIED | | | | | | 1) DISCREPANCY IN PLANS. THE PERMIT APPLICATION | | | INDICATES THE WORK DESCRIBED UNDER THIS PREMIT AS THE | | | INSTALATION OF A PAINT SPRAY BOOTH. NOTE THE PLANS | | | INDICATE THE INSTALATION OF A MIXING ROOM. PLEASE | | | CORRECT THE DISCREPANCY. FOR THIS REVIEW, I WILL BE | | | REVIEWING THE PLANS AS INDICATED UNDER THE PERMIT | | | DESCIPTION, A SPRAY BOOTH. | | | | | | 2) SHEET B-2 SHOWS A ROOF PENETRATION BUT THERE IS NO | | | DETAIL OF THE ADDITIONAL FRAMING AROUND THE NEW | | | OPENING, ROOF CURB OR FLASHING DETAILS, PLANS INDICATE | | | THE ROOF TOP EXHAUST IS GOOD FOR 170 MPH, NO ADDITIONAL | | | SUPPORT IS REQUIRED. FBC-B 1609.4.2. | | | | | | 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION | | | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A | | | RESULT OF THE ADDITIONAL INFORMATION REQUESTED | | | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF | | | THIS REVIEW. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2015-07-13 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2015-07-13 |
Time |
19:06 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2015-07-13 |
Time |
18:32 |
Sent To |
I |
|
| Notes |
| 2015-07-13 19:08:41 | AFTER DISCUSSING THE SCOPE OF WORK W/LIGHTNING | | | ELECTRIC, NOT ALL OF THE PRIOR PLAN REVIEW COMMENTS ARE | | | APPLICABLE. ALL THAT WAS REQUIRED WAS PRESENTED AND | | | APPROVED TODAY. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
N |
Date |
2015-06-30 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2015-06-30 |
Time |
14:27 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2015-06-30 |
Time |
13:53 |
Sent To |
Z |
|
| Notes |
| 2015-06-30 14:30:32 | PER A TELEPHONE CONVERSATION WITH TOM DRAKE OF | | | LIGHTNING ELECTRIC, THIS PERMIT IS BEING ISSUED WITHOUT | | | ELECTRIC SO THAT THE STRUCTURAL CAN PROCEED. EC WILL | | | SUBMIT FOR THE ELECTRIC PRIOR TO COMMENCEMENT OF ANY | | | ELECTRICAL WORK. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2015-06-23 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2015-06-23 |
Time |
10:10 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2015-06-23 |
Time |
08:54 |
Sent To |
|
|
| Notes |
| 2015-06-23 09:47:53 | 6/23/2015 | | | PROJECT: GLUE PRODUCTS | | | PERMIT#: 15041010 | | | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC, | | | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | 2ND ELECTRICAL PLAN REVIEW | | | ACTION: DENIED | | | | | | BELOW IS THE LIST OF ITEMS REQUESTED ON THE FIRST | | | REVIEW ALONG WITH THE ITEMS PROVIDED ON YOUR | | | RE-SUBMITTAL. AS NOTED, THERE IS A DEFICIENCY AND NOT | | | UNTIL ALL ITEMS ARE PROVIDED WILL THIS PERMIT BE | | | APPROVED. THE RISER DIAGRAM YOU PROVIDED DOES NOT MATCH | | | THE ONE ON THE PLANS. IF THE ONE ON THE PLANS IS | | | INCORRECT, PLEASE CROSS IT OUT. PER NEC REQUIREMENTS | | | YOU SHALL PROVIDE A LOAD CALC OF THE4 EXISTING TO | | | ASCERTAIN THAT THE SERVICE WILL ABSORB THE ADDED LOAD | | | PROPERLY. | | | | | | | | | MISSING 1. PROVIDE THE CIRCUITRY ON THE FLOOR PLAN TO | | | COINCIDE WITH THE REQUIRED PANEL SCHEDULE AS WELL AS A | | | RISER DIAGRAM AND LOAD CALCULATION. FBC 107.3.5 | | | ELECTRICAL | | | | | | MISSING 2. PROVIDE COMPLETE CIRCUIT DIRECTORIES FOR | | | ELECTRICAL PANELS. EVERY CIRCUIT SHALL BE LEGIBLY | | | IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND SPECIFIC | | | PURPOSE OR USE. NEC 408.4 | | | | | | MISSING 3. INDICATE THE REQUIRED LIGHTING CONTROLS FOR | | | INTERIOR AND EXTERIOR ILLUMINATION. LIGHTING SYSTEMS | | | SHALL BE PROVIDED WITH CONTROLS AS REQUIRED IN | | | FBC-ENERGY CONSERVATION SECTIONS 505 ELECTRICAL POWER & | | | LIGHTING SYSTEMS (MANDATORY). | | | | | | MISSING 4. INDICATE THE REQUIRED LIGHTING ABOUT | | | ELECTRICAL EQUIPMENT. ILLUMINATION SHALL BE PROVIDED | | | FOR ALL WORKING SPACES ABOUT ELECTRICAL PANELS AND | | | EQUIPMENT. NEC 110.26 (D) | | | | | | MISSING 5. VERIFY SAFETY LABELING FOR ARC FLASH | | | PROTECTION FOR THE PANEL BOARDS AND MAIN DISCONNECTING | | | MEANS. NEC 110.16 | | | | | | MISSING 6. INDICATE ALL REQUIRED EMERGENCY | | | ILLUMINATION. EMERGENCY ILLUMINATION SHALL INCLUDE ALL | | | REQUIRED MEANS OF EGRESS LIGHTING, ILLUMINATED EXIT | | | SIGNS, AND ALL OTHER LIGHTS SPECIFIED AS NECESSARY TO | | | PROVIDE REQUIRED ILLUMINATION. NEC 700.16(F) | | | | | | INCOMPLETE 7. PROVIDE THE LOCATION OF ALL MECHANICAL | | | EQUIPMENT WITH ASSOCIATED REQUIRED DISCONNECTS AND GFI | | | OUTLETS. NEC 210.63, 210.8(A)(3), NEC 440.14, THE FIRE | | | PLAN DOES HAVE AN INDICATION OF THE LOCATION, BUT IT | | | DOES NOT COMPLY WITH THE ELECTRICAL REQUIREMENTS. | | | | | | MAY NOT BE NECESSARY AS ONLY THE MIX ROOMS ARE BEING | | | ADDED TO THE EXISTING LOCATION 8. INDICATE PROVISIONS | | | FOR THE REQUIRED SIGN CIRCUIT AND SHOW WINDOW LIGHTING. | | | NEC 210.62, 600.5(A) | | | | | | COMPLETE (15060821) 9. SEPARATE ELECTRICAL PERMIT | | | ACCOMPANIED BY MANUFACTURER?S EQUIPMENT SUBMITTAL | | | REQUIRED, FOR ELECTRICAL WORK | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED | | | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE | | | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE | | | REVIEW. | | | | | | MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER, PX3353, | | | 561-805-7943 OR [email protected] | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2015-05-28 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2015-05-28 |
Time |
20:07 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2015-05-28 |
Time |
19:04 |
Sent To |
B |
|
| Notes |
| 2015-05-28 20:08:31 | 5/28/2015 | | | PROJECT: GLUE PRODUCTS | | | PERMIT#: 15041010 | | | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC | | | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | 1ST ELECTRICAL PLAN REVIEW | | | ACTION: DENIED | | | | | | 1. PROVIDE THE CIRCUITRY ON THE FLOOR PLAN TO COINCIDE | | | WITH THE REQUIRED PANEL SCHEDULE AS WELL AS A RISER | | | DIAGRAM AND LOAD CALCULATION. FBC 107.3.5 ELECTRICAL | | | | | | 2. PROVIDE COMPLETE CIRCUIT DIRECTORIES FOR ELECTRICAL | | | PANELS. EVERY CIRCUIT SHALL BE LEGIBLY IDENTIFIED AS TO | | | ITS CLEAR, EVIDENT, AND SPECIFIC PURPOSE OR USE. NEC | | | 408.4 | | | | | | 3. INDICATE THE REQUIRED LIGHTING CONTROLS FOR INTERIOR | | | AND EXTERIOR ILLUMINATION. LIGHTING SYSTEMS SHALL BE | | | PROVIDED WITH CONTROLS AS REQUIRED IN FBC-ENERGY | | | CONSERVATION SECTIONS 505 ELECTRICAL POWER & LIGHTING | | | SYSTEMS (MANDATORY). | | | | | | 4. INDICATE THE REQUIRED LIGHTING ABOUT ELECTRICAL | | | EQUIPMENT. ILLUMINATION SHALL BE PROVIDED FOR ALL | | | WORKING SPACES ABOUT ELECTRICAL PANELS AND EQUIPMENT. | | | NEC 110.26 (D) | | | | | | 5. VERIFY SAFETY LABELING FOR ARC FLASH PROTECTION FOR | | | THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC | | | 110.16 | | | | | | 6. INDICATE ALL REQUIRED EMERGENCY ILLUMINATION. | | | EMERGENCY ILLUMINATION SHALL INCLUDE ALL REQUIRED MEANS | | | OF EGRESS LIGHTING, ILLUMINATED EXIT SIGNS, AND ALL | | | OTHER LIGHTS SPECIFIED AS NECESSARY TO PROVIDE REQUIRED | | | ILLUMINATION. NEC 700.16(F) | | | | | | 7. PROVIDE THE LOCATION OF ALL MECHANICAL EQUIPMENT | | | WITH ASSOCIATED REQUIRED DISCONNECTS AND GFI OUTLETS. | | | NEC 210.63, 210.8(A)(3), NEC 440.14 | | | | | | 8. INDICATE PROVISIONS FOR THE REQUIRED SIGN CIRCUIT | | | AND SHOW WINDOW LIGHTING. NEC 210.62, 600.5(A) | | | | | | SEPARATE ELECTRICAL PERMIT ACCOMPANIED BY | | | MANUFACTURER?S EQUIPMENT SUBMITTALS REQUIRED, FOR | | | ELECTRICAL WORK | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED | | | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE | | | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE | | | REVIEW. | | | | | | MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER, PX3353, | | | 561-805-7943 OR [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2015-06-29 |
|
|
Cont ID |
|
| Sent By |
Lindow |
Date |
2015-06-29 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
2015-06-29 |
Time |
|
Sent To |
E |
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2015-06-09 |
|
|
Cont ID |
|
| Sent By |
Lindow |
Date |
2015-06-09 |
Time |
|
Rev Time |
0.00 |
| Received By |
rlindow |
Date |
2015-06-09 |
Time |
|
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2015-05-13 |
|
|
Cont ID |
|
| Sent By |
rlindow |
Date |
2015-05-13 |
Time |
11:29 |
Rev Time |
0.00 |
| Received By |
rlindow |
Date |
2015-05-13 |
Time |
11:28 |
Sent To |
|
|
| Notes |
| 2015-05-13 11:28:40 | PROVIDE QUANTITY AND CLASS OF FLAMMABLE LIQUIDS TO BE | | | STORED IN MIXING ROOMS. | | | PLAN SHOWS 3 DIFFERENT ROOMS, ADDRESS ALL 3. | | | PROVIDE QUANTITY OF LARGEST CONTAINER(S) IN EACH ROOM. | | | | | | SHOW LOCATION OF SPRAY BOOTH IN THIS BUILDING. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2015-07-13 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2015-07-13 |
Time |
19:09 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2015-07-13 19:13:01 | 7/13/15 - PASSED ELECTRICAL REVIEW AS NOTE4D. | | | CONTRACTOR NOTIFIED VIA EMAIL. SENT TO SMALL READY BIN | | | "F". MA |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2015-07-08 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2015-07-08 |
Time |
08:45 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2015-07-08 08:59:43 | ELECTRICAL PROVISO: | | | IN AN EFFORT TO EXPEDITE THE CONSTRUCTION OF THIS | | | PROJECT, THE PERMIT WAS ISSUED PENDING AN ELECTRICAL | | | PERMIT. A REVISION TO THESE DRAWINGS, ADDRESSING ALL | | | ELECTRICAL REQUIREMENTS PREVIOUSLY STATED TO BE | | | SUBMITTED AT THE TIME OF ELECTRICAL PERMIT APPLICATION. | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2015-07-01 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2015-07-01 |
Time |
16:00 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2015-06-24 |
Time |
18:32 |
Sent To |
|
|
| Notes |
| 2015-06-30 14:25:59 | PULEED FROM B15 AND ROUTED TO M. ALBARRAN'S DSK FOR | | | ELECTRICAL REVIEW. | | 2015-06-24 18:34:26 | TRAVELING W/ 15041011 SENT TO B15 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2015-06-23 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2015-06-23 |
Time |
10:08 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2015-06-23 |
Time |
19:08 |
Sent To |
|
|
| Notes |
| 2015-06-23 10:10:40 | I CALLED FLORIDA FILTRATION AND LEFT A MESSAGE, ALSO | | | SPOKE W/LENEE OF LIGHTNING ELECTRIC. EC WILL WORK ON | | | THEIR SUBMITTAL, BUT I SEE THEY ARE STILL MISSING | | | ZONING REQUIREMENTS SO I RETURNED THIS TO SMALL DENIED | | | "F" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2015-06-12 |
|
|
Cont ID |
|
| Sent By |
|
Date |
2015-06-12 |
Time |
|
Rev Time |
0.00 |
| Received By |
shill |
Date |
2015-05-28 |
Time |
18:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2015-05-28 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2015-05-13 |
Time |
18:03 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2015-04-27 |
Time |
|
Sent To |
|
|
| Notes |
| 2015-04-27 15:38:11 | MECHANICAL OVER 5K |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2015-06-10 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2015-06-10 |
Time |
13:41 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2015-06-10 |
Time |
13:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2015-05-07 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2015-05-07 |
Time |
15:28 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2015-05-07 |
Time |
14:33 |
Sent To |
|
|
| Notes |
| 2015-05-07 15:28:27 | PLAN DENIED | | | EXHAUST DUCT SHALL TERMINATE 6 FT. ABOVE THE ROOF. | | | PER NFPA 33 AND 501.2.1 LOCATION OF EXHAUST OUTLETS. | | | 2010 FBC (M) | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2015-07-01 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2015-07-01 |
Time |
15:00 |
Rev Time |
0.00 |
| Received By |
sgraham |
Date |
2015-07-01 |
Time |
15:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2015-06-12 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2015-06-12 |
Time |
10:22 |
Rev Time |
0.00 |
| Received By |
sgraham |
Date |
2015-06-12 |
Time |
10:22 |
Sent To |
|
|
| Notes |
| 2015-06-12 10:23:11 | 6/12/15 ZONING FAILED | | | | | | 1. SUBMIT TWO UP TO DATE SURVEYS SHOWING THE LOCATION | | | OF THE SPRAY BOOTH |
|
|