Plan Review Details - Permit 15041009
Plan Review Stops For Permit 15041009
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-06-29 Cont ID  
Sent By dhayes Date 2015-06-29 Time 10:56 Rev Time 0.00
Received By dhayes Date 2015-06-29 Time 10:56 Sent To  
Notes
2015-06-29 11:06:366/29/2015
 PROJECT: MOLLY'S TROLLYS
 PERMIT#:15041009
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 3RD ELECTRICAL PLAN REVIEW
 ACTION: APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN
 APPROVED PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED
 INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION
 FEE(S).
  
 1) MANUFACTURER'S PRODUCT APPROVALS INDICATING THE
 POWER AND LISTING REQUIREMENTS FOR ALL OF THE
 COMPONENETS INVOLVED.
  
 2) NEC 514.11 CIRCUIT DISCONNECTS.
 (A) GENERAL. EACH CIRCUIT LEADING TO OR THROUGH
 DISPENSING EQUIPMENT, INCLUDING EQUIPMENT FOR REMOTE
 PUMPING SYSTEMS, SHALL BE PROVIDED WITH A CLEARLY
 IDENTIFIED AND READILY ACCESSIBLE SWITCH OR OTHER
 ACCEPTABLE MEANS, LOCATED REMOTE FROM THE DISPENSING
 DEVICES, TO DISCONNECT SIMULTANEOUSLY FROM THE SOURCE
 OF SUPPLY, ALL CONDUCTORS OF THE CIRCUITS, INCLUDING
 THE GROUNDED CONDUCTOR, IF ANY. SINGLE-POLE BREAKERS
 UTILIZING HANDLE TIES SHALL NOT BE PERMITTED.
  
 (B) ATTENDED SELF-SERVICE MOTOR FUEL DISPENSING
 FACILITIES. EMERGENCY CONTROLS AS SPECIFIED IN
 514.11(A) SHALL BE INSTALLED AT A LOCATION ACCEPTABLE
 TO THE AUTHORITY HAVING JURISDICTION, BUT CONTROLS
 SHALL NOT BE MORE THAN 30 M (100 FT) FROM DISPENSERS.
 [30A:6.7.1]
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-06-09 Cont ID  
Sent By dhayes Date 2015-06-09 Time 16:57 Rev Time 0.00
Received By dhayes Date 2015-06-09 Time 16:57 Sent To  
Notes
2015-06-09 16:57:015/2/2015
 PROJECT: MOLLY'S TROLLYS
 PERMIT#:15041009
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 PLEASE PROVIDE ELECTRICAL PLANS AND SPECIFICATIONS THAT
 CLEARLY INDICATE THE ENTIRE ESCOPE OF THE PROJECT
 INCLUDING BUT NOT LIMITED TO THE FOLLOWING:
  
 1) MANUFACTURER'S PRODUCT APPROVALS INDICATING THE
 POWER AND LISTING REQUIREMENTS FOR ALL OF THE
 COMPONENETS INVOLVED.
 2) A SITE PLAN INDICATING THE LOCATION OF THE SOURCE OF
 POWER INCLUDING A PANEL SCHEDULE WITH THE ELECTRICAL
 CIRCUITS OCPD AND WIRE SIZES PROPOSED.
 3) A SITE PLAN INDICATING THE LOCATIONS FOR THE PUMPS,
 DISPENSER(S) CONTROLERS, DISCONNECTS AND EPO'S
 (EMERGENCY POWER OFF),
 4) A SITE PLAN INDICATING THE LOCATIONS, PHOTOMETRIC
 DETAIL AND CIRCUITING OF THE LUMINAIRS (EXISTING OR
 NEW) FOR ILLUMINATION OF THE EQUIPMENT.
 5) A DETAILED PIPING AND CIRCUITING PLAN INDICATING THE
 ELECTRICAL CONNECTION OF ALL THE AFOREMENTIONED
 COMPONENETS BETWEEN THE SOURCE AND LOADS FOR THE ENTIRE
 SCOPE OF WORK PROPOSED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-05-02 Cont ID  
Sent By   Date 2015-05-02 Time 13:27 Rev Time 0.00
Received By dhayes Date 2015-05-02 Time 13:20 Sent To FIRE
Notes
2015-05-02 13:50:315/2/2015
 PROJECT:
 PERMIT#:
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 ELECTRICAL PLAN REVIEW
 ACTION:
  
 NO ELECTRICAL PLANS OR SPECIFICATIONS HAVE BEEN
 PROVIDED. PLEASE PROVIDE ELECTRICAL PLANS AND
 SPECIFICATIONS THAT CLEARLY INDICATE THE ENTIRE ESCOPE
 OF THE PROJECT INCLUDING BUT NOT LIMITED TO THE
 FOLLOWING:
  
 1) MANUFACTURER'S PRODUCT APPROVALS INDICATING THE
 POWER AND LISTING REQUIREMENTS FOR ALL OF THE
 COMPONENETS INVOLVED.
 2) A SITE PLAN INDICATING THE LOCATION OF THE SOURCE OF
 POWER INCLUDING A PANEL SCHEDULE WITH THE ELECTRICAL
 CIRCUITS OCPD AND WIRE SIZES PROPOSED.
 3) A SITE PLAN INDICATING THE LOCATIONS FOR THE PUMPS,
 DISPENSER(S) CONTROLERS, DISCONNECTS AND EPO'S
 (EMERGENCY POWER OFF),
 4) A SITE PLAN INDICATING THE LOCATIONS, PHOTOMETRIC
 DETAIL AND CIRCUITING OF THE LUMINAIRS (EXISTING OR
 NEW) FOR ILLUMINATION OF THE EQUIPMENT.
 5) A DETAILED PIPING AND CIRCUITING PLAN INDICATING THE
 ELECTRICAL CONNECTION OF ALL THE AFOREMENTIONED
 COMPONENETS BETWEEN THE SOURCE AND LOADS FOR THE ENTIRE
 SCOPE OF WORK PROPOSED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-06-04 Cont ID  
Sent By pleduc Date 2015-06-04 Time   Rev Time 0.00
Received By pleduc Date 2015-06-04 Time 15:44 Sent To E
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-05-04 Cont ID  
Sent By pleduc Date 2015-05-04 Time   Rev Time 0.00
Received By pleduc Date 2015-05-04 Time 10:53 Sent To  
Notes
2015-05-04 11:51:57THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PROVIDE DIMENSIONS FROM EACH PROPERTY LINE.
  
 PROVIDE INFORMATION INDICATING THAT THE TANK IS DOUBLED
 WALLED.
  
 PROVIDE PIPING DETAIL FOR DISPENSER AND TANK.
  
 PROVIDE LOCATION OF EMERGENCY SHUT OFF.
  
 PROVIDE LOCATION OF FIRE EXTINGUISHERS.
  
 PROVIDE LOCATION OF NO SMOKING SIGNS.
  
 TANK SHALL BE ENCLOSED IN A FENCE IF THE ENTIRE
 PROPEORTY IS NOT FENCED. PROVIDE NOTE INDICATING FENCE.
  
 ALL INSTALLATONS SHALL COMPLY WITH NFPA 1, 101, 30A AND
 58.
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
 FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 10, 2010 EDITION.
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION.
 NFPA 58, LIQUEFIED PETROLEUM GAS CODE, 2011 EDITION.
 NFPA 30A, CODE FOR MOTOR FUEL DISPENSING FACILITIES AND
 REPAIR GARAGES, 2012 EDITION.

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2015-07-18 Cont ID  
Sent By tklarge Date 2015-07-18 Time 05:17 Rev Time 0.00
Received By tklarge Date 2015-07-18 Time 05:08 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2015-06-23 Cont ID  
Sent By tklarge Date 2015-06-23 Time 04:31 Rev Time 0.00
Received By tklarge Date 2015-06-23 Time 04:06 Sent To  
Notes
2015-06-23 04:30:53THE ENGINEER'S SEAL AND SIGNATURE FOR THE TANK TIE-DOWN
 ARE COPIES. COMPLY WITH FL. ADMIN. CODE RULE
 61G15-23.002 FOR THE REQUIREMENTS FOR THE ENGINEER'S
 SEAL AND SIGNATURE.
  
 I SUGGEST SOMEONE CONTACT ME AT 561-805-6692 TO DISCUSS
 THE ABOVE COMMENT AS IT SEEMS THERE IS SOME CONFUSION
 AS TO WHAT IS REQUIRED REGARDING THE ENGINEER'S SEAL.
 NOTE: I SPOKE TO KELLY AT AMERIGAS ON 6/23/15 @8:35 AM
 AND EXPLAINED TO HIM WHAT WAS NEEDE TO COMPLY W/STATE
 ADMINISTRATIVE CODE RULE. HE STATED HE WOULD GET IT
 TAKEN CARE OF.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2015-06-04 Cont ID  
Sent By tklarge Date 2015-06-04 Time 08:31 Rev Time 0.00
Received By tklarge Date 2015-06-04 Time 06:18 Sent To FIRE
Notes
2015-06-04 06:59:161) SUBMIT TIE-DOWN ENGINEERING FOR THE PROPANE TANK PER
 2010 FBC-FUEL GAS SEC. 301.10.THE RESPONSE FROM
 AMERIGAS STATES THERE ARE SIGNED AND SEALED DRAWINGS
 FROM AN ENGINEER BUT THERE ARE NO DRAWINGS FOR THE
 ANCHORING OF THE TANK FROM AN ENGINEER. CLARIFY. 2ND
 REQUEST.
 2) THE PLAN FROM SUPERIOR ENERGY SYSTEMS IS SIGNED AND
 SEALED BY AN ENGINEER REGISTERED IN THE THE STAE OF
 OHIO. THIS IS UNACCEPTABLE. IF THE DOCUMENTS ARE GOING
 TO BE SIGNED AND SEALED BY AN ENGINEER, THE ENGINEER
 SHALL BE REGISTERED IN THE STATE OF FLORIDA PER F.S>
 471 & FL. ADMIN. CODE RULE 61G15-23.002.
 3) THE SUBMITTED PLANS DO NOT SHOW COMPLIANCE WITH THE
 FOLLOWING REQUIREMENTS OF NFPA 58. PLEASE SHOW
 COMPLIANCE WITH THE FOLLOWING CODE SECTION REQUIREMENTS
 ON THE PLANS. IDENTIFY ALL COMPONENTS OF THE PIPING
 SYSTEM:
 A) THE FUEL DISPENSER SHALL BE INSTALLED IN ACCORDANCE
 WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS PER
 NFPA 58 SEC.6.22.3.1. SUBMIT TWO COPIES OF THE
 INSTALLATION INSTRUCTIONS.
 B) THE PIPING AND THE DISPENSING HOSE SHALL BE PROVIDED
 WITH HYDROSTATIC RELIEF VALVES PER NFPA 58 SEC.
 6.22.3.6 & NFPA SEC. 6.11.
 C) AN IDENTIFIED AND ACCESSIBLE SWITCH SHALL BE
 INSTALLED AT A LOCATION NOT LESS THAN 20 FT. OR MORE
 THAN 100 FT. FROM THE DISPENSING DEVICE TO SHUT OFF THE
 POWER PER NFPA 58 SEC. 6.22.3.11. SHOW THE DISTANCE OF
 THE EMERGENCY SHUTOFF SWITCH FROM THE DISPENSER.
 D) THE HOSE LENGTH FROM THE DISPENSER SHALL NOT EXCEED
 18 FT. NFPA 58 SEC. 6.222.4.1 (1). ALL HOSES SHALL
 LISTED FOR USE WITH LP GAS.
 E) A LISTED EMERGENCY BREAKAWAY DEVICE COMPLYING WITH
 UL 567 SHALL BE INSTALLED ON THE DISPENSER HOSE.NFPA 58
 SEC.6.22.4.2.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2015-05-02 Cont ID  
Sent By dhayes Date 2015-05-02 Time 04:56 Rev Time 0.00
Received By tklarge Date 2015-05-02 Time 04:03 Sent To E
Notes
2015-05-02 04:55:381) SUBMIT DOCUMENTATION THAT THE PLAN HAS BEEN SPPROVED
 BY THE DEPT. OF AGRICULTURE, DIVISION OF LP GAS. WPB
 AMENDMENTS TO 2010 FBC SEC.102.1.2, 107.2.1.
 2) THE VALUE OF THIS PROJECT SEEMS LOW. SUBMIT A COPY
 OF THE SIGNED CONTRACT PER THE WPB AMENDMENTS TO 2010
 FBC SEC. 109.3.
 3) SUBMIT A SITE PLAN THAT IS LARGER AND LEGIBLE AND
 SHOWS ALL DETAILS. WPB AMENDMENTS TO 2010 FBC SEC.
 107.2.1.
 4) SUBMIT CLEAR AND LEGIBLE SPECIFICATION SHEETS FOR
 THE LP TANK.WPB AMENDMENTS TO 2010 FBC SEC. 107.2.1.
 5) DOCUMENTS THAT BEAR THE NAME AND TITLE BLOCK OF AN
 ENGINEER SHALL BE SIGNED AND SEALED BY THAT DESIGN
 PROFESSIONAL PER THE FL. ADMINISTRATIVE CODE.
 SEC.61G15-23.002. SEE SHEET FROM RUSSEL PERLITA OF
 BERLIN DRAFTING AND ALSO FROM R.F. TUCKER FROM TIE-DOWN
 ENGINEERING
 6) SUBMIT DETAILS FOR THE BOLLARDS.SHOW HEIGHT ABOVE
 GROUND, DEPTH IN GROUND, ARE DIRECT BURIAL OR IN
 CONCRETE. IF IN CONCRETE SUPPLY DETAILS. SHOW DIAMETER
 OF THE BOLLARDS AND THE CENTER TO CENTER SPACING OF THE
 BOLLARDS AROUND THE TANK. WPB AMENDMENTS TO 2010 FBC
 SEC. 107.2.1.
 7) SUBMIT PIPING DETAILS FOR THE PIPING FROM THE TANK
 TO THE DISPENSER AND SUBMIT MANUF. SPECS THAT SHOW THE
 CONNECTION DIAGRAM TO THE PUMP. WPB AMENDMENTS TO 2010
 FBC SEC. 107.2.1.
 8) CLEARLY SHOW THE LOCATION OF THE DISPENSER ON THE
 SITE PLAN.
 9) INSTALLATION SHALL COMPLY WITH NFPA 58 FOR THE
 INSTALLATION OF THE TANK & DISPENSER.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2015-07-18 Cont ID  
Sent By tklarge Date 2015-07-18 Time 05:17 Rev Time 0.00
Received By tklarge Date 2015-07-18 Time 05:17 Sent To  
Notes
2015-07-17 12:43:19TLARGE DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-06-29 Cont ID  
Sent By dhayes Date 2015-06-29 Time 10:56 Rev Time 0.00
Received By dhayes Date 2015-06-22 Time 19:23 Sent To  
Notes
2015-06-22 19:24:02RE-SUBMITTAL SENT TO TIM LARGE FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-06-09 Cont ID  
Sent By dhayes Date 2015-06-09 Time 16:57 Rev Time 0.00
Received By dhayes Date 2015-06-02 Time 16:05 Sent To  
Notes
2015-06-02 16:05:44TO PLUMBING
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-05-04 Cont ID  
Sent By pleduc Date 2015-05-04 Time   Rev Time 0.00
Received By pleduc Date 2015-05-02 Time 04:56 Sent To  
Notes
2015-04-27 15:38:35ROUTED TO PLUMBING LESS THAN $5000


Account Summary | Usage Policy | Privacy Policy