2015-04-25 09:00:12SENT TO MECHANICAL UNDER $5000

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-05-27 Cont ID  
Sent By hmoser Date 2015-05-26 Time 09:55 Rev Time 0.00
Received By hmoser Date 2015-05-27 Time 10:52 Sent To  
Notes
2015-05-26 09:54:39PLAN DENIED
 1) PROVIDE ENERGY CALCULATIONS WITH PLANS
 PER SECTION 603.2 DUCT SIZING 2010 FBC (M)
 AND SECTION 503.2.1 CALCULATION OF HEATING
 AND COOLING LOADS. 2010 FLORIDA ENERGY CODE.
 2) MISSING FIRE DAMPERS REFER TO SECTION
 607.5 FIRE WALLS 2010 FBC (M)
 3) NOTE 2 SHOWS 4" BATH EXHAUST THROUGH
 THE ROOF, NOTE 5 SHOWS 8" BATH EXHAUST THROUGH
 THE ROOF
 4) PROVIDE EQUIPMENT SCHEDULE ON THE PLANS
 SHOWING SEER SECTION 107 2010 FBC
 5) NOTE 10 SHOWS FIRE RATED RETURN AIR
 PLENUM ( MISSING DAMPER )
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-04-27 Cont ID  
Sent By hmoser Date 2015-04-27 Time 09:40 Rev Time 0.00
Received By hmoser Date 2015-04-27 Time 09:11 Sent To  
Notes
2015-04-27 09:39:55PLAN DENIED
 1) MISSING FIRE DAMPERS IN SUPPLY DUCT IN
 BEDROOMS. 607.5.1 FIRE WALLS 2010 FBC (M)
 2) FLEX CAN'T PASS THROUGH FIRE RATED WALLS PER
 SECTION 607.7 FLEX DUCT AND CONNECTORS
 2010 FBC (M)
 3) MISSING FIRE DAMPERS SECTION 607.5.1
 FBC (M)
 4) REFER TO TABLE 1509.7 CLEARANCE BELOW
 RAISED ROOF MOUNTED MECHANICAL UNITS.
 2010 FBC.
 5) PROVIDE A NEW DETAIL FROM THE ENGINEER
 SHOWING SIZE AND TYPE OH ANCHOR USED FOR
 CONDENSER STAND TO ROOF AND UNIT TO STAND.
 PER SECTION 301.12 WIND RESISTANCE.
 2010 FBC (M)
 6) SHOW DUCT SIZE FOR THE FRESH AIR ON THE
 PLAN. PER SECTION 107 FBC 2010.
 7) NOTE # 1 SHOWS NEW 2.5 AIR CONDITIONING SYSTEM.
 PROVIDE EQUIPMENT SCHEDULE ON PLANS.PER SECTION
 107 FBC 2010
  
 PLAN REVIEW BY HAROLD MOSER