Plan Review Details - Permit 15040949
Plan Review Stops For Permit 15040949
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2015-07-31 Cont ID  
Sent By rmcdouga Date 2015-07-31 Time 19:02 Rev Time 0.00
Received By rmcdouga Date 2015-07-31 Time 19:02 Sent To Z
Notes
2015-07-31 19:02:38APPROVED WITH EXCEPTIONS
  
 1) SUBMIT SIGNED AND SEALED EMBED ANCHOR PLATE DETAILS.
 FBC-R 107.2.1.3
 2) SUBMIT SIGNED AND SEALED RAS 117 ENHANCED FASTENING
 DETAILS FOR THE FIBERTITE SINGLE PLY ROOF SYSTEM ( NOA
 NO. 12-1019.34 ) FOR REVIEW BEFORE ROOFING IS
 INSTALLED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2015-07-16 Cont ID  
Sent By rmcdouga Date 2015-07-16 Time 18:40 Rev Time 0.00
Received By rmcdouga Date 2015-07-16 Time 16:43 Sent To  
Notes
2015-07-16 18:53:10PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 THE BUILDING OFFICIAL HAS DETERMINED THAT THE SUCCESSOR
 ARCHITECT LETTER IS NOT SUFFICIENT. HE REQUIRES THAT
 THE LETTER STATE "THIS IS TO INFORM YOU THAT PURSUANT
 TO FLORIDA ADMINISTRATIVE CODE 61G1-18.002, WE WILL BE
 USING OR REUSING YOUR DRAWINGS FOR THIS PROJECT".

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2015-07-02 Cont ID  
Sent By rmcdouga Date 2015-07-02 Time 17:38 Rev Time 0.00
Received By rmcdouga Date 2015-07-02 Time 07:35 Sent To  
Notes
2015-07-02 17:38:19PLAN
 REVIEW COMMENTS
  
 3RD REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT A LETTER FROM THE SUCCESSOR ARCHITECT WHICH
 STATES THAT HE IS ADOPTING THE WORK OF THE ORIGINAL
 REGISTERED ARCHITECT AND TAKING PROFESSIONAL AND LEGAL
 RESPONSIBILITY FOR THE CONSTRUCTION DOCUMENTS. THE
 LETTER SHALL STATE THAT THE SUCCESSOR ARCHITECT HAS
 NOTIFIED THE ORIGINAL REGISTERED ARCHITECT BY CERTIFIED
 LETTER OF THE SUCCESSOR'S INTENTIONS TO USE OR REUSE
 THE ORIGINAL REGISTERED ARCHITECT'S WORK AS REQUIRED BY
 F.A.C. 61G1-18.002
  
 2) PROVIDE BUCK FASTENING DETAILS FOR THE EXTERIOR
 DOOR, WINDOW AND SECTIONAL GARAGE DOOR. FBC-R612.10.2.1
  
 3) THE PRODUCT APPROVALS FOR THE PGT PW-701 FIXED
 WINDOWS NOA NO. 13-0502.03 HAVE NOT BEEN APPROVED IN
 WRITING BY THE SUCCESSOR ARCHITECT.
  
 4) THE ROOFING PRODUCT APPROVAL FOR THE FIBERTITE
 SINGLE PLY ROOF SYSTEM (NOA NO. 12-1019.29) IN THE
 SUBMITTAL DOCUMENTS IS FOR USE ON STEEL DECKS. THIS
 GARAGE HAS A 5/8" PLYWOOD DECK. SUBMIT TWO COPIES OF
 ROOFING PRODUCT APPROVALS FOR A WOOD DECK. DCA RULE
 9N-3 AND FBC 107.2.1
  
 5) SPECIFY WHICH ONE OF THE APPROVED ASSEMBLIES LISTED
 IN THE ROOFING PRODUCT APPROVAL WILL BE USED. SPECIFY
 THE ATTACHMENT METHOD AND THE MAXIMUM DESIGN PRESSURE
 FOR THE PROPOSED SYSTEM. IF ENHANCED FASTENING IS
 REQUIRED TO MEET THE HIGHER UPLIFTS IN ROOF ZONES 2 AND
 3, SUBMIT SIGNED AND SEALED RAS 117 CALCULATIONS.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-06-23 Cont ID  
Sent By rmcdouga Date 2015-06-23 Time 15:14 Rev Time 0.00
Received By rmcdouga Date 2015-06-23 Time 15:14 Sent To  
Notes
2015-06-23 14:11:54PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 I HAVE RECEIVED AND REVIEWED THE FOUNDATION PLANS FOR
 THE MODULAR BUILDING. PLEASE ADDRESS THE ITEMS NOTED
 BELOW:
  
 1) I LOCATED THE HOME PRIDE (HP8) EARTH ANCHORS
 SPECIFICATIONS AND INSTALLATION INSTRUCTION ON THE
 INTERNET AND PLACED TWO COPIES OF THEM WITH THE
 FOUNDATION PLANS.
  
 2) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS AND INSTALLATION INSTRUCTIONS FOR THE
 PFV1 POWER FOUNDATION VENTS SPECIFIED ON THE FOUNDATION
 PLANS. FBC 107.2.1
  
 3) SUBMIT TWO SETS OF THE FOUNDATION PLANS WITH THE
 PROFESSIONAL ENGINEER'S HANDWRITTEN SIGNATURE (
 FACSIMILES ARE NOT ACCEPTABLE) AS REQUIRED BY FAC
 61G15-23.002.
  
 4) THE FONT SIZE FOR THE NOTES ON THE DETAILS ARE TOO
 SMALL TO BE READ CLEARLY FOR FIELD INSPECTION PURPOSES.
 INCREASE THE FONT SIZE. FBC 107.2.1.4
  
 5) SPECIFY THE MINIMUM HEIGHT ABOVE GRADE FOR THE
 MASONRY STEM WALL ON THE PLANS. FBC 107.2.1
  
 6) THE FOUNDATION PLAN INDICATES TWO (2) WELD PLATES
 AND TWO HP 8 EARTH ANCHORS LOCATED AT EACH OF THE
 STRUCTURES CORNERS. PLEASE VERIFY THAT THESE
 CONNECTIONS FROM THE FOUNDATION TO THE STRUCTURE WILL
 BE CAPABLE OF SAFELY RESISTING THE 170 MPH EXPOSURE C
 WINDLOADS. FBC-R301.1
  
 7) PROVISO: PLEASE HAVE YOUR INTENDED ELECTRICAL
 SUB-CONTRACTOR SUBMIT AN ELECTRICAL SUB-PERMIT
 APPLICATION. A BOND WIRE IS REQUIRED TO BE ATTACHED TO
 THE FOUNDATION STEEL AND INSPECTED BEFORE THE FOOTING
 CAN BE POURED. 2008 NEC 250.50
  
 8) SOME DOCUMENTS FROM THE BUILDING PERMIT PACKET MUST
 BE DUPLICATED SO THAT THE FOUNDATION ONLY PERMIT CAN
 STAND ALONE FOR RECORD PURPOSES. IF YOU WOULD LIKE A
 FOUNDATION ONLY PERMIT, YOU WILL NEED TO SUBMIT ANOTHER
 PERMIT APPLICATION FORM FOR THE MODULAR HOME FOUNDATION
 ONLY. THE COST VALUATION FOR THE FOUNDATION ONLY PERMIT
 SHOULD BE SUBTRACTED FROM THE OTHER PERMIT AND APPLIED
 TO THIS NEW ONE. IN ADDITION TO THE INFORMATION LISTED
 ABOVE, YOU WILL NEED TO SUBMIT TWO SETS OF THE
 FOLLOWING: PLANS FOR THE MODULAR HOME, SOIL REPORTS AND
 SURVEYS/SITE PLANS. ONE SET OF THE PLANS WILL NEED TO
 BE TAKEN TO PALM BEACH COUNTY FOR AN IMPACT FEE REVIEW.
 THE PLANS WITH THE COUNTY IMPACT FEE STAMP AND A COPY
 OF THE PAID RECEIPT WILL HAVE TO BE SUBMITTED TO THE
 CITY BEFORE THE PERMIT IS ISSUED. A RECORDED COPY OF
 THE NOTICE OF COMMENCEMENT IS ALSO REQUIRED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-06-16 Cont ID  
Sent By rmcdouga Date 2015-06-16 Time 16:05 Rev Time 0.00
Received By rmcdouga Date 2015-06-16 Time 16:04 Sent To  
Notes
2015-06-16 10:06:31PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 MODULAR PLANS
  
 1) GENERAL NOTE #7 ON SHEET 1 REQUIRES A FIRE
 SEPARATION DISTANCE OF 10 FEET BASED ON 2010 FBC TABLE
 602 & SECTION 704, THE WEST WALL OF THE STRUCTURE IS 5
 FEET FROM THE PROPERTY LINE. NOTE: THIS IS AN R-3
 SINGLE FAMILY DWELLING. THE 2010 FBC RESIDENTIAL CODE
 SHOULD BE THE APPLICABLE CODE. FBC-R TABLE R302.1
 ALLOWS A FIRE SEPARATION DISTANCE OF 3 FEET.
  
 2) PLANS DO NOT SPECIFY THE REQUIRED SOIL BEARING
 CAPACITY TO SAFELY SUPPORT THE STRUCTURE. FBC-R401.2
  
 3) SUBMIT TWO SETS OF SIGNED AND SEALED FOUNDATION AND
 TIE DOWN PLANS FOR THE MODULAR STRUCTURE. SEE
 FOUNDATION PLAN NOTES ON SHEET 1 AND ELEVATION NOTES ON
 SHEET 2. SHOW COMPLIANCE WITH FBC-R 318 FOR PROTECTION
 AGAINST TERMITES, FBC-R 317 FOR CLEARANCES OF WOOD
 SIDING, SHEATHING & WALL FRAMING FROM THE GROUND AND
 PORCH SLABS AND FBC-R 704 FOR NOT LESS THAN 6 INCHES OF
 CLEARANCE BETWEEN EXTERIOR WALL COVERINGS AND FINAL
 EARTH GRADE.
  
 4) SUBMIT TWO SETS OF SITE SPECIFIC ENERGY CALCULATIONS
 AND HVAC EQUIPMENT SIZING CALCULATIONS. FBC 107.2.1 AND
 2010 FBC ENERGY CONSERVATION SECT. 101.4.3 & 103.2
  
 SITE BUILT GARAGE PLANS
  
 1) GENERAL SITE NOTE #6 ON SHEET AS1.1 REFERENCES
 CHAPTERS 1403, 1826 AND 2304 OF THE 2004 FBC, WHICH DO
 NOT APPLY TO THIS JOB. THE 2010 FLORIDA BUILDING CODE
 RESIDENTIAL APPLIES TO THIS PROJECT. FBC-R 101.2
  
 2) GENERAL SITE NOTE #8 ON SHEET AS1.1 SPECIFIES THAT
 THE FINISHED GRADE IS TO BE SLOPED AWAY FROM THE
 BUILDING WALLS A MINIMUM OF 1/4" PER FOOT. FBC-R 401.3
 REQUIRES THE GRADE TO FALL A MINIMUM OF 6 INCHES WITHIN
 THE FIRST 10 FEET. WHICH IS A LITTLE LESS THAN 5/8" PER
 FOOT.
  
 3) GENERAL SITE NOTE #9 ON SHEET AS1.1 SPECIFIES THAT
 ALL EXTERIOR CONCRETE SLABS ARE TO BE SLOPED @ 1/8" PER
 FOOT AWAY FROM BUILDING WALLS. FBC-R 403.1 REQUIRES
 IMPERVIOUS SURFACES WITHIN 10 FEET OF THE BUILDING
 FOUNDATION TO BE SLOPED A MINIMUM OF 2 PERCENT (.24"
 PER FOOT) AWAY FROM THE BUILDING.
  
 4) THE NOTE ARROWS FOR SECTIONS H1 AND H4 ON SHEET A1.2
 ARE OFF SET FROM THE DRAWING SUCH THAT THEY DO NOT
 SPECIFY THE CORRECT LOCATION FOR THE ITEM NOTES. FBC
 107.2.1
  
 5) THE DESIGNER OF RECORD DID NOT PROVIDE SEPARATE
 PRESSURES FOR THE 8' X 8' SECTIONAL GARAGE DOORS IN THE
 COMPONENT & CLADDING WALL PRESSURE SCHEDULE ON SHEET
 A0.1. BASED ON THE WALL PRESSURES PROVIDED IN THE
 SCHEDULE, THE DESIGN PRESSURES IN THE PRODUCT APPROVAL
 FOR THE SECTIONAL GARAGE DOORS ( +/- 37 PSF ) ARE NOT
 ADEQUATE. FBC-R 301.2.1
  
 6) THE PRODUCT APPROVAL SUBMITTED FOR THE 3' X 8'
 OUTSWING DOOR DOES NOT HAVE A FL# OR NOA NO. SPECIED IN
 THE DOCUMENTS. THE +/- 50 PSF DESIGN PRESSURE LISTED
 FOR THE DOOR IS INADEQUATE. THE DOOR IS NOT IMPACT
 RATED (AN APPROVED DCA RULE 9N-3, FBC-R 301.2.1 AND
 301.2.1.2
  
 7) SPECIFY WHICH ONE OF THE APPROVED ASSEMBLIES LISTED
 IN THE FIBERTITE NOA WILL BE INSTALLED. INDICATE THE
 MAXIMUM DESIGN PRESSURE FOR THE SYSTEM AND PROVIDE
 SIGNED AND SEALED RAS 117 AND/OR RAS 137 CALCULATIONS
 FOR ENHANCED FASTENING TO MEET THE UPLIFT PRESSURES IN
 ROOF ZONES 2 AND 3. FBC-R 301.2.1
  
 8) IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE
 CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER
 INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN
 ADDRESSED.
  
 9) LANDSCAPE AND IRRIGATION REQUIRE SEPARATE PERMITS,
 APPLICATIONS AND REVIEWS. PLEASE REMOVE BOTH SETS OF
 LANDSCAPE AND IRRIGATION PLANS FROM THE SUBMITTAL
 DOCUMENTS AND SUBMIT THEM WITH SEPARATE PERMIT
 APPLICATIONS. IF THE VALUE FOR THIS WORK WAS INCLUDED
 IN THE VALUE OF THE STRUCTURE, PLEASE REMOVE THE AMOUNT
 FOR EACH AND APPLY IT TO THE SEPARATE PERMITS.
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-06-30 Cont ID  
Sent By albarran Date 2015-06-30 Time 18:27 Rev Time 0.00
Received By albarran Date 2015-06-30 Time 17:01 Sent To B
Notes
2015-06-30 18:30:46ADDED NOTE REFERENCING THE ADDITIONAL NEC REQUIREMENTS:
 1 NEC 250.94 (INTER-SYSTEM BONDING); 250.52 TIE GEC TO
 FOUNDATION STEEL
 2 NEC 210.8 GFCI PROTECTION REQUIRED FOR ALL OUTLETS IN
 THE GARAGE.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-06-01 Cont ID  
Sent By albarran Date 2015-06-01 Time 18:19 Rev Time 0.00
Received By albarran Date 2015-06-01 Time 17:44 Sent To  
Notes
2015-06-01 18:23:40THE FOLLOWING ITEMS SHALL BE CORRECTED AND THE PLANS
 RESUBMITTED FOR A SECOND REVIEW:
  
  
 THESE PLANS WERE REVIEWED FOR COMPLIANCE WITH THE 2008
 EDITION OF THE NEC, THE 2013 EDITION OF THE NFPA72, THE
 APPLICABLE CHAPTERS OF THE 2010 EDITION OF THE FLORIDA
 BUILDING CODE, FLORIDA BUILDING CODE RESIDENTIAL AND
 FLORIDA BUILDING CODE ENERGY CONSERVATION.
 1. YOU SHALL SUBMIT A SITE SPECIFIC SERVICE RISER
 DIAGRAM.
 2. YOU NEED TO SPECIFY THE SCOPE OF ALL SITE INSTALLED
 APPARATUS, AND INCLUDE THAT IN WITH THE ABOVE RISER.
 3. NEC 210.70 REQUIRES A LIGHT W/A SWITCH AT THE REAR
 DOOR OF THE GARAGE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS
  
 FOR QUESTIONS ON THE ABOVE, PLEASE CONTACT:
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 PH: (561) 805-6743
 EMAIL: [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2015-08-03 Cont ID  
Sent By rmcdouga Date 2015-08-03 Time 10:48 Rev Time 0.00
Received By rmcdouga Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-07-17 Cont ID  
Sent By rmcdouga Date 2015-07-17 Time 09:23 Rev Time 0.00
Received By rmcdouga Date 2015-07-13 Time 16:43 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-07-02 Cont ID  
Sent By rmcdouga Date 2015-07-02 Time 17:38 Rev Time 0.00
Received By rmcdouga Date 2015-06-30 Time 12:11 Sent To  
Notes
2015-06-30 12:11:57TO MALBARAN DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-06-16 Cont ID  
Sent By rmcdouga Date 2015-06-16 Time 16:05 Rev Time  
Received By rmcdouga Date 2015-04-24 Time   Sent To  
Notes
2015-04-25 10:25:56R30

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2015-07-31 Cont ID  
Sent By rmcdouga Date 2015-07-31 Time 17:23 Rev Time 0.00
Received By rmcdouga Date 2015-07-31 Time 17:23 Sent To  
Notes
2015-07-31 17:24:45MU 2015 - 18119, NO FEES WERE DUE.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2015-07-01 Cont ID  
Sent By rmcdouga Date 2015-07-01 Time 18:24 Rev Time 0.00
Received By rmcdouga Date 2015-07-01 Time 18:24 Sent To  
Notes
2015-07-01 18:24:57SEE PREVIOUS COMMENTS.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-06-15 Cont ID  
Sent By rmcdouga Date 2015-06-15 Time 19:13 Rev Time 0.00
Received By rmcdouga Date 2015-06-15 Time 18:03 Sent To  
Notes
2015-06-15 19:13:27BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2015-07-31 Cont ID  
Sent By rmcdouga Date 2015-07-31 Time 17:23 Rev Time 0.00
Received By rmcdouga Date 2015-07-31 Time 17:23 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2015-07-16 Cont ID  
Sent By rmcdouga Date 2015-07-16 Time 18:39 Rev Time 0.00
Received By rmcdouga Date 2015-07-16 Time 18:39 Sent To  
Notes
2015-07-17 09:23:00PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT TWO SETS OF SITE SPECIFIC ENERGY CALCULATIONS
 AND HVAC EQUIPMENT SIZING CALCULATIONS. FBC 107.2.1 AND
 2010 FBC ENERGY CONSERVATION SECT. 101.4.3 & 103.2

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-07-02 Cont ID  
Sent By rmcdouga Date 2015-07-02 Time 16:51 Rev Time 0.00
Received By rmcdouga Date 2015-07-02 Time 16:51 Sent To  
Notes
2015-07-02 16:52:56PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT TWO SETS OF SITE SPECIFIC ENERGY CALCULATIONS
 AND HVAC EQUIPMENT SIZING CALCULATIONS. FBC 107.2.1 AND
 2010 FBC ENERGY CONSERVATION SECT. 101.4.3 & 103.2

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-06-16 Cont ID  
Sent By hmoser Date 2015-06-04 Time 10:57 Rev Time 0.00
Received By hmoser Date 2015-06-04 Time 10:56 Sent To  
Notes
2015-06-16 14:59:06PROVIDE ENERGY CALCULATIONS WITH PLANS
 PER SECTION M1401.3 SIZING
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-05-30 Cont ID  
Sent By tklarge Date 2015-05-30 Time 08:12 Rev Time 0.00
Received By tklarge Date 2015-05-30 Time 07:22 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2015-08-03 Cont ID  
Sent By sgraham Date 2015-08-03 Time 10:33 Rev Time 0.00
Received By sgraham Date 2015-08-03 Time 10:33 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2015-05-08 Cont ID  
Sent By sgraham Date 2015-05-08 Time 15:29 Rev Time 0.00
Received By sgraham Date 2015-05-08 Time 15:29 Sent To  
Notes
***NONE***