Plan Review Details - Permit 15040842
Plan Review Stops For Permit 15040842
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-08-10 Cont ID  
Sent By jwitmer Date 2015-08-10 Time   Rev Time 0.00
Received By jwitmer Date 2015-08-10 Time 08:23 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-05-26 Cont ID  
Sent By jwitmer Date 2015-05-26 Time 12:27 Rev Time 0.00
Received By jwitmer Date 2015-05-26 Time 10:59 Sent To  
Notes
2015-05-26 12:21:31BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15040842
 ADD: 901 45TH ST.
 CONT: WESTBROOKE CORPORATION
 TEL: ( 561) 395-4126
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. MAY 26/ 2015
 ACTION: DENIED
  
 1) NEITHER THE ARCHITECTURAL NOR STRUCTURAL SHEETS SHOW
 THE OUSIDE CONDENSORS CU1 & CU2. THE M111 SHOWS THESE
 UNITS ON THE EXTERIOR WALL, CU-1 A (2) TON UNIT AND
 CU-2 A 3/4 TON UNIT.
  
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 2010 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS. L. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE
 THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED
 AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES.
  
 THE PLANS DO NOT PROVIDE THE BRACING SYSTEM (STAND) NOR
 IS THERE A ANCHORING OF THESE STANDS TO THE WALL.
 PLEASE PROVIDE THE WIND DESIGN CRITERIA FOR THESE
 STANDS.
 NOTE THIS IS A BUILDING RISK CATEGORY III. 2010 FBC-B
 TABLE 1604.5.
  
 2) WIND DESIGN CRITERIA
 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
  
  
 2.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 2.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 2.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 2.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 2.5) COMPONENTS & CLADDING PRESSURES POSITIVE &
 NEGATIVE TABLE 1609.2(2) .
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-05-28 Cont ID  
Sent By rlecky Date 2015-05-28 Time 13:55 Rev Time 0.00
Received By rlecky Date 2015-05-28 Time 13:28 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-08-04 Cont ID  
Sent By pleduc Date 2015-08-04 Time   Rev Time 0.00
Received By pleduc Date 2015-08-04 Time 16:58 Sent To  
Notes
2015-08-04 17:09:19THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 SHEET G001 DID NOT INDICATE THE CHANGES PER THE
 ATTACHED LETTER.
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO AS PREVIOUSLY
 STATED:
  
 1) SHEET G001 INDICATES INCORRECT FIRE CODE REFERENCES.
 THESE DO NOT APPEAR TO NEGATIVELY AFFECT YOUR PROJECT;
 HOWEVER, MORE INTENSIVE REVEIW MAY BE NECESSARY. THE
 FIRE INSPECTOR SHALL REVIEW AND INSPECT YOUR PROJECT
 UNDER THE FOLLOWING:
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2010 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2010 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2009 EDITION.
 FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 10, 2010 EDITION.
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION.
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-04-29 Cont ID  
Sent By pleduc Date 2015-04-29 Time   Rev Time 0.00
Received By pleduc Date 2015-04-27 Time 16:49 Sent To  
Notes
2015-04-29 09:55:42THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 1) SHEET G001 INDICATES INCORRECT FIRE CODE REFERENCES.
 THESE DO NOT APPEAR TO NEGATIVELY AFFECT YOUR PROJECT;
 HOWEVER, MORE INTENSIVE REVEIW MAY BE NECESSARY. THE
 FIRE INSPECTOR SHALL REVIEW AND INSPECT YOUR PROJECT
 UNDER THE FOLLOWING:
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2010 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2010 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2009 EDITION.
 FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 10, 2010 EDITION.
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION.
  
 2) SHEET FP001 INDOCATES AN INCORRECT FIRE CODE
 REFERENCE THAT DOES NOT APPEAR TO NEGATIVELY AFFECT
 YOUR PROJECT. SHOP DRAWINGS SHALL BE REVIEWED AND
 INSPECTED UNDER THE REQUIREMENTS OF NFPA 13, 2010.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-08-10 Cont ID  
Sent By jwitmer Date 2015-08-10 Time 09:09 Rev Time 0.00
Received By jwitmer Date 2015-07-27 Time 15:16 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-05-28 Cont ID  
Sent By rlecky Date 2015-05-28 Time 13:56 Rev Time 0.00
Received By rlecky Date 2015-04-23 Time 12:43 Sent To  
Notes
2015-04-23 12:43:23C26
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-08-06 Cont ID  
Sent By ccole Date 2015-08-06 Time 11:16 Rev Time 0.00
Received By ccole Date 2015-08-06 Time 11:16 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-05-14 Cont ID  
Sent By skennedy Date 2015-05-14 Time 16:01 Rev Time 0.00
Received By skennedy Date 2015-04-23 Time 16:01 Sent To  
Notes
2015-05-14 16:16:23REVIEW BY CHRIS COLE.
  
 1) PROVIDE AC LOAD CALCULATIONS FOR THE NEW SYSTEMS IN
 ACCORDANCE WITH SECTION 503.2.1 FBC-10 ENERGY
 CONSERVATION.
 2) SHEET M111: PROVIDE STRUCTURAL DETAILS FOR ANCHORING
 THE CU ANGLE BRACKETS TO THE EXTERIOR WALLS, AND THE
 CU'S TO THE ANGLE BRACKETS- SECTION 301.12 FMC-10.
 3) M111: THE CONDENSATE FROM THE FCU'S IS NOT PERMITTED
 TO DRAIN INTO THE CITY SANITARY SYSTEM IN COMPLIANCE
 WITH SECTION 90-203, WPB AMENDMENTS TO THE FBC-10
 BUILDING CODE.
 PROVIDE AN ALTERNATE LOCATION.
  
 CHRISTOPHER COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-08-07 Cont ID  
Sent By tklarge Date 2015-08-07 Time 05:43 Rev Time 0.00
Received By tklarge Date 2015-08-07 Time 04:53 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-05-09 Cont ID  
Sent By tklarge Date 2015-05-09 Time 05:24 Rev Time 0.00
Received By tklarge Date 2015-05-09 Time 05:05 Sent To  
Notes
2015-05-09 05:12:47SHT. P0001 - THE PLAN NOTES "REMOVED FROM SCOPE" BUT
 VENDOE SHT. V002 SHOWS WHAT APPEARS TO BE A NEW OR
 RELOCATED SINK IN THE CT ROOM. CLARIFY.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  