Plan Review Details - Permit 15040815
Plan Review Stops For Permit 15040815
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-05-27 Cont ID  
Sent By shill Date 2015-05-27 Time 09:32 Rev Time 0.00
Received By shill Date 2015-05-27 Time 09:32 Sent To  
Notes
2015-05-27 09:35:59****PROVISO****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 ALTHOUGH CONTRACTOR HAS INDICATED THAT THE SUBSTRATE IS
 BLOCK, CBS STRUCTURES TYPICALLY HAVE CONCRETE TOP
 SUBSTRATE, BLOCK BOTTOM. THE ANCHOR SPACING PROPOSED
 COMPLIES FOR ANY OF THE INSTALLATION METHODS WITH THE
 EXCEPTION OF MANY WHICH DO NOT ALLOW INSTALLATION INTO
 A BLOCK SUBSTRATE.
  
 THIS PERMIT IS ISSUED SUBJECT TO A CONCRETE SUBSTRATE
 AT THE TOP. IF THIS IS NOT THE JOB CONDITION,
 CONTRACTOR IS TO REVISE THE INSTALLATION SCHEDULE AND
 SUBMIT (AS A REVISION IF PERMIT IS ALREADY ISSUED, AS A
 RESUBMITTAL IF PERMIT HAS NOT YET BEEN ISSUED).
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-05-05 Cont ID  
Sent By shill Date 2015-05-05 Time 14:33 Rev Time 0.00
Received By shill Date 2015-05-05 Time 14:33 Sent To  
Notes
2015-05-05 14:39:15****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 FBC 2010 RESIDENTIAL 301, RESISTANCE TO WIND LOADS:
  
 1. TWO COMPLETE SETS OF PLANS REQUIRED FOR PERMIT
 ISSUANCE, FBC 107. FAILURE TO PROVIDE TWO COMPLETE SETS
 MAY RESULT IN ADDITIONAL FEES CHARGED.
  
 2. PROPOSED INSTALLATION NOT CLEAR. VERTICAL
 INSTALLATION, SPAN SHOULD CORRELATE WITH THE OPENING
 SIZE HEIGHT AND EDGE DISTANCE. THIS NUMBER SHOULD BE
 ANCHOR TO ANCHOR.
  
 3. CONCRETE SUBSTRATE IS STATED. THE BOTTOM IS
 TYPICALLY A FILLED CELL OR HOLLOW, NOT FORMED AND
 POURED CONCRETE. PLEASE REVISE OR CLARIFY.
  
 4. 1" EDGE DISTANCE PROPOSED; 3 1/2" REQUIRED OR A
 FACTOR TO BE APPLIED, SEE CHART ON SHEET 5. MINIMUM
 EDGE DISTANCE IS 2" FOR PANELMATE (AND REQUIRED A .5
 FACTOR).
  
 5. PROVIDE A COPY OF THE CONTRACT FOR THIS JOB, FBC
 109.
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-05-27 Cont ID  
Sent By shill Date 2015-05-27 Time 09:36 Rev Time 0.00
Received By shill Date 2015-05-14 Time 18:42 Sent To  
Notes
2015-05-14 18:42:48TO SH DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-05-05 Cont ID  
Sent By shill Date 2015-05-05 Time 14:39 Rev Time 0.00
Received By shill Date 2015-05-05 Time 14:39 Sent To  
Notes
***NONE***