Plan Review Details - Permit 15040794
Plan Review Stops For Permit 15040794
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-07-21 Cont ID  
Sent By skennedy Date 2015-07-21 Time 14:29 Rev Time 0.00
Received By skennedy Date 2015-07-21 Time 14:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-06-17 Cont ID  
Sent By mmanhong Date 2015-06-17 Time 16:22 Rev Time 0.00
Received By mmanhong Date 2015-06-17 Time 16:22 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-06-17 Cont ID  
Sent By mmanhong Date 2015-06-17 Time 16:17 Rev Time 0.00
Received By mmanhong Date 2015-06-17 Time 16:17 Sent To  
Notes
2015-06-02 05:26:10 
  
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2015-07-13 Cont ID  
Sent By albarran Date 2015-07-13 Time 12:33 Rev Time 0.00
Received By albarran Date 2015-07-13 Time 12:04 Sent To B
Notes
2015-07-13 12:36:01BECAUSE A NEW SET OF DRAWINGS HAS BEEN SUBMITTED, THIS
 HAS TO GO BY EVERY DISCIPLINE FOR RE-STAMP.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2015-06-26 Cont ID  
Sent By albarran Date 2015-06-26 Time 12:02 Rev Time 0.00
Received By albarran Date 2015-06-26 Time 11:57 Sent To  
Notes
2015-06-26 12:02:45ELECTRICAL PROVISO:
 IN AN EFFORT TO EXPEDITE THE CONTRUCTION OF THIS
 PROJECT, THE PERMIT WAS ISSUED PENDING AN ELECTRICAL
 PERMIT. A REVISION TO THESE DRAWINGS, ADDRESSING ALL
 ELECTRICAL REQUIREMENTS PREVIOUSLY STATED TO BE
 SUBMITTED AT THE TIME OF ELECTRICAL PERMIT APPLICATION.
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2015-06-25 Cont ID  
Sent By albarran Date 2015-06-25 Time 16:47 Rev Time 0.00
Received By albarran Date 2015-06-25 Time 16:00 Sent To P
Notes
2015-06-25 16:47:54PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE CORRECTIONS NOTED.
  
 THE FOLLOWING ITEMS SHALL BE CORRECTED AND THE PLANS
 RESUBMITTED FOR A SECOND REVIEW:
  
 1. AN ELECTRICAL PERMIT SHALL BE REQUIRED FOR THIS
 FOUNTAIN.
 2. AS INDICATED IN NEC 680.50, THIS FOUNTAIN SHARES
 WATER W/THE POOL. THEREFORE ALL REQUIREMENTS FOR A
 PERMANENT POOL SHALL APPLY THUS REQUIRING AN
 EQUIPOTENTIAL BOND AROUND THE FOUNTAIN MEETING THE
 REQUIREMENTS OF 680.26.
 3. THE ELECTRICAL DIAGRAM OF PAGE 2 OF 2 SHALL BE
 AMENDED TO INDICATE THE EXACT PANEL WHERE FOUNTAIN
 CONTROL PANEL IS BEING SERVED FROM, FURTHERMORE AS
 INDICATED IN NEC 230.70 A PLAQUE INDICATING THE
 LOCATION OF SUCH DISCONNECT SHALL BE PLACED ON THAT
 SOURCE.
 4. INDICATE ON FLOOR OR SITE PLAN THE LOCATION OF THE
 GENERAL PURPOSE RECEPTACLE SHOWN ON THE RISER. IT SHALL
 COMPLY W/NEC 210.8, 406.8 & 680.58
 5. PROVIDE PANEL SCHEDULE AND LOAD CALCS FOR THE
 CONTROL PANEL
 6. THIS IS AN OUTDOOR FOUNTAIN, PROVIDE CUT SHEETS ON
 LUMINARIES. CONFIRM COMPLIANCE W/NEC 680.23, 680.51 &
 W/FBC-E ?505.
  
 ALL THIS CAN BE ACCOMPLISHED WITH IDENTIFYING NOTES ON
 THE DRAWINGS. YOU DON?T HAVE TO DRAW THE ENTIRE RISER
 DIAGRAM ALL YOU DO HAVE TO INCLUDE A RISER DIAGRAM
 SHOWING THE POWER SOURCE FOR THE CONTROL PANEL.
 INDICATE ITS LOCATION AND ADD THE NOTES INDICATED
 ABOVE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 RESPECTFULLY SUBMITTED,
  
 MIKE ALBARRAN
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-06-18 Cont ID  
Sent By albarran Date 2015-06-18 Time 10:23 Rev Time 0.00
Received By albarran Date 2015-06-18 Time 09:54 Sent To P
Notes
2015-06-18 10:50:12THE SECOND REVIEW FAILED DUE TO FAILURE TO PROVIDE THE
 PREVIOUSLY REQUESTED ITEMS AS INDICATED BELOW FOR
 CLARITY:
 1. FBC- 107.3.5.3 ? ELECTRIC SERVICE RISER WITH WIRE
 SIZES, CONDUIT DETAIL AND GROUNDING DETAIL. COMPLETE
 LOAD CALCULATIONS, PANEL SCHEDULES AND SHOW CIRCUITS ON
 FLOOR PLAN. WHICH WAS INITIALLY REQUESTED WITH
 REFERENCE TO NEC 215.5
 2. NEC 230.70 - YOU SHALL INDICATE THE LOCATION OF THE
 DISCONNECTING MEANS FOR THIS PANEL
 3. NEC 225.34(A) - THE DISCONNECT SHALL BE LABELED TO
 INDICATE LOAD SERVED.
 4. NEC 680.22 - THE CIRCULATING PUMPS SHALL BE
 PROTECTED WITH A GFI CIRCUIT.
  
 YOU CAN VIEW ANY OTHER COMMENTS BY SELECTING THE PLAN
 REVIEWS TAB AT: HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/
 PERMIT/PERM_STATUS.ASPX .
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-05-04 Cont ID  
Sent By rlecky Date 2015-05-04 Time 11:45 Rev Time 0.00
Received By rlecky Date 2015-05-04 Time 11:36 Sent To  
Notes
2015-05-04 11:46:0715040794
 600 OKEECHOBEE BLVD.
 COMMERCIAL FOUNTAIN
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS
  
 PROVIDE FEEDER DETAILS FOR THE NEW ELECTRICAL
 PANELBOARD FOR THE FOUNTAIN. NEC 215.5
  
 VERIFY THAT ALL FEEDERS FROM THE ELECTRICAL SERVICE
 SOURCE INCLUDE A FULL SIZE INSULATED COPPER EQUIPMENT
 GROUNDING CONDUCTOR SIZED IN ACCORDANCE WITH NEC
 250.22, 680.21, 680.25
  
 SHOW THE LOCATION AND SAFETY CLEARANCES REQUIRED FOR
 THE NEW PANEL BOARD SERVING THE FOUNTAIN EQUIPMENT. NEC
 110.26
  
  
 ROBERT LECKY
 ELECTRICAL PLANS REVIEW
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2015-07-21 Cont ID  
Sent By skennedy Date 2015-07-21 Time 14:29 Rev Time 0.00
Received By skennedy Date 2015-07-02 Time 14:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2015-07-01 Cont ID  
Sent By tklarge Date 2015-07-01 Time 05:20 Rev Time 0.00
Received By tklarge Date 2015-07-01 Time 05:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-06-26 Cont ID  
Sent By tklarge Date 2015-06-26 Time 06:55 Rev Time 0.00
Received By tklarge Date 2015-06-25 Time 15:10 Sent To  
Notes
2015-06-25 15:11:14SENT TO MALBARRAN.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-06-25 Cont ID  
Sent By mmanhong Date 2015-06-19 Time 15:10 Rev Time 0.00
Received By skennedy Date 2015-06-17 Time 16:20 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-06-17 Cont ID  
Sent By mmanhong Date 2015-06-17 Time 16:17 Rev Time 0.00
Received By mmanhong Date 2015-04-22 Time 05:18 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 6 Status P Date 2015-07-13 Cont ID  
Sent By tklarge Date 2015-07-13 Time 11:02 Rev Time 0.00
Received By tklarge Date 2015-07-13 Time 11:01 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 5 Status F Date 2015-07-09 Cont ID  
Sent By tklarge Date 2015-07-09 Time 08:46 Rev Time 0.00
Received By tklarge Date 2015-07-09 Time 07:44 Sent To  
Notes
2015-07-09 08:46:441) THE FOUNTAIN PLANS SHOW THE EQUIPMENT ROOM AS BEING
 ON GRADE. THE EQUIPMENT ROOM IS ACTUALLY BELOW GROUND.
 THERE IS NO LOUVERED DOOR ON THIS ROOM AND THERE IS NO
 WAY TO INSTALL A VENT ON THE OPPOSITE WAL AS NOTED ON
 THE PLANSL. SUBMIT REVISE PLANS SHOWING THE EQUIPMENT
 ROOM BELOW GRADE & LOCATION OF THE EQUIPMENT WITHIN THE
 ROOM. THE LOCATION OF THE EQUIPMENT BELOW GRADE WILL
 ALSO AFFECT THE TOTAL DYNAMIC HEAD.RECHECK THE FLOW
 CALCULATIONS TO CONFIRM COMPLIANCE AND CONFIRM
 COMPLIANCE ON THE PLANS.THE SWIMMING POOL AND THE SPA
 WILL REQUIRE REVISIONS FOR THIS SAME REASON.
 2) SHT. 2 SHOWS THE RETURN LINE AS 2" ON THE ISOMETRIC
 BUT THE FOUNTAIN CROSS SECTION SHOWS IT AS 2 1/2" .
 CLARIFY.
 3) VENTILATION SHALL BE PROVIDED IN ACCORDANCE WITH
 2010 FBC SEC.424.1.5.4. SUBMIT CALCULATIONS.
 4) THE OPENING TO THE EQUIPMENT ROOM SHALL COMPLY WITH
 2010 FBC SEC.424.1.5.5.
  
  
 I SUGGEST SOMEONE CALL ME TO DISCUSS THESE COMMENTS SO
 I CAN PROVIDE THE PROPER DIRECTION.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 4 Status F Date 2015-06-30 Cont ID  
Sent By andrian Date 2015-07-01 Time 15:11 Rev Time 0.00
Received By tklarge Date 2015-07-01 Time 05:07 Sent To  
Notes
2015-07-01 05:08:311) PLUMBING IS FAILED, SO IS THE SUB-PERMIT.
 2) PLEASE CLARIFY WHY THERE IS A DRAWING DONE BY HAND
 FOR THE POOL EQUIPMENT IN THE BASEMENT.
 2) I HAVE ABSOLUELY NO IDEA WHAT RELEVANCE THE
 RESUBMITTED PLANS HAVE IN REGARDS TO THE FOUNTAIN. YOU
 HAVE SUBMITTED ONE SET THAT APPEARS TO BE FOR THE SPA
 AND THE PLANS ARE ONLY SHEETS 1 & 2 OF 3. WHERE IS
 SHEET #3? THE OTHER SET APPEARS TO BE FOR THE SWIMMING
 POOL WHICH ARE SHEETS 1 & 3 OF 4. THE SPA AND POOL ARE
 TWO ENTIRELY DIFFERENT PERMIT NUMBERS. THE RESUBMITTED
 PLANS AGAIN, FOR THE FOURTH TIME REVIEWED, DO NOT
 ANSWER MY COMMENTS. PLEASE DO NOT RESUBMIT CORRECTIONS
 UNTIL SOMEONE CAN FIGURE OUT HOW TO ADDRESS MY PLAN
 REVIEW COMMENTS. FOUR TIMES THE PLAN REVIEW FEE SHALL
 BE CHARGED AGAIN FOR A RESUBMITTAL PER F.S. 553.80 (2)
 (B).
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
2015-06-30 15:12:07SEE SUB PERMIT FOR PASSED REVIEW

Review Stop P PLUMBING
Rev No 3 Status F Date 2015-06-26 Cont ID  
Sent By tklarge Date 2015-06-26 Time 06:55 Rev Time 0.00
Received By tklarge Date 2015-06-26 Time 06:39 Sent To  
Notes
2015-06-26 06:44:03NONE OF MY PREVIOUS 7 COMMENTS HAVE BEEN ADDRESSED.
 THIS IS THE THIRD REVIEW I HAVE DONE ASKING FOR THE
 SAME THINGS AND NOTHING HAS BEEN DONE. THESE COMMENTS
 ARE NOT GOING AWAY SO I SUGGEST SOMEONE CONTACT ME TO
 SET UP A MEETING TO DISCUSS WHAT IT IS THAT IS NOT
 CLEAR.
 THE NEXT RESUBMITTAL IS SUBJECT TO 4 TIMES THE PLAN
 REVIEW FEE PER F.S. 553.80 (2) (B).
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2015-06-19 Cont ID  
Sent By tklarge Date 2015-06-19 Time 08:26 Rev Time 0.00
Received By tklarge Date 2015-06-19 Time 06:36 Sent To  
Notes
2015-06-19 08:26:041) SUBMIT MANUFACTURER SPECS. ON THE MAIN DRAINS BEING
 USED. WPB AMEND. TO 2010 FBC SEC. 107.2.1.2ND REQUEST.
 2) SHOW THE DISTANCE BETWEEN THE TWO MAIN DRAINS.WPB
 AMEND. TO 2010 FBC SEC. 107.2.1.2ND REQUEST.
 3) SUBMIT PUMP CURVE INFO.2ND REQUEST.
 4) SUBMIT SPECS. FOR THE PUMP, SKIMMER AND TABLET
 FEEDER.2ND REQUEST.
 5) THE POTABLE WATER SUPPLY SHALL BE PROTECTED WITH A
 RPZ BACKFLOW PREVENTION DEVICE PER THE CITY OF WPB
 CROSS CONNECTION MANUAL. 2ND REQUEST.
 6) THE PLANS AND ISOMETRIC SHOW A 4" MAIN DRAIN BUT THE
 FOUNTAIN CROSS SECTION SHOWS A 6" MAIN DRAIN. CLARIFY.
 2ND REQUEST.
 7) THE PLAN SHOWS 2" OVERFLOW TO ON-SITE STORM DRAIN.
 CLARIFY "ON-SITE STORM DRAIN. THE OVERDLOW SHALL NOT
 DISCHARGE TO THE STORMWATER SYSTEM PER CITY ORDINANCE
 90-203.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-06-02 Cont ID  
Sent By tklarge Date 2015-06-02 Time 05:35 Rev Time 0.00
Received By tklarge Date 2015-06-02 Time 04:46 Sent To  
Notes
2015-06-08 05:13:061) SUBMIT MANUFACTURER SPECS. ON THE MAIN DRAINS BEING
 USED. WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 2) SHOW THE DISTANCE BETWEEN THE TWO MAIN DRAINS.WPB
 AMEND. TO 2010 FBC SEC. 107.2.1.
 3) SUBMIT PUMP CURVE INFO.
 4) SUBMIT SPECS. FOR THE PUMP, SKIMMER AND TABLET
 FEEDER.
 5) THE POTABLE WATER SUPPLY SHALL BE PROTECTED WITH A
 RPZ BACKFLOW PREVENTION DEVICE PER THE CITY OF WPB
 CROSS CONNECTION MANUAL.
 6) THE PLANS AND ISSOMETRIC SHOW A 4" MAIN DRAIN BUT
 THE FOUNTAIN CROSS SECTION SHOWS A 6" MAIN DRAIN.
 CLARIFY.
 7) THE PLAN SHOWS 2" OVERFLOW TO WASTE. CLARIFY
 TERMINATION POINT. THE OVERDLOW SHALL NOT DISCHARGE TO
 THE STORMWATER SYSTEM PER CITY ORDINANCE 90-203.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2015-06-19 Cont ID  
Sent By skennedy Date 2015-06-25 Time 15:10 Rev Time 0.25
Received By eschneid Date 2015-06-19 Time 14:13 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2015-05-29 Cont ID  
Sent By eschneid Date 2015-05-29 Time 16:48 Rev Time 0.25
Received By eschneid Date 2015-05-29 Time 16:48 Sent To P
Notes
***NONE***