| Plan Review Stops For Permit 15040738 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2015-07-29 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2015-07-27 |
Time |
13:47 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2015-07-27 |
Time |
13:47 |
Sent To |
M |
|
| Notes |
| 2015-07-27 13:53:14 | SENT TO CHRIS COLE FOR MECHANICAL REVIEW. JG. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2015-06-30 |
|
|
Cont ID |
|
| Sent By |
J GOMEZ |
Date |
2015-06-30 |
Time |
13:37 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2015-06-30 |
Time |
17:48 |
Sent To |
|
|
| Notes |
| 2015-06-30 13:37:27 | RESIDENTIAL (R3) ADDITION/ALTERATION, SECOND BUILDING | | | REVIEW COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- A) MISSING DRAWINGS. MISSING DRAWINGS A-2, S-1 AND | | | S-2.. | | | | | | B) ONE SET OF SHEET S-2 AND S-3 SUBMITTED IS MISSING | | | THE ENGINEER'S SEAL. SEC. 471 F.S. | | | | | | 2- ENERGY CALCULATIONS SUBMITTED; | | | A) REVISE THE WINDOWS OVERHANG DEPTH AND SEPARATION TO | | | MATCH PLANS. SEC. 103.2.2 OF 2010 FBC-ENERGY | | | CONSERVATION. (REPEAT COMMENT). | | | | | | B) REVISE DOOR TYPE TO MATCH PRODUCT APPROVAL AND | | | PLANS. NOTE: DOORS WITH GLAZING SHALL BE INCLUDED IN | | | THE GLAZING CALCULATIONS. SEE SEC. 405.5.3 OF 2010 | | | FBC-ENERGY CONSERVATION. (REPEAT COMMENT. THERE ARE NO | | | INSULATED DOORS). | | | | | | C) COMPLETE PAGE 5 OF 5. SEC. 103.2.2 OF 2010 | | | FBC-ENERGY CONSERVATION. (REPEAT COMMENT). | | | | | | ***IMPORTANT: WINDOWS AND DOORS LABELS SHOWING THE | | | U-FACTORS AND SHGC FACTORS SPECIFIED ON ITEM #7 ARE | | | REQUIRED FOR INSPECTION. | | | | | | 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | | DCA RULE 9N-3 FOR: | | | A) ROOF TILE ADHESIVE AS SPECIFIED ON SHEET S-4. SEE | | | ROOF TILE PRODUCT APPROVAL FOR LISTED ADHESIVES. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2015-05-26 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2015-05-26 |
Time |
15:08 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2015-05-26 |
Time |
14:45 |
Sent To |
|
|
| Notes |
| 2015-05-26 15:10:20 | RESIDENTIAL (R3) ADDITION/ALTERATION, BUILDING REVIEW | | | COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.) | | | FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED | | | PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY | | | IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT | | | CODE. | | | | | | 2- ENERGY CALCULATIONS SUBMITTED; | | | A) WALL TYPES IS MISSING THE FRAMED WALLS OF THE BONUS | | | ROOM. SEC. 103.2.2 OF 2010 FBC-ENERGY CONSERVATION. | | | | | | B) REVISE THE BUILDING ORIENTATION OF WALLS, DOORS AND | | | WINDOWS TO MATCH THE ACTUAL BUILDING ORIENTATION OF THE | | | EXISTING HOUSE. SEC. 103.2.2 OF 2010 FBC-ENERGY | | | CONSERVATION. | | | | | | C) REVISE THE WINDOWS OVERHANG SEPARATION TO MATCH | | | PLANS. SEC. 103.2.2 OF 2010 FBC-ENERGY CONSERVATION. | | | | | | D) REVISE DOOR TYPE TO MATCH PRODUCT APPROVAL AND | | | PLANS. NOTE: DOORS WITH GLAZING SHALL BE INCLUDED IN | | | THE GLAZING CALCULATIONS. SEE SEC. 405.5.3 OF 2010 | | | FBC-ENERGY CONSERVATION. | | | | | | E) COMPLETE PAGE 5 OF 5. SEC. 103.2.2 OF 2010 | | | FBC-ENERGY CONSERVATION. | | | | | | F) COMPLETE ALL THE INFORMATION ON TOP OF FORM, | | | INCLUDING OWNER, BUILDER NAME, PERMIT OFFICE AND THE | | | JURISDICTION NUMBER. SEC. 103.2.2 OF 2010 FBC-ENERGY | | | CONSERVATION. | | | | | | 3- SEC. R803.2.3.1 OF 2010 FBC-RESIDENTIAL. REQUIRES 8D | | | RING SHANK NAILS MIN. FOR ROOF SHEATHING. PLANS CALL | | | FOR "ALT: 8D .131 DIA. W/ TYP. NAILING PATTERN". | | | PROVIDE ENGINEERING CALCULATIONS SHOWING THAT THE | | | ALTERNATIVE NAILS AND NAILING PATTERN ARE EQUAL OR | | | BETTER THAN THE MIN. REQUIRED BY SEC. R803.2.3.1. (SEC. | | | 107.2.1.3 CITY AMENDMENTS). REVISE GENERAL CONSTRUCTION | | | NOTES ON SHEET A-1, ROOF FRAMING NOTES ON SHEET S-3 AND | | | ALL WALL SECTIONS ON SHEET S-4. | | | | | | 4- SHEET S-4: | | | A) ATTIC INSULATION SHOWN ON THE WALL SECTIONS TO MATCH | | | ENERGY CALCULATIONS. OPTIONAL R19 IS NOT INCLUDED IN | | | THE ENERGY CALCULATIONS. SEC. 103.2.2 OF 2010 | | | FBC-ENERGY CONSERVATION. | | | | | | B) FRAMED WALL REQUIRES 7/8" MIN. STUCCO NOT 3/4". | | | TABLE R702.1(1) OF 2010 FBC-RESIDENTIAL. | | | | | | C) ROOF SHEATHING SPECIFICATIONS SHOWN ON GABLE END | | | DETAIL 4/S-4 DOESN'T MATCH ROOF SHEATHING SPECS SHOWN | | | ON THE OTHER SECTIONS. REVISE AS REQUIRED. SEC. 107.2.1 | | | CITY AMENDMENTS. | | | | | | 5- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | | DCA RULE 9N-3 FOR: | | | A) ROOF TILE. | | | | | | B) ROOF TILE ADHESIVE. SEE ROOF TILE PRODUCT APPROVAL | | | FOR LISTED ADHESIVES. | | | | | | C) PROVIDE LEGIBLE DRAWINGS FOR PRODUCT APPROVAL | | | SUBMITTED FOR SERIES "130 SENTINEL" FIXED WINDOWS, | | | SERIES "238 DESIGNER" FIXED WINDOWS, WINDOW MULLIONS, | | | SERIES "160 SENTINEL" OUTSWING DOORS AND SERIES "110 | | | SENTINEL" SINGLE HUNG WINDOWS. DRAWINGS ARE TOO SMALL. | | | SEC. 107.2.1.4 CITY AMENDMENTS. PLEASE PRINT DRAWINGS | | | IN LANDSCAPE FORMAT INSTEAD OF PORTRAIT FORMAT. THIS | | | WAY DRAWINGS WILL BE MORE LEGIBLE. | | | | | | 6- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING | | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS | | | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. | | | | | | ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH | | | COMMENT TO EXPEDITE THE REVIEW PROCESS. | | | ***PLEASE REMOVE AND REPLACE ANY REVISED SHEET. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2015-06-23 |
|
|
Cont ID |
|
| Sent By |
ALBARRAN |
Date |
2015-06-23 |
Time |
15:00 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2015-06-22 |
Time |
16:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2015-05-14 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2015-05-14 |
Time |
17:10 |
Rev Time |
|
| Received By |
albarran |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2015-05-14 17:58:30 | DISPOSITION AND RESPECTIVE COMMENTS FOR ELECTRICAL PLAN | | | REVIEW | | | APPLICABLE CODES: FBC 2010; WPB AMENDMENTS TO FBC 2010 | | | CHAPTER 1; NEC 2008 | | | REVIEW CYCLE: 1ST REVIEW | | | ACTION: FAILED AS NOTED BELOW: | | | 1. INDICATE THE SCALE USED FOR THE DRAWING TO PROPERLY | | | ASCERTAIN OUTLET PLACEMENT. ALL OUTLETS SHALL BE AS PER | | | NEC 210.52 | | | 2. PER NEC 110.33(B), A PERMANENT LADDER OR STAIRWAY TO | | | THE ATTIC WILL BE REQUIRED TO ACCESS THE AHU. | | | 3. PER NEC 210.63, A SERVICE OUTLET SHALL BE INSTALLED | | | IN THE ATTIC WITHIN SIGHT AND NO MORE THAN 25' FROM THE | | | AHU | | | 4. PER NEC 210.70(A)(3), A LIGHT WITH A SWITCH AT THE | | | ENTRY TO THE ATTIC SHALL BE INSTALLED INSIDE THE ATTIC | | | NEAR THE AHU | | | 5. PER NEC 210.52(E)(3), AN OUTLET SHALL BE INSTALLED | | | IN THE BALCONY | | | 6. PER NEC 314.27(A), CEILING BOXES SHALL BE LISTED TO | | | SUPPORT 50#. | | | 7. PER FBC-R SEC. 314 & 315, ADDITIONAL DETECTORS MAY | | | BE REQUIRED. | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2015-07-29 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2015-07-29 |
Time |
11:23 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2015-07-20 |
Time |
16:32 |
Sent To |
|
|
| Notes |
| 2015-07-20 16:32:50 | RE-SUBMITTAL SENT TO JULIO GOMEZ FOR REVIEW. JG. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2015-06-30 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2015-06-30 |
Time |
18:03 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2015-06-10 |
Time |
17:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2015-05-27 |
Time |
|
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2015-04-21 |
Time |
12:48 |
Sent To |
|
|
| Notes |
| 2015-04-22 12:49:20 | SENT TO R2 SHELF FOR REVIEW. JG. |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2015-06-23 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2015-06-23 |
Time |
14:24 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2015-06-22 |
Time |
16:57 |
Sent To |
|
|
| Notes |
| 2015-06-30 13:48:32 | NO FEES. MU-2015-13706. JG. |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2015-05-26 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2015-05-26 |
Time |
15:07 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2015-05-26 |
Time |
15:07 |
Sent To |
|
|
| Notes |
| 2015-05-26 15:08:52 | 1-BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.) | | | FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED | | | PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY | | | IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT | | | CODE. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2015-07-31 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2015-07-31 |
Time |
07:23 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2015-07-31 |
Time |
06:50 |
Sent To |
|
|
| Notes |
| 2015-07-31 07:33:41 | MECHANICAL PROVISO: | | | 7/31/15 | | | PERMIT #15040738 | | | | | | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO | | | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO | | | INSPECTION WILL RESULT IN FAILED INSPECTIONS(S) AND THE | | | ASSESSMENT OF RE-INSPECTION FEE(S). | | | | | | 1) REVISE THE AC EQUIPMENT SCHEDULE ON THE PLAN TO | | | MATCH THE EQUIPMENT SPECIFIED IN THE AC LOAD | | | CALULATIONS, AND THE ENERGY CALCULATIONS- 2-1/2 TON | | | CARRIER SYSTEM. | | | 2) REVISE THE PLAN TO PROVIDE CODE COMPLIANT ACCESS TO | | | THE AIR HANDLER IN THE ATTIC, AND ALL COMPLIANCES | | | LISTED UNDER SECTION M1305.1.3.2 FBC-10 RESIDENTIAL- | | | SEE ITEMS 1-4. | | 2015-07-29 13:58:30 | NEW EQUIPMENT SIZING CALCULATIONS SUBMITTED. JG. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2015-06-23 |
|
|
Cont ID |
|
| Sent By |
C COLE |
Date |
2015-06-23 |
Time |
14:08 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2015-06-22 |
Time |
16:57 |
Sent To |
|
|
| Notes |
| 2015-06-23 14:11:26 | 1ST REVIEW: FBC 2010 | | | | | | THERE ARE 5 SETS OF A/C LAYOUT DRAWINGS ALL DATED | | | 4/7/15. NONE ARE SIGNED BY THE DESIGNER. PLEASE PROVIDE | | | TWO SETS SIGNED BY THE DESIGNER AND MEETING THE | | | COMMENTS FOR THE PREVIOUS REVIEW. | | | | | | | | | FBC-107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. ALL | | | INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING | | | DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON | | | RESPONSIBLE FOR THE DESIGN. | | | | | | | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2015-05-27 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2015-05-27 |
Time |
10:34 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2015-05-27 |
Time |
10:34 |
Sent To |
|
|
| Notes |
| 2015-05-27 11:00:44 | 1ST REVIEW: FBC 2010 MECHANICAL | | | | | | 1) THE AC PLANS FROM CMI SHOW THE AIR HANDLER IN THE | | | BONUS ROOM ADDITION, HOWEVER THE ELECTRICAL PLANS SHOWS | | | IT IN THE ATTIC: PLEASE MAKE THESE PLANS AGREE ON | | | LOCATION. SEE SECTION M1305.1.3.2FBC-RESIDENTIAL FOR | | | AIR HANDLER IN ATTIC REQUIREMENTS. | | | 2) SUBMIT MANUAL J AC LOAD WORKSHEETS INDICATING THE | | | CALCULATIONS PER EACH ROOM OF THE NEW ADDITION. THE | | | SUBMITTED SUMMARY CALC SHEET DOES NOT INDICATE THE | | | ADDRESS, DIRECTIONAL ORIENTATION OR AREA CALCULATION- | | | SECTION 403.6.1 FBC-10 ENERGY. | | | 3) THE AC PLAN DOESN'T INDICATE A MEANS OF RETURN AIR | | | FROM THE BONUS ROOM- SECTION M1602.4 FBC-10 | | | RESIDENTIAL. | | | 4) PROVIDE A PRIMARY CONDENSATE DISPOSAL PLAN- SHOW | | | TYPE AND SIZE OF PIPING, PIPING RUN, AND DISCHARGE | | | LOCATION. PLACE A NOTE OR DETAIL CLARIFYING HOW | | | SECONDARY DISPOSAL WILL BE ACCOMPLISHED- SECTION | | | M1411.3 FBC-10 RES. | | | 5) SHOW THE REFRIGERATION PIPING RUNS ON THE PLAN. | | | 6) PROVIDE DETAILS FOR INSTALLATION OF THE CONDENSER | | | PAD AND TIE DOWN OF THE UNIT PER SECTIONS- M1305.1.4.1 | | | AND M1307.2.1 FBC-10 RES. | | | 7) ENERGY EFFICIENCY FORM 405-2010: COMPLETE THE CODE | | | COMPLIANCE CHECKLIST ON PAGE 5. | | | | | | CHRISTOPHER COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
3 |
Status |
P |
Date |
2015-07-29 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2015-07-29 |
Time |
11:23 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2015-07-29 |
Time |
11:23 |
Sent To |
|
|
| Notes |
| 2015-07-29 11:25:39 | 1) ROOF TILE NOA 11-0510.02. | | | | | | 2) TILE FOAM NOA 14-0805.01. | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2015-06-30 |
|
|
Cont ID |
|
| Sent By |
J GOMEZ |
Date |
2015-06-30 |
Time |
18:03 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2015-06-30 |
Time |
18:03 |
Sent To |
|
|
| Notes |
| 2015-06-30 18:03:41 | 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | | DCA RULE 9N-3 FOR: | | | A) ROOF TILE ADHESIVE. SEE ROOF TILE PRODUCT APPROVAL | | | FOR LISTED ADHESIVES. | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2015-05-27 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2015-05-27 |
Time |
09:13 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2015-05-27 |
Time |
09:13 |
Sent To |
|
|
| Notes |
| 2015-05-27 09:13:37 | 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | | DCA RULE 9N-3 FOR: | | | A) ROOF TILE. | | | | | | B) ROOF TILE ADHESIVE. SEE ROOF TILE PRODUCT APPROVAL | | | FOR LISTED ADHESIVES. | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2015-06-23 |
|
|
Cont ID |
|
| Sent By |
S GRAHAM |
Date |
2015-06-23 |
Time |
15:26 |
Rev Time |
0.00 |
| Received By |
sgraham |
Date |
2015-06-23 |
Time |
15:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2015-05-08 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2015-05-08 |
Time |
12:48 |
Rev Time |
0.00 |
| Received By |
sgraham |
Date |
2015-05-08 |
Time |
12:48 |
Sent To |
|
|
| Notes |
| 2015-05-08 12:49:22 | 5/8/15 ZONING FAILED | | | | | | 1. SUBMIT TWO UP TO DATE SURVEYS |
|
|