Plan Review Details - Permit 15040719
Plan Review Stops For Permit 15040719
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2015-09-29 Cont ID  
Sent By shill Date 2015-09-29 Time 16:32 Rev Time 0.00
Received By shill Date 2015-09-28 Time 15:52 Sent To ENG
Notes
2015-09-29 16:32:35OK PER RB
 RB GAVE TWO OPTIONS; EITHER A SWALE TO SERVE AS A
 DETENTION AREA, OR WATERPROOF THE WALL.
 PLAN WAS REVISED TO DEPICT A SWALE.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2015-09-14 Cont ID  
Sent By shill Date 2015-09-14 Time 12:32 Rev Time 0.00
Received By shill Date 2015-09-14 Time 12:32 Sent To  
Notes
2015-09-14 12:35:16****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 PLAN REVIEW #3 REVISED ON 9/14/15
  
 1. APPLICANT HAS ALREADY CHANGED THE ELEVATION OF THE
 PROPERT FROM APPROXIMATELY 5' TO 7' IN SOME AREAS. NEW
 PLAN SHOWS A 6" RETAINING WALL RATHER THAN A 2'
 RETAINING WALL, BUT THAT IS BECAUSE THE GRADE WAS
 CHANGED. A DEVELOPMENT PERMIT TO ADD FILL IS REQUIRED
 PER NFIP AND CITY OF WEST PALM BEACH MUNICIPAL CODE
 94-546.
  
 ARROWS WERE ADDED TO THE PLAN. IT APPEARS THAT THIS IS
 THE PROPOSED GRADING PLAN. WATER IS SHOWN AS DIRECTED
 TO A CORNER OF THE PROPERTY, WITH A CITY OWNED (OR
 FUTURE) DRAINAGE STRUCTURES. IT IS NOT CLEAR HOW WATER
 WILL BE DIRECTED AWAY FROM OTHER PROPERTIES, OVER THE
 WALL AND INTO THE DRAINAGE STRUCTURE.
  
 THE DESIGN PROPOSED DOES NOT PREVENT WATER FROM SEEPING
 THROUGH THE BLOCK WALL. TWO OPTIONS WERE SUGGESTED BY
 BUILDING OFFICIAL:
  
 A. FOR THE WALL WHICH IS ADJACENT TO OTHER PROPERTIES /
 CITY DRAINAGE EASEMENT, WALL TO BE GROUTED AND
 WATERPROOFED TO PREVENT WATER FROM LEAKING ONTO
 ADJACENT PARCELS.
  
 B. CREATE A SWALE AROUND THE PERIMETER OF THE PROPERTY
 TO ACT AS A DETENTION AREA.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2015-08-29 Cont ID  
Sent By shill Date 2015-08-29 Time 08:42 Rev Time 0.00
Received By shill Date 2015-08-27 Time 13:25 Sent To  
Notes
2015-08-29 08:44:20****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. APPLICANT HAS ALREADY CHANGED THE ELEVATION OF THE
 PROPERT FROM APPROXIMATELY 5' TO 7' IN SOME AREAS. NEW
 PLAN SHOWS A 6" RETAINING WALL RATHER THAN A 2'
 RETAINING WALL, BUT THAT IS BECAUSE THE GRADE WAS
 CHANGED. A DEVELOPMENT PERMIT TO ADD FILL IS REQUIRED
 PER NFIP AND CITY OF WEST PALM BEACH MUNICIPAL CODE
 94-546.
  
 ARROWS WERE ADDED TO THE PLAN. IT APPEARS THAT THIS IS
 THE PROPOSED GRADING PLAN. WATER IS SHOWN AS DIRECTED
 TO A CORNER OF THE PROPERTY, WITH A CITY OWNED (OR
 FUTURE) DRAINAGE STRUCTURES. IT IS NOT CLEAR HOW WATER
 WILL BE DIRECTED AWAY FROM OTHER PROPERTIES, OVER THE
 WALL AND INTO THE DRAINAGE STRUCTURE.
  
 PLEASE REVISE PLAN TO SHOW HOW WATER RUNOFF WILL NOT
 AFFECT OTHER PROPERTIES, SEE PREVIOUS LISTS FOR CODE
 REFERENCES.
  
 COORDINATION WITH THE ENGINEERING DEPARTMENT MAY BE
 REQUIRED. A CONTACT PERSON WILL BE PROVIDED IF THIS
 COORDINATION IS REQUIRED.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-07-24 Cont ID  
Sent By shill Date 2015-07-24 Time 13:26 Rev Time 0.00
Received By shill Date 2015-07-24 Time 13:26 Sent To  
Notes
2015-07-24 13:31:52****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 SEE PREVIOUS LIST; COMMENTS NOT ADDRESSED.
  
 1. PROVIDE A DRAINAGE PLAN, FBC 2010 RESIDENTIAL 401.3.
  
 110.7 IMPACT OF CONSTRUCTION. ALL CONSTRUCTION ACTIVITY
 REGULATED BY THIS CODE SHALL BE PERFORMED IN
 A MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF
 ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS
 PERMITTED TO AFFECT SAID PROPERTY PURSUANT TO A CONSENT
 GRANTED BY THE APPLICABLE PROPERTY OWNER,
 UNDER TERMS OR CONDITIONS AGREEABLE TO THE APPLICABLE
 PROPERTY OWNER. THIS INCLUDES, BUT IS NOT
 LIMITED TO, THE CONTROL OF DUST, NOISE, WATER OR
 DRAINAGE RUN-OFFS, DEBRIS, AND THE STORAGE OF
 CONSTRUCTION MATERIALS. NEW CONSTRUCTION ACTIVITY SHALL
 NOT ADVERSELY IMPACT LEGAL HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, AND
 MAY REQUIRE SPECIAL DRAINAGE DESIGN
 COMPLYING WITH ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE DRAINAGE PATTERNS OF THE AFFECTED
 SITES. ACCORDINGLY, DEVELOPERS, CONTRACTORS AND OWNERS
 OF ALL NEW RESIDENTIAL DEVELOPMENT, INCLUDING
 ADDITIONS, POOLS, PATIOS, DRIVEWAYS, DECKS OR SIMILAR
 ITEMS, ON EXISTING PROPERTIES RESULTING IN A
 SIGNIFICANT DECREASE OF PERMEABLE LAND AREA ON ANY
 PARCEL OR HAS ALTERED THE DRAINAGE FLOW ON THE
 DEVELOPED PROPERTY SHALL, AS A PERMIT CONDITION,
 PROVIDE A PROFESSIONALLY PREPARED DRAINAGE PLAN
 CLEARLY INDICATING COMPLIANCE WITH THIS PARAGRAPH. UPON
 COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED PROFESSIONAL SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 THE DRAINAGE PLAN SHOULD SHOW THE IMPACT OF FILLING
 THIS PROPERTY ON THE ADJACENT PROPERTIES.
  
 2ND REVIEW - DRAINAGE PLAN SHOWS GRADING TO SHED WATER
 ONTO ADJACENT PROPERTIES WHICH HAVE ELEVATIONS OF LESS
 THAN 5' (AFTER RAISING SUBJECT PROPERTY TO 7').
  
 2. THIS PROPERTY IS IN A SPECIAL HAZARD FLOOD AREA.
 PROVIDE CALCULATIONS TO SHOW THAT THE 2' OF
 UNREINFORCED RETAINING WALL WILL RESIST THE LOADS OF
 SOIL COMBINED WITH WATER.
  
 NOT ADDRESSED. THE WALL IS NOT REINFORCED BY
 CONVENTIONAL METHODS (STEEL, GROUT). SINCE THIS IS NOT
 A TYPICAL CONSTRUCTION METHOD, I CANNOT DETERMINE
 WHETHER OR NOT THE DESIGN OF THE 2' WALL WILL BE
 SUFFICIENT TO RESIST FLOOD LOADS, WIND LOADS. PLEASE
 SHOW COMPLIANCE WITH THE THREE LOADS TO WHICH THE WALL
 WILL BE SUBJECT - SOIL/WATER, FLOOD LOADS (MOVING WATER
 AGAINST THE SIDE), WIND.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-05-18 Cont ID  
Sent By shill Date 2015-05-18 Time 17:18 Rev Time 0.00
Received By shill Date 2015-05-11 Time 10:55 Sent To ENG
Notes
2015-05-18 17:31:32****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. PROVIDE A DRAINAGE PLAN, FBC 2010 RESIDENTIAL 401.3.
  
 110.7 IMPACT OF CONSTRUCTION. ALL CONSTRUCTION ACTIVITY
 REGULATED BY THIS CODE SHALL BE PERFORMED IN
 A MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF
 ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS
 PERMITTED TO AFFECT SAID PROPERTY PURSUANT TO A CONSENT
 GRANTED BY THE APPLICABLE PROPERTY OWNER,
 UNDER TERMS OR CONDITIONS AGREEABLE TO THE APPLICABLE
 PROPERTY OWNER. THIS INCLUDES, BUT IS NOT
 LIMITED TO, THE CONTROL OF DUST, NOISE, WATER OR
 DRAINAGE RUN-OFFS, DEBRIS, AND THE STORAGE OF
 CONSTRUCTION MATERIALS. NEW CONSTRUCTION ACTIVITY SHALL
 NOT ADVERSELY IMPACT LEGAL HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, AND
 MAY REQUIRE SPECIAL DRAINAGE DESIGN
 COMPLYING WITH ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE DRAINAGE PATTERNS OF THE AFFECTED
 SITES. ACCORDINGLY, DEVELOPERS, CONTRACTORS AND OWNERS
 OF ALL NEW RESIDENTIAL DEVELOPMENT, INCLUDING
 ADDITIONS, POOLS, PATIOS, DRIVEWAYS, DECKS OR SIMILAR
 ITEMS, ON EXISTING PROPERTIES RESULTING IN A
 SIGNIFICANT DECREASE OF PERMEABLE LAND AREA ON ANY
 PARCEL OR HAS ALTERED THE DRAINAGE FLOW ON THE
 DEVELOPED PROPERTY SHALL, AS A PERMIT CONDITION,
 PROVIDE A PROFESSIONALLY PREPARED DRAINAGE PLAN
 CLEARLY INDICATING COMPLIANCE WITH THIS PARAGRAPH. UPON
 COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED PROFESSIONAL SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 THE DRAINAGE PLAN SHOULD SHOW THE IMPACT OF FILLING
 THIS PROPERTY ON THE ADJACENT PROPERTIES.
  
 2. THIS PROPERTY IS IN A SPECIAL HAZARD FLOOD AREA.
 PROVIDE CALCULATIONS TO SHOW THAT THE 2' OF
 UNREINFORCED RETAINING WALL WILL RESIST THE LOADS OF
 SOIL COMBINED WITH WATER.
  
  

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2015-11-16 Cont ID  
Sent By cranford Date 2015-11-16 Time 13:19 Rev Time 0.00
Received By cranford Date 2015-11-16 Time 13:06 Sent To I
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status N Date 2015-07-09 Cont ID  
Sent By cranford Date 2015-07-09 Time 12:27 Rev Time 0.00
Received By cranford Date 2015-07-06 Time 15:58 Sent To B
Notes
2015-06-30 07:20:45ROUTED TO ENGINEERING/CC

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2015-07-14 Cont ID  
Sent By skennedy Date 2015-05-19 Time 08:37 Rev Time 0.00
Received By skennedy Date 2015-05-19 Time 15:26 Sent To  
Notes
2015-05-20 10:26:321. CALL OUT THE PROPERTY LINE ON THE SECTION DETAIL AND
 LABEL THE SET BACK DISTANCE.
  
 2. THE PROPOSED CONSTRUCTION IS LOCATED WITHIN THE
 100-YR FLOOD BOUNDARY WITH A BASE FLOOD ELEVATION OF 7
 FT NGVD. PLEASE DEMONSTRATE THE PROJECT COMPLIES WITH
 SECTION 94-546 OF THE CODE OF ORDINANCES.
  
 - ALL NEW CONSTRUCTION AND SUBSTANTIAL IMPROVEMENTS
 SHALL BE ANCHORED TO PREVENT FLOTATION, COLLAPSE OR
 LATERAL MOVEMENT OF THE STRUCTURE, AND SHALL BE
 CONSTRUCTED WITH MATERIALS AND UTILITY EQUIPMENT
 RESISTANT TO FLOOD DAMAGE BY METHODS AND PRACTICES THAT
 MINIMIZE FLOOD DAMAGE.
  
 - ELECTRICAL, PLUMBING AND OTHER UTILITY CONNECTIONS
 ARE PROHIBITED BELOW THE BASE FLOOD ELEVATION.
  
 KELLY CRANFORD, P.E.
 LAND DEVELOPMENT ENGINEER
 PUBLIC WORKS DEPARTMENT
 CITY OF WEST PALM BEACH
 [email protected]
 561-494-1098 (OFFICE)

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2015-11-16 Cont ID  
Sent By cranford Date 2015-11-16 Time 13:19 Rev Time 0.00
Received By cranford Date 2015-09-21 Time 08:59 Sent To  
Notes
2015-09-29 16:32:559/29 TO ENG BOX
  
2015-09-22 08:59:51RESUB ROUTED TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-08-29 Cont ID  
Sent By shill Date 2015-08-29 Time 09:42 Rev Time 0.00
Received By shill Date 2015-08-19 Time 13:11 Sent To  
Notes
2015-08-19 13:11:44RESUB ROUTED TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-07-24 Cont ID  
Sent By shill Date 2015-07-24 Time 14:06 Rev Time 0.00
Received By shill Date 2015-06-30 Time 07:19 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-05-20 Cont ID  
Sent By cranford Date 2015-05-20 Time 11:01 Rev Time 0.00
Received By cranford Date 2015-04-21 Time 13:41 Sent To  
Notes
2015-04-22 13:41:40SENT TO ZONING SHELF FOR REVIEW. JG.

Review Stop Z ZONING
Rev No 2 Status P Date 2015-07-14 Cont ID  
Sent By   Date 2015-07-14 Time   Rev Time 0.00
Received By   Date 2015-07-14 Time   Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2015-04-23 Cont ID  
Sent By sgraham Date 2015-04-23 Time 08:55 Rev Time 0.00
Received By sgraham Date 2015-04-23 Time 08:55 Sent To B
Notes
***NONE***