| 2015-04-26 11:26:06 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15040712 |
| | ADD: 3710 WHITEHALL DR. SUITE # 206 |
| | CONT: HIGH ROCK BUILDERS |
| | TEL: (561) 714-8836 |
| | E-MAIL: [email protected] |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: SUN. APRIL 26/2015 |
| | ACTION: DENIED |
| | |
| | NOTICE!!!!!!!! CHAPTER 553.80(2)(B) FLORIDA STATUTES |
| | STATES THAT A LOCAL GOVERNMENT SHALL IMPOSE A FEE OF |
| | FOUR TIMES THE FEE FOR PLAN REVIEW, IF PLANS ARE |
| | REJECTED (3) OR MORE TIMES FOR REPEATED FAILURE TO |
| | CORRECT A CODE VIOLATION. |
| | I WOULD SUGGEST A MEETING BEFORE THE NEXT SUBMITTAL, |
| | THIS WILL BE THE (3RD) REVIEW. |
| | |
| | |
| | 1) 2ND REVIEW. THE SUBMITTED FLOOR TILE UNDERLAYMENT |
| | PROFLEX MAXIUM SIM-90, THE SUBMITTED TEST REPORT IS FOR |
| | A 8 INCH SLAB, (TO BE VERIFIED BY AN ENGINEER) WAS |
| | TESTED ALSO WITH A DROPPED CEILING ( SEE PAGE 2 OF 4) A |
| | 10 AIR PLENUM, 3 1/2 INCHES OF INSULATION, A GYPSUM |
| | BOARD RIGID CEILING SYSTEM BY ARMSTRONG. TESTING IS TO |
| | BE WITH THE TILE MASTIC, UNDERLAYMENT AND CONCRETE |
| | SLAB. THE ABOVE MENTIONED UNIT MAY HAVE A DROPPED |
| | CEILING OVER THE KITCHEN, DINING ROM AND BATHROOM |
| | AREAS, THIS IS WHERE THE A/C DUCTWORK IS RUN, THE |
| | REMAINDER OF THE UNIT IS CONCRETE DECK. THIS IS WHY THE |
| | REPORTS CAN NOT INCLUDE DROPPED CEILINGS. |
| | |
| | NOTE THE SUBMITTED REPORT WAS FOR ASTM E -492 ONLY. NO |
| | TESTING WAS SUBMITTED FOR COMMENT (1B) ASTM E-90 OR |
| | COMMENT (2) FLAME SPREAD OF NOT OVER 50 FOR BUILDING |
| | TYPES III, IV AND V. ASTM E84 OR UL 723. |
| | |
| | NOTE IF THE BUILDING TYPE IS TYPE I OR TYPE II THE |
| | FLAME SPREAD CAN BE UP TO 200 WHEN TESTED TO ASTM E-84 |
| | OR UL 723. |
| | |
| | COMMENTS FROM REVIEW # 1: |
| | 1A) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 1B) FBC-B 2010 1207.2 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | 2) FLAME SPREAD- FBC-B 2010 603.1.2 EXCEPTION 2. |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| | |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | 703.4 NONCOMBUSTIBILITY TESTS. |
| | THE TESTS INDICATED IN SECTIONS 703.4.1 AND 703.4.2 |
| | SHALL SERVE AS CRITERIA FOR ACCEPTANCE OF BUILDING |
| | MATERIALS AS SET FORTH IN SECTIONS 602.2, 602.3 AND |
| | 602.4 IN TYPE I, II, III AND IV CONSTRUCTION. THE TERM |
| | ?NONCOMBUSTIBLE? DOES NOT APPLY TO THE FLAME SPREAD |
| | CHARACTERISTICS OF INTERIOR FINISH OR TRIM MATERIALS. A |
| | MATERIAL SHALL NOT BE CLASSIFIED AS A NONCOMBUSTIBLE |
| | BUILDING CONSTRUCTION MATERIAL IF IT IS SUBJECT TO AN |
| | INCREASE IN COMBUSTIBILITY OR FLAME SPREAD BEYOND THE |
| | LIMITATIONS HEREIN ESTABLISHED THROUGH THE EFFECTS OF |
| | AGE, MOISTURE OR OTHER ATMOSPHERIC CONDITIONS. |
| | |
| | 703.4.1 ELEMENTARY MATERIALS. |
| | MATERIALS REQUIRED TO BE NONCOMBUSTIBLE SHALL BE TESTED |
| | IN ACCORDANCE WITH ASTM E 136. |
| | |
| | 703.4.2 COMPOSITE MATERIALS. |
| | MATERIALS HAVING A STRUCTURAL BASE OF NONCOMBUSTIBLE |
| | MATERIAL AS DETERMINED IN ACCORDANCE WITH SECTION |
| | 703.4.1 WITH A SURFACING NOT MORE THAN 0.125 INCH (3.18 |
| | MM) THICK THAT HAS A FLAME SPREAD INDEX NOT GREATER |
| | THAN 50 WHEN TESTED IN ACCORDANCE WITH ASTM E 84 OR UL |
| | 723 SHALL BE ACCEPTABLE AS NONCOMBUSTIBLE MATERIALS. |
| | |
| | JAMES A. WITMER CBO |