Plan Review Details - Permit 15040691
Plan Review Stops For Permit 15040691
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-09-18 Cont ID  
Sent By wjolin Date 2015-09-18 Time 13:03 Rev Time 0.00
Received By wjolin Date 2015-09-18 Time 13:01 Sent To M
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-04-22 Cont ID  
Sent By wjolin Date 2015-04-22 Time 14:37 Rev Time 0.00
Received By wjolin Date 2015-04-22 Time 13:55 Sent To M
Notes
2015-04-22 14:37:16600 OKEECHOBEE BOULEVARD
 PERMIT #15040691
 MASTER #14050111
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE PERMIT VALUE OF $5,000 APPEARS TO BE UNDERVALUED.
 SUBMIT A COPY OF THE OFFICIAL SIGNED CONTRACT. THE
 TOTAL PERMIT JOB VALUE NEEDS TO INCLUDE MATERIALS AND
 LABOR.
  
 PROVIDE DETAILED SCALABLE SHOP DRAWINGS. THE PLANS
 SUBMITTED ARE ONLY SCHEMATIC IN NATURE. PLANS DO NOT
 INDICATE THE FLOOR LEVELSL OR LOCATIONS OF WHERE THESE
 HOOD FIRE SUPPRESSION SYSTEMS ARE LOCATED. PER NFPA 96
 SECTION 10.9.1 WHERE REQUIRED, COMPLETE DRAWINGS OF THE
 SYSTEM INSTALLATION, INCLUDING THE HOOD(S), EXHAUST
 DUCT(S), AND APPLIANCES,
 ALONG WITH THE INTERFACE OF THE FIRE-EXTINGUISHING
 SYSTEM DETECTORS, PIPING, NOZZLES, FUEL AND ELECTRIC
 POWER SHUTOFF DEVICES, AGENT STORAGE CONTAINER(S), AND
 MANUAL ACTUATION DEVICE(S), SHALL BE SUBMITTED TO THE
 AUTHORITY HAVING JURISDICTION.
  
 SUBMIT EQUIPMENT CUTSHEETS FOR THE ANSUL R-102 SYSTEMS.
  
 THE PLANS INDICATE "COMPLIANCE WITH NFPA 96 AND NFPA
 17"; HOWEVER, NO EDITIONS OF THE STANDARDS ARE
 INDICATED.
  
 THE PLANS INDICATE ONLY ELECTRIC UNDER THE HOOD TO BE
 SHUTDOWN. UPON ACTIVATION OF ANY FIRE-EXTINGUISHING
 SYSTEM FOR A COOKING OPERATION, ALL SOURCES OF FUEL AND
 ELECTRICAL POWER THAT PRODUCE HEAT TO ALL EQUIPMENT
 REQUIRING PROTECTION BY THAT SYSTEM SHALL AUTOMATICALLY
 SHUT OFF.
  
 HOODS INSTALLED END TO END, BACK TO BACK, OR BOTH, OR
 SHARING A COMMON DUCTWORK, AND HAVING A
 GREASE-PRODUCING APPLIANCE(S) LOCATED UNDER ONE OR MORE
 OF THE HOODS SHALL BE CONSIDERED A SINGLE HAZARD AREA
 REQUIRING SIMULTANEOUS AUTOMATIC FIRE PROTECTION IN ALL
 HOODS AND DUCTS.
  
 THE PLANS SHOW MANUAL PULL STATIONS; HOWEVER, THE
 LOCATIONS ARE GENERIC. AT LEAST ONE MANUAL ACTUATION
 DEVICE SHALL BE LOCATED A MINIMUM OF 10 FEET AND A
 MAXIMUM OF 20 FEET FROM THE PROTECTED KITCHEN
 APPLIANCE(S) WITHIN THE PATH OF EGRESS. MANUAL
 ACTIVATION USING A CABLE-OPERATED PULL STATION SHALL
 NOT REQUIRE MORE THAN 178 N (40 LB) OF FORCE, WITH A
 PULL MOVEMENT NOT TO EXCEED 14-INCHES TO ACTIVATE THE
 AUTOMATIC FIRE-EXTINGUISHING EQUIPMENT.
  
 A PLACARD SHALL BE CONSPICUOUSLY PLACED NEAR EACH
 EXTINGUISHER THAT STATES THAT THE FIRE PROTECTION
 SYSTEM SHALL BE ACTIVATED PRIOR TO USING THE FIRE
 EXTINGUISHER. INSTRUCTION SHALL BE PROVIDED TO
 EMPLOYEES REGARDING THE PROPER USE OF PORTABLE FIRE
 EXTINGUISHERS AND THE MANUAL ACTIVATION OF
 FIRE-EXTINGUISHING EQUIPMENT.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-09-29 Cont ID  
Sent By ccole Date 2015-09-29 Time 09:51 Rev Time 0.00
Received By ccole Date 2015-08-25 Time 12:50 Sent To  
Notes
2015-08-25 12:50:39ROUTED TO FIRE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-04-30 Cont ID  
Sent By hmoser Date 2015-04-30 Time 10:01 Rev Time 0.00
Received By hmoser Date 2015-04-22 Time 13:55 Sent To  
Notes
2015-04-21 11:25:51ROUTED TO FIRE

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-09-29 Cont ID  
Sent By ccole Date 2015-09-29 Time 09:48 Rev Time 0.00
Received By ccole Date 2015-09-29 Time 09:42 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-04-30 Cont ID  
Sent By hmoser Date 2015-04-30 Time 09:33 Rev Time 0.00
Received By hmoser Date 2015-04-30 Time 09:33 Sent To  
Notes
2015-04-30 10:01:19PLAN DENIED
 1) REFER TO SECTION 904.11.1 MANUAL SYSTEM OPERATION
 2010 FBC
 2) PROVIDE A COPY OF THE CONTRACT FOR THE JOB VALUE
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  