Plan Review Details - Permit 15040684
Plan Review Stops For Permit 15040684
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-04-24 Cont ID  
Sent By dhayes Date 2015-04-24 Time 14:18 Rev Time 0.00
Received By dhayes Date 2015-04-24 Time 14:17 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-04-22 Cont ID  
Sent By dhayes Date 2015-04-22 Time 15:18 Rev Time 0.00
Received By dhayes Date 2015-04-22 Time 15:12 Sent To  
Notes
2015-04-22 15:18:03REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1) PROVIDE ADDITIONAL INFORMATION FROM THE MANUFACTURER
 THAT STATES THE RETROFIT KIT IS COMPATABLE WITH ALL
 PANEL TYPES OR AT THE VERY LEAST THE LANEL TYPE YOU ARE
 REPLACING.
  
 2) PROVIDE A COMPLETE RISER DIAGRAM THAT CLARIFIES THE
 COMPLETE SCOPE OF WORK AS WELL AS THE WIRE TYPE AND
 SIZE IN EACH OF THE FEEDER CONDUITS AND NIPPLES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-04-24 Cont ID  
Sent By dhayes Date 2015-04-24 Time 14:18 Rev Time 0.00
Received By dhayes Date 2015-04-24 Time 14:17 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-04-22 Cont ID  
Sent By dhayes Date 2015-04-22 Time 15:18 Rev Time  
Received By dhayes Date   Time   Sent To  
Notes
2015-04-20 11:36:28ELECTRICAL LESS THAN 5K