Plan Review Details - Permit 15040655
Plan Review Stops For Permit 15040655
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-06-17 Cont ID  
Sent By mmanhong Date 2015-06-17 Time 16:31 Rev Time 0.00
Received By mmanhong Date 2015-06-17 Time 16:31 Sent To  
Notes
2015-06-17 16:32:17REVIEW BY SKENNEDY

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-05-08 Cont ID  
Sent By skennedy Date 2015-05-08 Time 16:42 Rev Time 0.00
Received By skennedy Date 2015-05-08 Time 16:42 Sent To  
Notes
2015-05-08 16:46:351ST REVIEW: FBC 2010
  
 1009.3.2 SUBMERGED DEPTH.
 SLOPED ENTRIES SHALL EXTEND TO A DEPTH OF 24 INCHES
 (610 MM) MINIMUM AND 30 INCHES (760 MM) MAXIMUM BELOW
 THE STATIONARY WATER LEVEL. WHERE LANDINGS ARE REQUIRED
 BY 405.7, AT LEAST ONE LANDING SHALL BE LOCATED 24
 INCHES (610 MM) MINIMUM AND 30 INCHES (760 MM) MAXIMUM
 BELOW THE STATIONARY WATER LEVEL.
  
 REVISE SECTION BB ON SHEET 4 TO PROVIDE A LANDING
  
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  
  
2015-05-04 11:33:08 
 15040663
 600 OKEECHOBEE BLVD.
 COMMERCIAL POOL
  
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS
  
 PROVIDE FEEDER DETAILS FOR THE NEW ELECTRICAL
 PANELBOARD FOR THE POOL. NEC 215.5
  
 VERIFY THAT ALL FEEDERS FROM THE ELECTRICAL SERVICE
 SOURCE INCLUDE A FULL SIZE INSULATED COPPER EQUIPMENT
 GROUNDING CONDUCTOR SIZED IN ACCORDANCE WITH NEC
 250.22, 680.21, 680.25
  
 SHOW THE LOCATION AND SAFETY CLEARANCES REQUIRED FOR
 THE NEW PANEL BOARD SERVING THE SPA EQUIPMENT. NEC
 110.26
  
 VERIFY ALL SIGHT LIGHTING AND DECORATIVE LIGHTING IS
 GFCI PROTECTED AND LOCATED MORE THAN 5 FEET FROM THE
 POOL AND ABOVE 12 FEET. NEC 680.42, 680.22 (C),
 680.43(B)
  
  
 ROBERT LECKY
 ELECTRICAL PLANS REVIEW
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2015-06-26 Cont ID  
Sent By albarran Date 2015-06-26 Time 11:48 Rev Time 0.00
Received By albarran Date 2015-06-26 Time 11:41 Sent To P
Notes
2015-06-26 11:49:07ELECTRICAL PROVISO:
 IN AN EFFORT TO EXPEDITE THE CONTRUCTION OF THIS
 PROJECT, THE PERMIT WAS ISSUED PENDING AN ELECTRICAL
 PERMIT. A REVISION TO THESE DRAWINGS, ADDRESSING ALL
 ELECTRICAL REQUIREMENTS PREVIOUSLY STATED TO BE
 SUBMITTED AT THE TIME OF ELECTRICAL PERMIT APPLICATION.
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2015-06-25 Cont ID  
Sent By albarran Date 2015-06-25 Time 18:11 Rev Time 0.00
Received By albarran Date 2015-06-25 Time 17:22 Sent To P
Notes
2015-06-25 18:12:07PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE CORRECTIONS NOTED.
  
 THE FOLLOWING ITEMS SHALL BE CORRECTED AND THE PLANS
 RESUBMITTED FOR A SECOND REVIEW:
  
 1. AN ELECTRICAL PERMIT FOR THIS WORK SHALL BE
 REQUIRED.
 2. THE ELECTRICAL DIAGRAM OF PAGE 3 OF 4 SHALL BE
 AMENDED TO INDICATE THE EXACT PANEL WHERE THIS POOL
 PANEL IS BEING SERVED FROM, FURTHERMORE AS INDICATED IN
 NEC 230.70 A PLAQUE INDICATING THE LOCATION OF SUCH
 DISCONNECT SHALL BE PLACED ON ?PANEL P?.
 3. PROVIDE PANEL SCHEDULE AND LOAD CALCS FOR THE NEW
 ?WP? PANEL. (THIS NEW PANEL IS LABELED ?WP? AS IS FOR
 THE SPA. IF THEY ARE ONE AND THE SAME, INDICATE SO
 OTHERWISE LABEL THEM DIFFERENTLY. THESE CALCS SHOULD
 INDICATE FEEDER CONDUCTOR TYPE & SIZING AS WELL.
 4. THIS IS AN OUTDOOR COMMERCIAL POOL, THUS AREA
 LIGHTING IS REQUIRED. INDICATE POWER SOURCE FOR SUCH
 LIGHTING & MAKE SURE IT COMPLIES W/FBC-E ?505.
 5. PROVIDE DOCUMENTATION ON ADA LIFT IF IT HAS ANY
 ELECTRICAL COMPONENTS.
 6. PROVIDE A DETAIL OF THE EQUIPMENT ROOM; INDICATE THE
 REQUIRED CLEARANCES.
  
 ALL THIS CAN BE ACCOMPLISHED WITH IDENTIFYING NOTES ON
 THE DRAWINGS. YOU DON?T HAVE TO DRAW THE ENTIRE RISER
 DIAGRAM AS SHOWN ON E4.01 AS IT DOESN?T PERTAIN TO THIS
 PERMIT, BUT YOU DO HAVE TO INCLUDE A RISER DIAGRAM
 SHOWING PANEL P AS THE SOURCE OF SERVICE. INDICATE ITS
 LOCATION AND ADD THE NOTES INDICATED ABOVE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 RESPECTFULLY SUBMITTED,
  
 MIKE ALBARRAN
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-06-18 Cont ID  
Sent By albarran Date 2015-06-18 Time 11:42 Rev Time 0.00
Received By albarran Date 2015-06-18 Time 10:58 Sent To P
Notes
2015-06-18 11:42:28THE SECOND REVIEW FAILED DUE TO FAILURE TO PROVIDE THE
 PREVIOUSLY REQUESTED ITEMS AS INDICATED BELOW FOR
 CLARITY:
 1. FBC- 107.3.5.3 - ELECTRIC SERVICE RISER WITH WIRE
 SIZES, CONDUIT DETAIL AND GROUNDING DETAIL. COMPLETE
 LOAD CALCULATIONS, PANEL SCHEDULES AND SHOW CIRCUITS ON
 FLOOR PLAN. WHICH WAS INITIALLY REQUESTED WITH
 REFERENCE TO NEC 215.5
 2. NEC 230.70 - YOU SHALL INDICATE THE LOCATION OF THE
 DISCONNECTING MEANS FOR THIS PANEL
 3. NEC 225.34(A) - THE DISCONNECT SHALL BE LABELED TO
 INDICATE LOAD SERVED.
 YOU CAN VIEW ANY OTHER COMMENTS BY SELECTING THE PLAN
 REVIEWS TAB AT: HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/
 PERMIT/PERM_STATUS.ASPX .
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-05-04 Cont ID  
Sent By rlecky Date 2015-05-04 Time 11:33 Rev Time 0.00
Received By rlecky Date 2015-05-04 Time 11:31 Sent To  
Notes
2015-05-08 16:42:02 
 15040663
 600 OKEECHOBEE BLVD.
 COMMERCIAL POOL
  
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS
  
 PROVIDE FEEDER DETAILS FOR THE NEW ELECTRICAL
 PANELBOARD FOR THE POOL. NEC 215.5
  
 VERIFY THAT ALL FEEDERS FROM THE ELECTRICAL SERVICE
 SOURCE INCLUDE A FULL SIZE INSULATED COPPER EQUIPMENT
 GROUNDING CONDUCTOR SIZED IN ACCORDANCE WITH NEC
 250.22, 680.21, 680.25
  
 SHOW THE LOCATION AND SAFETY CLEARANCES REQUIRED FOR
 THE NEW PANEL BOARD SERVING THE SPA EQUIPMENT. NEC
 110.26
  
 VERIFY ALL SIGHT LIGHTING AND DECORATIVE LIGHTING IS
 GFCI PROTECTED AND LOCATED MORE THAN 5 FEET FROM THE
 POOL AND ABOVE 12 FEET. NEC 680.42, 680.22 (C),
 680.43(B)
  
  
 ROBERT LECKY
 ELECTRICAL PLANS REVIEW
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2015-06-30 Cont ID  
Sent By Mgonzale Date 2015-06-30 Time   Rev Time 1.00
Received By mgonzale Date 2015-06-30 Time   Sent To I
Notes
2015-06-30 12:46:27PROVISOS:
  
 DECHLORINATED SWIMMING POOL DISCHARGES ARE AUTHORIZED
 IN FLORIDA IN ACCORDANCE WITH 62-624.200(2)(Q), F.A.C.;
 PROVIDED THAT THEY DO NOT CAUSE A VIOLATION OF WATER
 QUALITY STANDARDS."
 SUBSECTION 62-302.530(19), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.) LIMITS THE DISCHARGE OF CHLORINE TO SURFACE
 WATER BODIES TO < 0.01 MILLIGRAM PER LITER (MG/L).
 IN ADDITION, TURBIDITY ASSOCIATED WITH BACKWASHING AND
 CLEANING CAN ALSO VIOLATE SURFACE WATER QUALITY
 STANDARDS THEREFORE POOL DISCHARGES MUST BE CONTROLLED
 AND PROGRAMMED.
 FOR REFERENCE PLEASE KNOW THAT THE FLORIDA DEPARTMENT
 OF HEALTH REGULATES PUBLIC SWIMMING POOLS AND BATHING
 PLACES. SUBSECTION 64E-9.007 (15) ?POOL WASTE WATER
 DISPOSAL? STATES IN PART: ?POOL WASTE WATER SHALL BE
 DISCHARGED THROUGH AN AIR GAP; DISPOSAL SHALL BE TO
 SANITARY SEWERS, STORM SEWERS, DRAINFIELDS, OR BY OTHER
 MEANS, IN ACCORDANCE WITH LOCAL MUNICIPAL AND BUILDING
 OFFICIAL REQUIREMENTS INCLUDING OBTAINING ALL NECESSARY
 PERMITS.?
  
 GUIDANCE:
 TO HELP PROTECT FLORIDA?S ENVIRONMENT, THE FOLLOWING
 BEST MANAGEMENT PRACTICES SHOULD BE FOLLOWED WHEN
 DRAINING SWIMMING POOLS OR DISCHARGING FILTER BACKWASH
 INTO THE ENVIRONMENT.
 ONLY DRAIN YOUR POOL WHEN NECESSARY. AVOID
 DRAINING/BACKWASHING YOUR POOL DURING PERIODS OF
 DROUGHT AND DURING SIGNIFICANT RAINFALL EVENTS. DO NOT
 DRAIN YOUR POOL WHEN WATERING RESTRICTIONS ARE IN
 PLACE.
 BEFORE DRAINING YOUR POOL, ALLOW THE WATER TO STAND FOR
 AT LEAST 48 HOURS AFTER THE LAST ADDITION OF CHLORINE
 OR UNTIL THE FREE CHLORINE RESIDUAL IS < 0.01 MG/L. (IF
 YOU NEED TO DRAIN YOUR POOL QUICKLY, YOU CAN PURCHASE
 CHLORINE-NEUTRALIZING CHEMICALS SUCH AS SODIUM
 THIOSULFATE AT YOUR LOCAL POOL SUPPLY COMPANY.)
 TEST THE FREE CHLORINE RESIDUAL BEFORE DISCHARGING. A
 FREE CHLORINE RESIDUAL SHOULD NOT BE DETECTED. THE
 CHLORINE RESIDUAL CAN BE TESTED USING A STANDARD POOL
 TEST KIT. (REFER TO 64E-9.004 (11), F.A.C. FOR
 ADDITIONAL INFORMATION.)
 THE WATER SHOULD BE CLEAR AND FREE OF SOLIDS.
 THE PH MUST BE BETWEEN 6.5 AND 8.5 BEFORE IT IS
 DISCHARGED.
 ALGAECIDES CONTAINING COPPER OR SILVER CAN INTERRUPT
 NORMAL ALGAL AND PLANT GROWTH IN SURFACE WATER BODIES
 AND SHOULD BE USED WITH CAUTION. FOLLOW THE
 MANUFACTURER?S INSTRUCTIONS BEFORE DISCHARGING WATER
 THAT HAS HAD AN ALGAECIDE ADDED RECENTLY.
 CONTROL THE RATE OF DISCHARGE ACROSS YOUR PROPERTY TO
 AVOID EROSION AND NUISANCE CONDITIONS FOR NEIGHBORING
 PROPERTIES. NUISANCE CONDITIONS SUCH AS THE CREATION OF
 ODORS, MOSQUITO BREEDING CONDITIONS, OR FLOODING CAN
 OCCUR WHEN WATER IS PONDED FOR A PROLONGED PERIOD.
 DIRECT THE DISCHARGE OVER A VEGETATED SURFACE SO THAT
 SOME LEVEL OF FILTRATION CAN OCCUR.
 DO NOT DISCHARGE ON AREAS RECENTLY TREATED WITH
 HERBICIDES OR PESTICIDES.
  
 GUIDANCE IF DISPOSING TO CITY SANITARY SEWER SYSTEM:
 POOL AND SPA WASTEWATER SHOULD NOT BE DISCHARGED INTO
 THE SANITARY SEWER SYSTEM WITHOUT THE PERMISSION OF THE
 WASTEWATER TREATMENT FACILITY.
 AVOID DISCHARGING TO THE SANITARY SEWER SYSTEM DURING
 OR IMMEDIATELY AFTER A SIGNIFICANT RAINFALL EVENT.
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2015-05-02 Cont ID  
Sent By tklarge Date 2015-05-02 Time 09:33 Rev Time 0.00
Received By tklarge Date 2015-05-02 Time 07:56 Sent To  
Notes
2015-05-02 09:34:26SEPARATE PERMIT AND REVIEW REQUIRED FOR GAS. TKL.
 A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A GAS PERMIT IS REQUIRED FOR A CONTRACTOR TO
 PERFORM THE RELATED WORK. PROVIDE COMPLETE PLANS AND
 GAS RISER THAT REFLECTS THE ENTIRE SCOPE OF GAS WORK TO
 BE DONE.
 WPB AMEND. TO FBC SEC. 107.2.1.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-06-29 Cont ID  
Sent By tklarge Date 2015-06-29 Time 11:42 Rev Time 0.00
Received By tklarge Date 2015-06-25 Time 15:06 Sent To  
Notes
2015-06-25 15:06:52GIVEN TO MALBARRAN

Review Stop I INCOMING/PROCESSING
Rev No 2 Status   Date 2015-06-25 Cont ID  
Sent By skennedy Date 2015-06-19 Time 15:05 Rev Time 0.00
Received By skennedy Date 2015-06-11 Time 18:01 Sent To  
Notes
2015-06-11 18:04:31ROUTED TO POOL BIN

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-05-08 Cont ID  
Sent By skennedy Date 2015-05-08 Time 16:42 Rev Time 0.00
Received By skennedy Date 2015-04-17 Time   Sent To  
Notes
2015-04-17 17:41:18SENT TO ZONING

Review Stop P PLUMBING
Rev No 3 Status P Date 2015-06-29 Cont ID  
Sent By tklarge Date 2015-06-29 Time 11:38 Rev Time 0.00
Received By tklarge Date 2015-06-29 Time 11:09 Sent To  
Notes
2015-06-29 11:42:27****PROVISO*** - THE DISCHARGE OF THE POOL WATER WASTE
 TO THE SANITARY OR THE THE STORMWATER SYSTEM SHALL BE
 DECIDED BY THE CITY OF WPB UTILITIES DEPT.WRITTEN
 APPROVAL SHALL BE REQUIRED FROM UTILITIES FOR FINAL
 PLUMBING APPROVAL. TKL.

Review Stop P PLUMBING
Rev No 2 Status F Date 2015-06-19 Cont ID  
Sent By tklarge Date 2015-06-19 Time 05:28 Rev Time 0.00
Received By tklarge Date 2015-06-19 Time 04:54 Sent To Z
Notes
2015-06-19 05:50:001) SUBMIT DOCUMENTATION THAT THE POOL MAIN DRAIN
 COMPLIES WITHTHE 2010 FBC SEC. 424.1.6.5.10.2. SUBMIT
 MANUF. SPECIFICATION SHEETS FOR THE MAIN DRAIN COVER.
 2ND REQUEST.
 2) THE PLANS SHOW THE POOL WATER DISCHARGE AND THE
 FILTER TANK DRAINS DISCHARGING TO THE "ON-SITE STORM
 WATER DRAINAGE SYSTEM". CLARIFY WHAT IS MEANT BY THE
 "ON-SITE STORM WATER DRAINAGE SYSTEM." POOL WATER SHALL
 NOT DISCHARGE TO THE CITY'S STORM WATER SYSTEM PER CITY
 ORDINANCE SEC. 90-203. 2ND REQUEST
 3) SUBMIT THE MSDS SHETS FOR THE CHLORINE AND THE
 "ACID".WPB AMEND. TO 2010 FBC SEC.107.2.1.2ND REQUEST.
 4) SUBMIT MANUF. SPECIFICATIONS FOR THE CHEMICAL
 FEEDERS. THE FEEDERS SHALL COMPLY W/ANSI/NSF
 50-2007.FBC SEC.424.1.6.5.14. 2ND REQUEST
 5) THE POOL HEATERS SHALL HAVE VALVES PROVIDED WHICH
 ALLOW FOR THE ISOLATION OR THE REMOVAL OF THE HEATER
 FROMTHE SYSTEM. THE CURRENT DESIGN DOES NOT APPEAR TO
 MEET THIS REQUIREMENT. CURRENTLY THERE IS ONE VALVE
 THAT SHUTS DOWN ALL THREE HEATERS AT THE SAME TIME. SEE
 FBC 424.1.6.5.14. 2ND REQUEST.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-05-02 Cont ID  
Sent By tklarge Date 2015-05-02 Time 09:33 Rev Time 0.00
Received By tklarge Date 2015-05-02 Time 07:56 Sent To  
Notes
2015-05-02 09:33:331) THE ENTRY DOORS OF ALL RESTROOMS SHALL BE LOCATED
 WITHIN 200 FEET WALKING DISTANCE OF THE NEAREST WATER'S
 EDGE OF EACH POOL SERVED BY THE FACILITIES. 2010 FBC
 SEC. 424.1.6.
 2) THE WATER FILL FOR THE COLLECTOR TANK SHALL BE
 EQUIPPED WITH A REDUCED PRESSURE BACKFLOW PREVENTER PER
 CITY ORDINANCE AND THE CITY'S CROSS CONNECTION CONTROL
 MANUAL.
 3) SUBMIT MANUFACTURING SPECS FOR THE POOL HEATERS. WPB
 AMEND. TO 2010 FBC SEC. 107.2.1.
 4) PROVIDE CALCULATIONS ON THE PLAN THAT THE MAXIMUM
 FILTRATION RATE THROUGH THE CARTRIDGE FILTERS DOES NOT
 EXCEED 0.075 PER THE 2010 FBC SEC.424.1.6.5.5.1.
 5) THE EQUIPMENT ROOM SHALL HAVE POSITIVE FLOOR
 DRAINAGE PER 2010 FBC SEC.424.1.5.4.
 6) SUBMIT DOCUMENTATION THAT THE GRATING ON THE POOL
 MAIN DRAIN COMPLIES WITH 2010 FBC SEC.424.1.6.5.10.2.
 SUBMIT MANUF. SPECIFICATIONS FOR THE MAIN DRAIN COVER.
 7) THE PLANS SHOW THE POOL WATER DISCHARGING TO THE
 STORM WATER SYSTEM. POOL WATER SHALL NOT DISCHARGE TO
 THE CITY'S STORMWATER SYSTEM PER CITY ORDINANCE
 SEC.90-203.
 8) SUBMIT MSDS DOCUMENTS FOR THE THE CHLORINE AND THE
 "ACID'.WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 9) SUBMIT DETAILS/SPECS FOR THE CHEMICAL FEEDERS. THE
 FEEDERS SHALL COMPLY WITH ANSI/NSF 50 - 2007 PER 2010
 FBC SEC.424.1.6.5.16.
 10) THE POOL HEATERS SHALL HAVE VALVES PROVIDED WHICH
 ALLOW FOR THE ISOLATION OR REMOVAL OF THE HEATER FROM
 THE SYSTEM. THE DESIGN DOES NOT APPEAR TO MEET THIS
 REQUIREMENT. SEE 2010 FBC SEC.424.1.6.5.14.
  
 THIS REVIEW DID NOT INCLUDE THE POOL HOUSE BUILDING FOR
 THE MINIMUM SANITARY FACILITY REQUIREMENTS FOR THE
 RESTROOMS.
  
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2015-06-19 Cont ID  
Sent By eschneid Date 2015-06-19 Time 13:34 Rev Time 0.25
Received By eschneid Date 2015-06-19 Time 13:34 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2015-04-29 Cont ID  
Sent By eschneid Date 2015-04-29 Time 15:24 Rev Time 0.25
Received By eschneid Date 2015-04-29 Time 15:24 Sent To  
Notes
***NONE***