Plan Review Details - Permit 15040645
Plan Review Stops For Permit 15040645
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2015-04-29 Cont ID  
Sent By jwitmer Date 2015-04-29 Time 16:56 Rev Time  
Received By jwitmer Date 2015-04-29 Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-04-21 Cont ID  
Sent By pleduc Date 2015-04-21 Time   Rev Time 0.00
Received By pleduc Date 2015-04-21 Time 13:33 Sent To  
Notes
2015-04-21 13:46:27THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 1) ALL REQUIRED EXITS FROM THE EXISTING FACILITY SHALL
 BE MAINTAINED THROUGHT THE CONSTRUCTION PERIOD.
  
 2) THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  
 3) SHEET G-101 SHOWS INCORRECT REFERENCES TO THE FIRE
 CODE: THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS
 OF THE 5TH EDITION OF FLORIDA FIRE PREVENTION CODE
 INCLUDING THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND
 ALL OTHER APPLICABLE CODES OR STANDARDS.
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2010 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2010 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2009 EDITION.
 FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 10, 2010 EDITION.
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION.
  
 4) SHEET G-101 SHOWS EXIT ACCESS THROUGH CORRIDOR 103
 LEADING TO THE FRONT DOOR. THERE IS NO EXIT SIGN IN
 THAT CORRIDOR. AN EXIT SIGN IS REQUIRED IN CORRIDOR 103
 DIRECTING EGRESS TO THE FRONT DOOR.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date 2015-04-17 Time   Sent To  
Notes
2015-04-18 08:16:05C29

Review Stop M MECHANICAL (A/C)
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***