| Plan Review Stops For Permit 15040620 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2015-07-28 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2015-07-28 |
Time |
07:15 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2015-07-28 |
Time |
06:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2015-06-21 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2015-06-21 |
Time |
09:50 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2015-06-21 |
Time |
09:19 |
Sent To |
|
|
| Notes |
| 2015-06-21 09:35:43 | BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 15040620 | | | ADD: 10130 NORTHLAKE BLVD. # 118 | | | CONT: VN CONSTRUCTION | | | TEL: (407)928-4148 | | | E-MAIL: [email protected] | | | | | | 2010 FLORIDA BUILDING CODE W | | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | I | | | 2ND REVIEW | | | DATE: TUES. JUNE 23/ 2015 | | | ACTION: DENIED | | | | | | 1-7) COMPLIED. | | | | | | 8) SHEET M-1 SHOWS AN EQUIPMENT SHELTERWITH DESIGN | | | CRITERIA OTHER THAN 170 MPH WIND SPEED, EXPOSURE "C". | | | | | | 8A) THE PLANS DO NOT PROVIDE COMPLIANCE WITH: 2010 | | | FBC-B 1809.4 THE MINIMUM DEPTH OF THE FOOTING BELOW THE | | | UNDISTRUBED GROUND SURFACE SHALL BE 12 INCHES. | | | | | | 8B) THE PLANS WILL NEED TO SHOW STUCCO OVER 5/8 INCH | | | PLYWOOD. THE PLANS DO NOT INDICATE THE USE OF WIRE | | | LATH, HOW WILL THE STUCCO BE ATTACHED TO THE PLYWOOD. | | | PLEASE NOTE IF PAPER BACKED WIRE LATH IS USED, A BOND | | | BREAK IN ACCORDANCE WITH THE 2010 FBC-B SECTION | | | 14104.2.1 WILL BE REQUIRED. | | | | | | 8C) THE PLANS DO NOT SHOW COMPLIANCE WITH 2010 FBC-B | | | 1403.7 PROVIDE FOR INSPECTION FOR TERMITE INFESTATION, | | | A CLEARANCE BETWEEN THE STUCCO AND GRADE, A MINIMUM OF | | | 6 INCHES CLEARANCE. | | | | | | 9) THE ROOFING PRODUCT APPROVAL MIAMI-DADE NOA | | | 14-0611.01 WAS SUBMITTED WITH PAGES 7, 8 .9 & 27 OF | | | SUB-SYSTEMS PLEASE IDENTIFY WHICH SUB-SYSTEM WILL BE | | | APPLIED. NOTE IF LIMITATION # 7 OR 9. LIMITATION #7 | | | REQUIRES ENHANCED FASTENING BY A DESIGN PROFESSIONAL. | | | | | | 10) NO PRODUCT APPROVAL WAS SUBMITTED FOR THE EXTERIOR | | | DOOR. 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, | | | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT | | | OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) | | | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT | | | WILL REQUIRE PRODUCT APPROVALS: (31)(A) EXTERIOR DOORS. | | | | | | 11) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE | | | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 | | | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR | | | JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE | | | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING | | | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. | | | | | | 12) THE PLANS DO NOT INDICATE ANY NATURAL VENTILATION, | | | FBC-B 1203.4. | | | | | | 13) WHEN RESUBMITTING PLANS PLEASE INDICATE THE | | | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES | | | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A | | | RESULT OF THE ADDITIONAL INFORMATION REQUESTED | | | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF | | | THIS REVIEW. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2015-04-21 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2015-04-21 |
Time |
08:02 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2015-04-21 |
Time |
07:11 |
Sent To |
|
|
| Notes |
| 2015-04-21 08:02:00 | BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 15040620 | | | ADD: 10130 NORTHLAKE BLVD. # 118 | | | CONT: VN CONSTRUCTION | | | TEL: (407)928-4148 | | | E-MAIL: [email protected] | | | | | | 2010 FLORIDA BUILDING CODE W | | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | IMPORTANT NOTICE: EFFECTIVE MARCH 30, 2015 | | | ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED | | | ELECTRONICALLY | | | UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS | | | SUBMISSION OPTIONS ARE AS FOLLOWS: | | | 1 UPLOAD VIA THE PROJECT DOX PORTAL WITH DIGITAL | | | SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE | | | THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT | | | 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL | | | SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED | | | NAMING CONVENTION FOR EACH DOCUMENT | | | 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER | | | DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE | | | REQUIRED NAMING CONVENTION FOR EACH DOCUMENT | | | 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT | | | TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS | | | ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES | | | AVAILABLE. | | | | | | 1ST REVIEW | | | DATE: TUES. APRIL 21/ 2015 | | | ACTION: DENIED | | | | | | 1) SHEET A-1/ COVER-SHEET OCCUPANCY LOAD BUSINESS, | | | 1,336 SQ, FT. / 100= 14 OCCUPANTS NOT 13 YOU DO NOT | | | ROLL DOWN OR PART OF A OCCUPANT. 2010 FBC-B TABLE | | | 1004.1.1. | | | | | | 2) SHEET A-1/ COVER-SHEET TYPE OF CONSTRUCTION LIST | | | PROTECTED /SPRINKLERED, DOES NOT INDICATE THE TYPE OF | | | CONSTRUCTION, PROTECTED MEANS CONSTRUCTION ELEMENTS ARE | | | (1) HOUR PROTECTED, NOT SPRINKLERED. 2010 FBC-B TABLE | | | 503 & TABLE 601. | | | | | | 3) SHEET A-1 THE RECEPTIONIST ENTRY DOOR IS MISSING THE | | | 18 INCHES ON THE LATCH SIDE OF THE DOOR. 2010 | | | FBC-ACCESSIBILITY CODE 404.2.4 MANEUVERING CLEARANCES. | | | | | | 4) SHEET A-1. THE UNISEX RESTROOM DOES NOT GIVE A | | | FINISHED OR ROUGH DIMENSION AGAINST THE FIXTURE WALL | | | SHOWING COMPLIANCE WITH 2010 FBC-ACCESSIBILITY FIGURE | | | 604.8.1.6, 604.8.1.6 & 604.3.1. | | | | | | 5) SHEET A-1. ROOMS MARKED OFFICE STORAGE AND STORAGE | | | SHOW A 2'-0" WIDE DOOR IN ROOMS APPROXIMATELY 5'-6" | | | DEEP. SEE THE 2010 FBC-ACESS. CODE 404.2.3. OPENINGS | | | MORE THAN 24 INCHES (610 MM) DEEP SHALL PROVIDE A CLEAR | | | OPENING OF 36 INCHES (915 MM) MINIMUM. | | | | | | 6) SHEET A-1. THE (2) STORAGE ROOM DOORS SWING OVER | | | HALF OF THE REQUIRED EXIT ACCESS CORRIDOR WIDTH. 2010 | | | FBC-B 1008.1.9.11 | | | DURING ITS SWING, ANY DOOR IN A MEANS OF EGRESS SHALL | | | LEAVE UNOBSTRUCTED AT LEAST ONE HALF OF THE REQUIRED | | | WIDTH OF AN AISLE, CORRIDOR OR PASSAGEWAY. | | | | | | 7) SHEET A-1 LIFE SAFETY PLAN INDICATES EXISITNG FIRE | | | SPRINKLER LAYOUT, NOTE THERE ARE ROOMS WITHOUT | | | SPRINKLER HEADS IN THE ROOM. 2010 FBC-B 504.2. | | | SPRINKLER INCREASES/ AREA. | | | | | | 8) SHEET M-1 SHOWS AN EQUIPMENT SHELTER BUT THERE IS NO | | | DESIGN CRITERIA OTHER THAN 170 MPH WIND SPEED. PLEASE | | | PROVIDE EXPOSURE CATEGORY ALSO IN THE DESIGN CRITERIA. | | | PRESSURES FOR THE MAIN WIND FORCE RESISTING SYSTEM, & | | | PRESSURES FOR COMPONENTS AND CLADDING. | | | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING | | | CODE, CHAPTER 1, ADMINISTRATION, 107.3.5 MINIMUM PLAN | | | REVIEW CRITERIA FOR BUILDINGS. | | | 107.3.5.1.1 COMMERCIAL BUILDINGS: | | | STRUCTURAL REQUIREMENTS SHALL INCLUDE: | | | DESIGN LOADS | | | WIND REQUIREMENTS | | | BUILDING ENVELOPE | | | FOUNDATION | | | WALL SYSTEMS | | | FLOOR SYSTEMS | | | ROOF SYSTEMS | | | COMPONENTS & CLADDING | | | MATERIALS SHALL BE REVIEWED AND SHALL AT A MINIMUM | | | INCLUDE THE FOLLOWING: | | | WOOD | | | STEEL | | | ALUMINUM | | | CONCRETE | | | PLASTIC | | | GLASS | | | MASONRY | | | GYPSUM BOARD AND PLASTER | | | INSULATING (MECHANICAL) | | | ROOFING | | | INSULATION | | | | | | 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION | | | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A | | | RESULT OF THE ADDITIONAL INFORMATION REQUESTED | | | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF | | | THIS REVIEW. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2015-07-10 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2015-07-10 |
Time |
11:23 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2015-07-10 |
Time |
09:00 |
Sent To |
I |
|
| Notes |
| 2015-07-10 11:27:50 | AFTER FURTHER RESEARCH AND MULTIPLE CONVERSATIONS WITH | | | THE DENTIST, MR. PATEL, WE DETERMINED THAT ORAL SURGERY | | | IS BEYOND THE SCOPE OF HIS LICENSE. THEREFORE AS | | | DESCRIBED IN THE 2005 EDITION NFPA 99, SECTION A 4.4.2, | | | AN ESSENTIAL ELECTRICAL SYSTEM WOULD NOT BE REQUIRED. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2015-07-08 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2015-07-08 |
Time |
11:47 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2015-07-08 |
Time |
10:23 |
Sent To |
I |
|
| Notes |
| 2015-07-08 13:39:29 | WITH THE EXCEPTION TO ELECTRICAL COMMENT # 7 EVERYTHING | | | HAS BEEN ADDRESSED AS REQUIRED. WITH REGARDS TO THE | | | REQUIRED ESSENTIAL ELECTRICAL SYSTEM, YOU HAVE IF I'M | | | NOT MISTAKEN ONLY INCLUDED THE EMERGENCY LIGHT ON THE | | | SYSTEM. THERE'S A BIT MORE TO WHAT COMPRISES AN | | | ESSENTIAL ELECTRICAL SYSTEM. FOR FURTHER INFORMATION ON | | | THAT CONSULT NFPA 70, 2008 EDITION SECTION 517.25 OR | | | NFPA 99, 2005 SECTION 4.4. IF YOU WISH, FEEL FREE TO | | | CONTACT ME DIRECTLY. MIKE ALBARRAN (561) 805-6746 OR | | | [email protected]. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2015-05-28 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2015-05-28 |
Time |
11:04 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2015-05-28 |
Time |
08:31 |
Sent To |
I |
|
| Notes |
| 2015-05-28 10:56:26 | THESE PLANS WERE REVIEWED AND SUBSEQUENTLY DENIED FOR | | | THE FOLLOWING DEFICIENCIES WHICH SHALL BE CORRECTED AS | | | INDICATED: | | | 1. NEC 600.5 - MISSING THE DEDICATED SIGN OUTLET AT | | | EACH PEDESTRIAN ENTRANCE TO THE BUSINESS. | | | 2. NEC 210.62 - MISSING THE REQUIRED SHOW WINDOW | | | OUTLETS. ONE FOR EVERY 12' OF SHOW WINDOW. | | | 3. NEC 210.8 - EVERY OUTLET WITHIN 6' OF THE BASIN | | | SHALL BE GFI PROTECTED. **1 | | | 4. NEC 110.26(D) - PROVIDE ILLUMINATION ABOUT THE | | | ELECTRICAL PANEL. | | | 5. NEC 700.12(F) - EMERGENCY LIGHT SHALL BE ON THE SAME | | | CIRCUIT AS IS THE ROOM THEY OCCUPY. | | | 6. NEC 517.20 - DENTIST'S WORKSTATION SHALL BE | | | CONNECTED TO A GFI CIRCUIT/OUTLET. | | | 7. NEC 517.25 - YOU SHALL HAVE AN ESSENTIAL ELECTRICAL | | | SYSTEM IN OPERATION. **2 | | | 8. REVISE THE ELECTRICAL LIGHTING PLAN TO MATCH THE | | | LEGEND. I TRIED TO REVIEW THE LIGHTING PLAN FOR | | | COMPLIANCE, BUT WHEN ATTEMPTED TO MATCH IT TO THE | | | SUBMITTED LEGEND I WAS NOT ABLE TO. | | | | | | **1 - IF THESE OUTLETS ARE ALREADY DESIGNED ON THE GFI | | | CIRCUIT, PLACE THE CIRCUIT NUMBER ON EACH DEVICE FOR | | | CLARIFICATION. | | | **2 - AN ALTERNATE SOURCE OF POWER FOR EMERGENCY | | | SERVICE IS REQUIRED. PROVIDE A DETAILED RISER DIAGRAM | | | INDICATING THE PRESENCE OF THE ESSENTIAL POWER SOURCE. | | | | | | IF YOU HAVE ANY QUESTION, PLEASE DON'T HESITATE TO | | | CONTACT ME. I CAN BE REACHED VIA EMAIL AT | | | [email protected], OR ON THE PHONE BY CALLING: | | | 561-805-7943 | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2015-06-26 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2015-06-26 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2015-06-26 |
Time |
09:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2015-04-22 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2015-04-22 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2015-04-22 |
Time |
10:05 |
Sent To |
|
|
| Notes |
| 2015-04-22 10:25:40 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) PROVIDE A CONSTRUCTION NOTE INDICATING: | | | THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE | | | 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING | | | THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER | | | APPLICABLE CODES OR STANDARDS. | | | FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS | | | OF NFPA 13, 2010 EDITION. | | | FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF | | | NFPA 72, 2010 EDITION. | | | CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF | | | NFPA 241, 2009 EDITION. | | | FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS | | | OF NFPA 10, 2010 EDITION. | | | ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION. | | | | | | 2) THE SUBMITTED SHEETS WERE NOT STAPLED TOGETHER. | | | SHEET CVR AND ALL SUBSEQUENT SHEETS SHOW "OF 7". THERE | | | ARE ONLY 6 SHEETS. SHEETS SHALL BE FIXED/STAPLED | | | TOGETHER AND SHALL REFLECT ACURATE COUNTING. | | | | | | 3) THE OCCUPANT LOAD IS INCORRECT AND SHALL REFLECT 14. | | | | | | 4) SHEET A-1 NOTES SPRINKLER HEADS IN SOME ROOMS AND | | | NOT IN OTHERS, PLEASE CORRECT. | | | | | | 5) SHEET A-1 SHALL INDICATE A NOTE STATING: | | | THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE | | | SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE | | | CONSTRUCTION PERIOD. | | | ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER | | | SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND | | | BY CERTIFIED LIFE SAFETY CONTRACTORS. | | | ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS, | | | SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE | | | WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL | | | AND COMPLETE PROTECTION IS RETURNED. | | | | | | 6) DOORS OPENING INTO AN EXIT CORRIDOR SHALL COMPLY | | | WITH THE FOLLOWING REQUIREMENTS: | | | | | | | | | NFPA 101 CHAPTER 7, MEANS OF EGRESS | | | 7.2.1.4.3 DOOR LEAF ENCROACHMENT | | | 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS | | | OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE | | | REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY, | | | OR A LANDING UNOBSTRUCTED AND SHALL NOT PROJECT NOT | | | MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A | | | CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN FULLY OPEN, | | | UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE MET: | | | (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN | | | EXISTING BUILDING. | | | (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS | | | PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED | | | WIDTH OF THE STAIR LANDING WHEN THE DOOR LEAF IS FULLY | | | OPEN. | | | | | | THE SUBMITTED PLANS DO NOT MEET THE CONDITIONS. | | | | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2015-07-30 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2015-07-30 |
Time |
12:04 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2015-07-30 |
Time |
12:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2015-07-29 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2015-07-29 |
Time |
16:45 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2015-07-17 |
Time |
14:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2015-07-08 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2015-07-08 |
Time |
13:40 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2015-06-12 |
Time |
14:32 |
Sent To |
|
|
| Notes |
| 2015-07-08 13:48:10 | 7/8/15 - FAILED ELECTRICAL REVIEW. CONTRACTOR NOTIFIED | | | OF FAILED REVIEWS VIA EMAIL. SENT TO LARGE DENIED BIN | | | "V". MA | | 2015-06-12 14:33:09 | RE-SUBMITTAL SENT TO B35 SHELF FOR REVIEW. JG. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2015-05-28 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2015-05-28 |
Time |
11:05 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2015-04-16 |
Time |
16:48 |
Sent To |
|
|
| Notes |
| 2015-05-28 11:06:10 | SENT TO SMALL DENIED BIN "V". MA | | 2015-04-16 16:51:07 | ****EXPEDITED**** | | | B35 | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2015-07-24 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2015-07-24 |
Time |
16:22 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2015-07-24 |
Time |
16:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2015-07-08 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2015-07-08 |
Time |
08:31 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2015-07-08 |
Time |
08:02 |
Sent To |
|
|
| Notes |
| 2015-07-08 09:02:22 | 2ND REVIEW: FBC-10 MECHANICAL | | | | | | 1) THE REVISED PLAN SHOWS AN 8" ROUND MAIN RETURN DUCT | | | AT THE RTU WHICH IS UNDERSIZED FOR A LOW OR MEDIUM | | | PRESSURE SYSTEM RETURNING 1600 CFM'S OF SUPPLY AIR. IS | | | THIS A TYPO? | | | 2) IF THE RTU IS EXISTING PLEASE LABEL IT AS SUCH. | | | 3) PLEASE PLACE A SYMBOL "S" ON THE PLAN TO SHOW THE | | | LOCATION OF THE NEW DUCT SMOKE DETECTOR- SECTION 606.2. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2015-05-27 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2015-05-27 |
Time |
15:56 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2015-05-27 |
Time |
15:55 |
Sent To |
|
|
| Notes |
| 2015-05-27 16:33:56 | 1ST REVIEW: FBC 2010 MECHANICAL | | | | | | 1) M-1: PROVIDE A VENTILATION CALCULATION PER TABLE | | | 403.3 FMC-10. INDICATE ON THE PLAN THE REQUIRED O/A, | | | AND THE ACTUAL O/A BEING PROVIDED BY THE EXISTING RTU. | | | 2) M-1: PROVIDE A TOILET ROOM EXHAUST SYSTEM INCLUDING: | | | A FAN EQUIPMENT SCHEDULE, TYPE AND SIZE OF EXHAUST | | | DUCT, DUCT RUN, AND DUCT TERMINATION LOCATION. | | | 3) M-1: THE METHOD OF RETURN AIR SHOWN ON THE PLAN IS | | | CONFUSING: THERE APPEARS TO BE A MAIN RETURN DUCT | | | RUNNING DOWN THE CORRIDOR, HOWEVER THERE IS A DETAIL ON | | | THE PLAN INDICATING A TRANSFER SYSTEM POSSIBLE FROM THE | | | ROOMS TO THE CORRIDOR. | | | PLEASE NOTE THAT USING THE CORRIDOR AS A MEANS OF | | | RETURN AIR IS NOT PERMITTED PER SECTION 601.2 FMC-10. | | | INDICATE THE TYPE AND SIZE OF ALL RETURN DUCTS ON THE | | | PLAN TO CLARIFY. | | | 4) M-1: PLEASE REVIEW BUILDING PLAN REVIEW COMMENTS | | | REGARDING THE NEW OUTDOOR EQUIPMENT SCREENING | | | STRUCTURE. CLARIFY HOW THE ROOM WILL BE VENTILATED. | | | 5) M-1: TYPICALLY DENTAL VACUUM SYSTEMS ARE EQUIPPED | | | WITH AIR/WATER SEPARATORS THAT REQUIRE DRAINAGE: | | | PROVIDE A MEANS AND SUBMIT MANUFACTURER'S SPECS FOR | | | BOTH THE VACUUM AND THE COMPRESSOR. | | | PLEASE NOTE THAT THE VACUUM MAY REQUIRE AN EXHAUST | | | SYTEM AS WELL: PROVIDE DETAILS. | | | | | | CHRISTOPHER COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2015-07-30 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2015-07-30 |
Time |
11:55 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2015-07-30 |
Time |
11:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2015-07-29 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2015-07-29 |
Time |
16:29 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2015-07-29 |
Time |
16:28 |
Sent To |
|
|
| Notes |
| 2015-07-29 16:42:41 | | | | 7/29/15 REVIEW FAILED | | | | | | | | | 1.RISER DIAGRAM DOES NOT SHOW DRAIN FOR VACUM TANK MUST | | | DRAIN DIRECTLY INTO SANITARY THROUGH TRAP, SIZE TO | | | MANNAFACTURE SPECS. | | | MUST COMPLY WITH NFPA 99 5.3.3.6.3.1 AND FBCP 2010 | | | 713.7 | | | | | | 2. RISER DIAGRAM DOES NOT SHOW PLASTER TRAP PLEASE | | | CLARIFY | | | | | | 3.WATER RISER DIAGRAM IS SIZED INNCORECTLY USE TABLE | | | E201.1 FBCP 2010 | | | | | | 4.EXAUST FROM VACUM SYSTEM MUST DISTARGE ABOVE ROOF | | | FBCP 713.6 | | | | | | | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2015-07-06 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2015-07-06 |
Time |
07:16 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2015-07-06 |
Time |
05:09 |
Sent To |
|
|
| Notes |
| 2015-07-06 06:05:30 | 1) SUBMIT PIPING RISER DIAGRAMS FOR ALL MEDICAL GAS | | | SYSTEMS ( VACUUM & COMPRESSED AIR). THE DESIGN & | | | INSTALLATION SHALL COMPLY WITH NFPA 99C FOR A LEVEL 3 | | | PIPING SYSTEM. 2ND REQUEST. THE SUBMITTED RESPONSE OF | | | "EQUIPMENT INFORMATION PROVIDED" DDOES NOT SATISFY THE | | | PLAN REVIEW COMMENT. | | | 2) INDICATE THE USE OF THE 3/4" DRAIN LINE UNDER THE | | | SLAB. THE MINIMUM SIZE DRAIN SHALL BE 1 1/2" IN | | | ACCORDANCE WITH 2010 FPC TABLE 710.1 (2) OR YOU MAY USE | | | NFPA PPC DRAIN SIZE OPTIONS. CLARIFY. | | | 3) SUBMIT A LEGIBLE DETAIL OF THE EQUIPMENT FLOOR BOX | | | ON SHT. P-1. WPB AMEND. TO 2010 FBC SEC. 107.2.1. | | | 4) COMPRESSED AIR AND VACUUM PIPING SHALL COMPLY W/ | | | NFPA 99 CHAPTS. 5 & 14. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2015-05-13 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2015-05-13 |
Time |
09:33 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2015-05-10 |
Time |
08:25 |
Sent To |
|
|
| Notes |
| 2015-05-10 09:44:46 | 1) 5% OF THE EXAM ROOM SINKS SHALL COMPLY W/2010 FL. | | | ACCESSIBILITY CODE SEC. 212.3 & 606. | | | 2) THE PLANS NOTE THERE IS A TOTAL OF 7 SHEETS. ONLY | | | SIX ARE IN THE SET.CLARIFY. WPB AMEND. TO 2010 FBC SEC. | | | 107.2.1. | | | 3) THE SINKS IN THE BREAK ROOM, LAB & STERILE ROOM | | | SHALL COMPLY W/2010 FL. ACCESSIBILITY CODE SEC. 212.3 & | | | 606. | | | 4) SUBMIT MANUFACTURER'S SPECIFICATIONS AND | | | INSTALLATION INSTRUCTIONS FOR THE DENTAL CHAIRS (2 | | | COPIES). WPB AMEND. TO 2010 FBC SEC. 107.2.1. | | | 5) SHT.A-1 - SHOW THE WIDTH OF THE TOILET ROOM FIXTURE | | | WALL. A MINIMUM WIDTH OF 85 INCHES IS REQUIRED PER 2010 | | | FAC SEC.604.3.1, 604.8.1.6, AND SEC.405.3.1 OF 2010 FL. | | | PLBG. CODE. | | | 6) SUBMIT PIPING DETAILS/MANUF. SPECS FOR UNDER COUNTER | | | WATER FILTRATION SYSTEM. FPC SEC. 611.1. | | | 7) SUBMIT MANUF. SPCIFICATIONS & INSTALLATION MANUALS | | | FOR THE AIR COMPRESSOR AND VACUUM PUMP AND THE FLOOR | | | BOXES FOR THE CHAIRS.. (2 COPIES). WPB AMEND. TO 2010 | | | FBC SEC. 107.2.1. | | | 8) SHT. P-1 -SIZE ALL SECTIONS OF THE HORIZONTAL | | | SANITARY DRAIN LINE. COMPLY W/ CHAPTER 7 OF THE 2010 | | | FL. PLUMBING CODE. | | | 9) SHT. P-1 - THE SANITARY RISER SHOWS 2" DRAINAGE | | | STACKS WITH 3" VENTS. CLARIFY. | | | 10) CLEANOUTS ARE REQD. IN ALL STACKS PER FPC | | | SEC.708.3.4. | | | 11) SHOW THE SIZE & TERMINATION POINT OF THE WATER | | | HEATER PAN DRAIN. COMPLY WITH FPC SEC.504.7.2. | | | 12) THE WATER HEATER PAN SHALL COMPLY WITH 2010 FPC | | | SEC.504.7.1. | | | 13) THE SANITARY RISER DOES NOT CORRELATE WITH THE | | | FLOOR PLAN.WPB AMEND. TO 2010 FBC SEC. 107.2.1. | | | 14) THE DENTAL CHAIRS CANNOT BE INSTALLED AS DRAWN ON | | | THE RISER. | | | 15) SIZE ALL SECTIONS OF THE WATER PIPNG RISER.WPB | | | AMEND. TO 2010 FBC SEC. 107.2.1. | | | 16) SUBMIT RISER DIAGRAMS FOR ALL MEDICAL GAS (VACUUM & | | | COMPRESSED AIR) . THE DESIGN & INSTALLATION SHALL | | | COMPLY WITH NFPA 99C FOR A LEVEL 3 PIPING SYSTEM. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | | | | | | | | | | | | | |
|
|