Plan Review Details - Permit 15040620
Plan Review Stops For Permit 15040620
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-07-28 Cont ID  
Sent By jwitmer Date 2015-07-28 Time 07:15 Rev Time 0.00
Received By jwitmer Date 2015-07-28 Time 06:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-06-21 Cont ID  
Sent By jwitmer Date 2015-06-21 Time 09:50 Rev Time 0.00
Received By jwitmer Date 2015-06-21 Time 09:19 Sent To  
Notes
2015-06-21 09:35:43BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15040620
 ADD: 10130 NORTHLAKE BLVD. # 118
 CONT: VN CONSTRUCTION
 TEL: (407)928-4148
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 I
 2ND REVIEW
 DATE: TUES. JUNE 23/ 2015
 ACTION: DENIED
  
 1-7) COMPLIED.
  
 8) SHEET M-1 SHOWS AN EQUIPMENT SHELTERWITH DESIGN
 CRITERIA OTHER THAN 170 MPH WIND SPEED, EXPOSURE "C".
  
 8A) THE PLANS DO NOT PROVIDE COMPLIANCE WITH: 2010
 FBC-B 1809.4 THE MINIMUM DEPTH OF THE FOOTING BELOW THE
 UNDISTRUBED GROUND SURFACE SHALL BE 12 INCHES.
  
 8B) THE PLANS WILL NEED TO SHOW STUCCO OVER 5/8 INCH
 PLYWOOD. THE PLANS DO NOT INDICATE THE USE OF WIRE
 LATH, HOW WILL THE STUCCO BE ATTACHED TO THE PLYWOOD.
 PLEASE NOTE IF PAPER BACKED WIRE LATH IS USED, A BOND
 BREAK IN ACCORDANCE WITH THE 2010 FBC-B SECTION
 14104.2.1 WILL BE REQUIRED.
  
 8C) THE PLANS DO NOT SHOW COMPLIANCE WITH 2010 FBC-B
 1403.7 PROVIDE FOR INSPECTION FOR TERMITE INFESTATION,
 A CLEARANCE BETWEEN THE STUCCO AND GRADE, A MINIMUM OF
 6 INCHES CLEARANCE.
  
 9) THE ROOFING PRODUCT APPROVAL MIAMI-DADE NOA
 14-0611.01 WAS SUBMITTED WITH PAGES 7, 8 .9 & 27 OF
 SUB-SYSTEMS PLEASE IDENTIFY WHICH SUB-SYSTEM WILL BE
 APPLIED. NOTE IF LIMITATION # 7 OR 9. LIMITATION #7
 REQUIRES ENHANCED FASTENING BY A DESIGN PROFESSIONAL.
  
 10) NO PRODUCT APPROVAL WAS SUBMITTED FOR THE EXTERIOR
 DOOR. 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS: (31)(A) EXTERIOR DOORS.
  
 11) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 12) THE PLANS DO NOT INDICATE ANY NATURAL VENTILATION,
 FBC-B 1203.4.
  
 13) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-04-21 Cont ID  
Sent By jwitmer Date 2015-04-21 Time 08:02 Rev Time 0.00
Received By jwitmer Date 2015-04-21 Time 07:11 Sent To  
Notes
2015-04-21 08:02:00BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15040620
 ADD: 10130 NORTHLAKE BLVD. # 118
 CONT: VN CONSTRUCTION
 TEL: (407)928-4148
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 IMPORTANT NOTICE: EFFECTIVE MARCH 30, 2015
 ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED
 ELECTRONICALLY
 UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS
 SUBMISSION OPTIONS ARE AS FOLLOWS:
 1 UPLOAD VIA THE PROJECT DOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL
 SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED
 NAMING CONVENTION FOR EACH DOCUMENT
 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER
 DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE
 REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT
 TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS
 ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES
 AVAILABLE.
  
 1ST REVIEW
 DATE: TUES. APRIL 21/ 2015
 ACTION: DENIED
  
 1) SHEET A-1/ COVER-SHEET OCCUPANCY LOAD BUSINESS,
 1,336 SQ, FT. / 100= 14 OCCUPANTS NOT 13 YOU DO NOT
 ROLL DOWN OR PART OF A OCCUPANT. 2010 FBC-B TABLE
 1004.1.1.
  
 2) SHEET A-1/ COVER-SHEET TYPE OF CONSTRUCTION LIST
 PROTECTED /SPRINKLERED, DOES NOT INDICATE THE TYPE OF
 CONSTRUCTION, PROTECTED MEANS CONSTRUCTION ELEMENTS ARE
 (1) HOUR PROTECTED, NOT SPRINKLERED. 2010 FBC-B TABLE
 503 & TABLE 601.
  
 3) SHEET A-1 THE RECEPTIONIST ENTRY DOOR IS MISSING THE
 18 INCHES ON THE LATCH SIDE OF THE DOOR. 2010
 FBC-ACCESSIBILITY CODE 404.2.4 MANEUVERING CLEARANCES.
  
 4) SHEET A-1. THE UNISEX RESTROOM DOES NOT GIVE A
 FINISHED OR ROUGH DIMENSION AGAINST THE FIXTURE WALL
 SHOWING COMPLIANCE WITH 2010 FBC-ACCESSIBILITY FIGURE
 604.8.1.6, 604.8.1.6 & 604.3.1.
  
 5) SHEET A-1. ROOMS MARKED OFFICE STORAGE AND STORAGE
 SHOW A 2'-0" WIDE DOOR IN ROOMS APPROXIMATELY 5'-6"
 DEEP. SEE THE 2010 FBC-ACESS. CODE 404.2.3. OPENINGS
 MORE THAN 24 INCHES (610 MM) DEEP SHALL PROVIDE A CLEAR
 OPENING OF 36 INCHES (915 MM) MINIMUM.
  
 6) SHEET A-1. THE (2) STORAGE ROOM DOORS SWING OVER
 HALF OF THE REQUIRED EXIT ACCESS CORRIDOR WIDTH. 2010
 FBC-B 1008.1.9.11
 DURING ITS SWING, ANY DOOR IN A MEANS OF EGRESS SHALL
 LEAVE UNOBSTRUCTED AT LEAST ONE HALF OF THE REQUIRED
 WIDTH OF AN AISLE, CORRIDOR OR PASSAGEWAY.
  
 7) SHEET A-1 LIFE SAFETY PLAN INDICATES EXISITNG FIRE
 SPRINKLER LAYOUT, NOTE THERE ARE ROOMS WITHOUT
 SPRINKLER HEADS IN THE ROOM. 2010 FBC-B 504.2.
 SPRINKLER INCREASES/ AREA.
  
 8) SHEET M-1 SHOWS AN EQUIPMENT SHELTER BUT THERE IS NO
 DESIGN CRITERIA OTHER THAN 170 MPH WIND SPEED. PLEASE
 PROVIDE EXPOSURE CATEGORY ALSO IN THE DESIGN CRITERIA.
 PRESSURES FOR THE MAIN WIND FORCE RESISTING SYSTEM, &
 PRESSURES FOR COMPONENTS AND CLADDING.
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 107.3.5 MINIMUM PLAN
 REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1.1 COMMERCIAL BUILDINGS:
 STRUCTURAL REQUIREMENTS SHALL INCLUDE:
 DESIGN LOADS
 WIND REQUIREMENTS
 BUILDING ENVELOPE
 FOUNDATION
 WALL SYSTEMS
 FLOOR SYSTEMS
 ROOF SYSTEMS
 COMPONENTS & CLADDING
 MATERIALS SHALL BE REVIEWED AND SHALL AT A MINIMUM
 INCLUDE THE FOLLOWING:
 WOOD
 STEEL
 ALUMINUM
 CONCRETE
 PLASTIC
 GLASS
 MASONRY
 GYPSUM BOARD AND PLASTER
 INSULATING (MECHANICAL)
 ROOFING
 INSULATION
  
 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-07-10 Cont ID  
Sent By albarran Date 2015-07-10 Time 11:23 Rev Time 0.00
Received By albarran Date 2015-07-10 Time 09:00 Sent To I
Notes
2015-07-10 11:27:50AFTER FURTHER RESEARCH AND MULTIPLE CONVERSATIONS WITH
 THE DENTIST, MR. PATEL, WE DETERMINED THAT ORAL SURGERY
 IS BEYOND THE SCOPE OF HIS LICENSE. THEREFORE AS
 DESCRIBED IN THE 2005 EDITION NFPA 99, SECTION A 4.4.2,
 AN ESSENTIAL ELECTRICAL SYSTEM WOULD NOT BE REQUIRED.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-07-08 Cont ID  
Sent By albarran Date 2015-07-08 Time 11:47 Rev Time 0.00
Received By albarran Date 2015-07-08 Time 10:23 Sent To I
Notes
2015-07-08 13:39:29WITH THE EXCEPTION TO ELECTRICAL COMMENT # 7 EVERYTHING
 HAS BEEN ADDRESSED AS REQUIRED. WITH REGARDS TO THE
 REQUIRED ESSENTIAL ELECTRICAL SYSTEM, YOU HAVE IF I'M
 NOT MISTAKEN ONLY INCLUDED THE EMERGENCY LIGHT ON THE
 SYSTEM. THERE'S A BIT MORE TO WHAT COMPRISES AN
 ESSENTIAL ELECTRICAL SYSTEM. FOR FURTHER INFORMATION ON
 THAT CONSULT NFPA 70, 2008 EDITION SECTION 517.25 OR
 NFPA 99, 2005 SECTION 4.4. IF YOU WISH, FEEL FREE TO
 CONTACT ME DIRECTLY. MIKE ALBARRAN (561) 805-6746 OR
 [email protected].

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-05-28 Cont ID  
Sent By albarran Date 2015-05-28 Time 11:04 Rev Time 0.00
Received By albarran Date 2015-05-28 Time 08:31 Sent To I
Notes
2015-05-28 10:56:26THESE PLANS WERE REVIEWED AND SUBSEQUENTLY DENIED FOR
 THE FOLLOWING DEFICIENCIES WHICH SHALL BE CORRECTED AS
 INDICATED:
 1. NEC 600.5 - MISSING THE DEDICATED SIGN OUTLET AT
 EACH PEDESTRIAN ENTRANCE TO THE BUSINESS.
 2. NEC 210.62 - MISSING THE REQUIRED SHOW WINDOW
 OUTLETS. ONE FOR EVERY 12' OF SHOW WINDOW.
 3. NEC 210.8 - EVERY OUTLET WITHIN 6' OF THE BASIN
 SHALL BE GFI PROTECTED. **1
 4. NEC 110.26(D) - PROVIDE ILLUMINATION ABOUT THE
 ELECTRICAL PANEL.
 5. NEC 700.12(F) - EMERGENCY LIGHT SHALL BE ON THE SAME
 CIRCUIT AS IS THE ROOM THEY OCCUPY.
 6. NEC 517.20 - DENTIST'S WORKSTATION SHALL BE
 CONNECTED TO A GFI CIRCUIT/OUTLET.
 7. NEC 517.25 - YOU SHALL HAVE AN ESSENTIAL ELECTRICAL
 SYSTEM IN OPERATION. **2
 8. REVISE THE ELECTRICAL LIGHTING PLAN TO MATCH THE
 LEGEND. I TRIED TO REVIEW THE LIGHTING PLAN FOR
 COMPLIANCE, BUT WHEN ATTEMPTED TO MATCH IT TO THE
 SUBMITTED LEGEND I WAS NOT ABLE TO.
  
 **1 - IF THESE OUTLETS ARE ALREADY DESIGNED ON THE GFI
 CIRCUIT, PLACE THE CIRCUIT NUMBER ON EACH DEVICE FOR
 CLARIFICATION.
 **2 - AN ALTERNATE SOURCE OF POWER FOR EMERGENCY
 SERVICE IS REQUIRED. PROVIDE A DETAILED RISER DIAGRAM
 INDICATING THE PRESENCE OF THE ESSENTIAL POWER SOURCE.
  
 IF YOU HAVE ANY QUESTION, PLEASE DON'T HESITATE TO
 CONTACT ME. I CAN BE REACHED VIA EMAIL AT
 [email protected], OR ON THE PHONE BY CALLING:
 561-805-7943
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-06-26 Cont ID  
Sent By pleduc Date 2015-06-26 Time   Rev Time 0.00
Received By pleduc Date 2015-06-26 Time 09:22 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-04-22 Cont ID  
Sent By pleduc Date 2015-04-22 Time   Rev Time 0.00
Received By pleduc Date 2015-04-22 Time 10:05 Sent To  
Notes
2015-04-22 10:25:40THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) PROVIDE A CONSTRUCTION NOTE INDICATING:
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2010 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2010 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2009 EDITION.
 FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 10, 2010 EDITION.
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION.
  
 2) THE SUBMITTED SHEETS WERE NOT STAPLED TOGETHER.
 SHEET CVR AND ALL SUBSEQUENT SHEETS SHOW "OF 7". THERE
 ARE ONLY 6 SHEETS. SHEETS SHALL BE FIXED/STAPLED
 TOGETHER AND SHALL REFLECT ACURATE COUNTING.
  
 3) THE OCCUPANT LOAD IS INCORRECT AND SHALL REFLECT 14.
  
 4) SHEET A-1 NOTES SPRINKLER HEADS IN SOME ROOMS AND
 NOT IN OTHERS, PLEASE CORRECT.
  
 5) SHEET A-1 SHALL INDICATE A NOTE STATING:
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  
 6) DOORS OPENING INTO AN EXIT CORRIDOR SHALL COMPLY
 WITH THE FOLLOWING REQUIREMENTS:
  
  
 NFPA 101 CHAPTER 7, MEANS OF EGRESS
 7.2.1.4.3 DOOR LEAF ENCROACHMENT
 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS
 OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE
 REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY,
 OR A LANDING UNOBSTRUCTED AND SHALL NOT PROJECT NOT
 MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A
 CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN FULLY OPEN,
 UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE MET:
 (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN
 EXISTING BUILDING.
 (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS
 PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED
 WIDTH OF THE STAIR LANDING WHEN THE DOOR LEAF IS FULLY
 OPEN.
  
 THE SUBMITTED PLANS DO NOT MEET THE CONDITIONS.
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2015-07-30 Cont ID  
Sent By tklarge Date 2015-07-30 Time 12:04 Rev Time 0.00
Received By tklarge Date 2015-07-30 Time 12:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-07-29 Cont ID  
Sent By gjohnson Date 2015-07-29 Time 16:45 Rev Time 0.00
Received By gjohnson Date 2015-07-17 Time 14:29 Sent To  
Notes
2015-07-17 14:29:41B17

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-07-08 Cont ID  
Sent By albarran Date 2015-07-08 Time 13:40 Rev Time 0.00
Received By albarran Date 2015-06-12 Time 14:32 Sent To  
Notes
2015-07-08 13:48:107/8/15 - FAILED ELECTRICAL REVIEW. CONTRACTOR NOTIFIED
 OF FAILED REVIEWS VIA EMAIL. SENT TO LARGE DENIED BIN
 "V". MA
2015-06-12 14:33:09RE-SUBMITTAL SENT TO B35 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-05-28 Cont ID  
Sent By albarran Date 2015-05-28 Time 11:05 Rev Time 0.00
Received By albarran Date 2015-04-16 Time 16:48 Sent To  
Notes
2015-05-28 11:06:10SENT TO SMALL DENIED BIN "V". MA
2015-04-16 16:51:07****EXPEDITED****
 B35
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2015-07-24 Cont ID  
Sent By ccole Date 2015-07-24 Time 16:22 Rev Time 0.00
Received By ccole Date 2015-07-24 Time 16:22 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-07-08 Cont ID  
Sent By ccole Date 2015-07-08 Time 08:31 Rev Time 0.00
Received By ccole Date 2015-07-08 Time 08:02 Sent To  
Notes
2015-07-08 09:02:222ND REVIEW: FBC-10 MECHANICAL
  
 1) THE REVISED PLAN SHOWS AN 8" ROUND MAIN RETURN DUCT
 AT THE RTU WHICH IS UNDERSIZED FOR A LOW OR MEDIUM
 PRESSURE SYSTEM RETURNING 1600 CFM'S OF SUPPLY AIR. IS
 THIS A TYPO?
 2) IF THE RTU IS EXISTING PLEASE LABEL IT AS SUCH.
 3) PLEASE PLACE A SYMBOL "S" ON THE PLAN TO SHOW THE
 LOCATION OF THE NEW DUCT SMOKE DETECTOR- SECTION 606.2.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-05-27 Cont ID  
Sent By ccole Date 2015-05-27 Time 15:56 Rev Time 0.00
Received By ccole Date 2015-05-27 Time 15:55 Sent To  
Notes
2015-05-27 16:33:561ST REVIEW: FBC 2010 MECHANICAL
  
 1) M-1: PROVIDE A VENTILATION CALCULATION PER TABLE
 403.3 FMC-10. INDICATE ON THE PLAN THE REQUIRED O/A,
 AND THE ACTUAL O/A BEING PROVIDED BY THE EXISTING RTU.
 2) M-1: PROVIDE A TOILET ROOM EXHAUST SYSTEM INCLUDING:
 A FAN EQUIPMENT SCHEDULE, TYPE AND SIZE OF EXHAUST
 DUCT, DUCT RUN, AND DUCT TERMINATION LOCATION.
 3) M-1: THE METHOD OF RETURN AIR SHOWN ON THE PLAN IS
 CONFUSING: THERE APPEARS TO BE A MAIN RETURN DUCT
 RUNNING DOWN THE CORRIDOR, HOWEVER THERE IS A DETAIL ON
 THE PLAN INDICATING A TRANSFER SYSTEM POSSIBLE FROM THE
 ROOMS TO THE CORRIDOR.
 PLEASE NOTE THAT USING THE CORRIDOR AS A MEANS OF
 RETURN AIR IS NOT PERMITTED PER SECTION 601.2 FMC-10.
 INDICATE THE TYPE AND SIZE OF ALL RETURN DUCTS ON THE
 PLAN TO CLARIFY.
 4) M-1: PLEASE REVIEW BUILDING PLAN REVIEW COMMENTS
 REGARDING THE NEW OUTDOOR EQUIPMENT SCREENING
 STRUCTURE. CLARIFY HOW THE ROOM WILL BE VENTILATED.
 5) M-1: TYPICALLY DENTAL VACUUM SYSTEMS ARE EQUIPPED
 WITH AIR/WATER SEPARATORS THAT REQUIRE DRAINAGE:
 PROVIDE A MEANS AND SUBMIT MANUFACTURER'S SPECS FOR
 BOTH THE VACUUM AND THE COMPRESSOR.
 PLEASE NOTE THAT THE VACUUM MAY REQUIRE AN EXHAUST
 SYTEM AS WELL: PROVIDE DETAILS.
  
 CHRISTOPHER COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2015-07-30 Cont ID  
Sent By tklarge Date 2015-07-30 Time 11:55 Rev Time 0.00
Received By tklarge Date 2015-07-30 Time 11:55 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2015-07-29 Cont ID  
Sent By gjohnson Date 2015-07-29 Time 16:29 Rev Time 0.00
Received By gjohnson Date 2015-07-29 Time 16:28 Sent To  
Notes
2015-07-29 16:42:41 
 7/29/15 REVIEW FAILED
  
  
 1.RISER DIAGRAM DOES NOT SHOW DRAIN FOR VACUM TANK MUST
 DRAIN DIRECTLY INTO SANITARY THROUGH TRAP, SIZE TO
 MANNAFACTURE SPECS.
 MUST COMPLY WITH NFPA 99 5.3.3.6.3.1 AND FBCP 2010
 713.7
  
 2. RISER DIAGRAM DOES NOT SHOW PLASTER TRAP PLEASE
 CLARIFY
  
 3.WATER RISER DIAGRAM IS SIZED INNCORECTLY USE TABLE
 E201.1 FBCP 2010
  
 4.EXAUST FROM VACUM SYSTEM MUST DISTARGE ABOVE ROOF
 FBCP 713.6
  
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2015-07-06 Cont ID  
Sent By tklarge Date 2015-07-06 Time 07:16 Rev Time 0.00
Received By tklarge Date 2015-07-06 Time 05:09 Sent To  
Notes
2015-07-06 06:05:301) SUBMIT PIPING RISER DIAGRAMS FOR ALL MEDICAL GAS
 SYSTEMS ( VACUUM & COMPRESSED AIR). THE DESIGN &
 INSTALLATION SHALL COMPLY WITH NFPA 99C FOR A LEVEL 3
 PIPING SYSTEM. 2ND REQUEST. THE SUBMITTED RESPONSE OF
 "EQUIPMENT INFORMATION PROVIDED" DDOES NOT SATISFY THE
 PLAN REVIEW COMMENT.
 2) INDICATE THE USE OF THE 3/4" DRAIN LINE UNDER THE
 SLAB. THE MINIMUM SIZE DRAIN SHALL BE 1 1/2" IN
 ACCORDANCE WITH 2010 FPC TABLE 710.1 (2) OR YOU MAY USE
 NFPA PPC DRAIN SIZE OPTIONS. CLARIFY.
 3) SUBMIT A LEGIBLE DETAIL OF THE EQUIPMENT FLOOR BOX
 ON SHT. P-1. WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 4) COMPRESSED AIR AND VACUUM PIPING SHALL COMPLY W/
 NFPA 99 CHAPTS. 5 & 14.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-05-13 Cont ID  
Sent By tklarge Date 2015-05-13 Time 09:33 Rev Time 0.00
Received By tklarge Date 2015-05-10 Time 08:25 Sent To  
Notes
2015-05-10 09:44:461) 5% OF THE EXAM ROOM SINKS SHALL COMPLY W/2010 FL.
 ACCESSIBILITY CODE SEC. 212.3 & 606.
 2) THE PLANS NOTE THERE IS A TOTAL OF 7 SHEETS. ONLY
 SIX ARE IN THE SET.CLARIFY. WPB AMEND. TO 2010 FBC SEC.
 107.2.1.
 3) THE SINKS IN THE BREAK ROOM, LAB & STERILE ROOM
 SHALL COMPLY W/2010 FL. ACCESSIBILITY CODE SEC. 212.3 &
 606.
 4) SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS FOR THE DENTAL CHAIRS (2
 COPIES). WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 5) SHT.A-1 - SHOW THE WIDTH OF THE TOILET ROOM FIXTURE
 WALL. A MINIMUM WIDTH OF 85 INCHES IS REQUIRED PER 2010
 FAC SEC.604.3.1, 604.8.1.6, AND SEC.405.3.1 OF 2010 FL.
 PLBG. CODE.
 6) SUBMIT PIPING DETAILS/MANUF. SPECS FOR UNDER COUNTER
 WATER FILTRATION SYSTEM. FPC SEC. 611.1.
 7) SUBMIT MANUF. SPCIFICATIONS & INSTALLATION MANUALS
 FOR THE AIR COMPRESSOR AND VACUUM PUMP AND THE FLOOR
 BOXES FOR THE CHAIRS.. (2 COPIES). WPB AMEND. TO 2010
 FBC SEC. 107.2.1.
 8) SHT. P-1 -SIZE ALL SECTIONS OF THE HORIZONTAL
 SANITARY DRAIN LINE. COMPLY W/ CHAPTER 7 OF THE 2010
 FL. PLUMBING CODE.
 9) SHT. P-1 - THE SANITARY RISER SHOWS 2" DRAINAGE
 STACKS WITH 3" VENTS. CLARIFY.
 10) CLEANOUTS ARE REQD. IN ALL STACKS PER FPC
 SEC.708.3.4.
 11) SHOW THE SIZE & TERMINATION POINT OF THE WATER
 HEATER PAN DRAIN. COMPLY WITH FPC SEC.504.7.2.
 12) THE WATER HEATER PAN SHALL COMPLY WITH 2010 FPC
 SEC.504.7.1.
 13) THE SANITARY RISER DOES NOT CORRELATE WITH THE
 FLOOR PLAN.WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 14) THE DENTAL CHAIRS CANNOT BE INSTALLED AS DRAWN ON
 THE RISER.
 15) SIZE ALL SECTIONS OF THE WATER PIPNG RISER.WPB
 AMEND. TO 2010 FBC SEC. 107.2.1.
 16) SUBMIT RISER DIAGRAMS FOR ALL MEDICAL GAS (VACUUM &
 COMPRESSED AIR) . THE DESIGN & INSTALLATION SHALL
 COMPLY WITH NFPA 99C FOR A LEVEL 3 PIPING SYSTEM.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved