Plan Review Details - Permit 15040570
Plan Review Stops For Permit 15040570
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2016-02-29 Cont ID  
Sent By shill Date 2016-02-29 Time 11:26 Rev Time 0.00
Received By shill Date 2016-02-29 Time 11:26 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2015-10-21 Cont ID  
Sent By shill Date 2015-10-21 Time 18:18 Rev Time 0.00
Received By shill Date 2015-10-21 Time 18:02 Sent To  
Notes
2015-10-21 18:19:56****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. COST BREAKDOWN DOES NOT INCLUDE ANY BACKUP
 DOCUMENTATION. PROVIDE A STICK ESTIMATE COST BREAKDOWN
 (PER SQUARE FOOT) AND A VERIFIABLE COPY OF THE CONTRACT
 FOR THIS JOB, FBC 109. THIS MAY BE SENT VIA EMAIL.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2015-05-13 Cont ID  
Sent By shill Date 2015-05-13 Time 08:27 Rev Time 0.00
Received By shill Date 2015-05-13 Time 08:26 Sent To  
Notes
2015-05-13 08:28:44****CORRECTIONS****
 REVISED 5/13/15
  
 ART LANGE
 BUILDING INSPECTOR
 [email protected]
 561-805-6724
  
 OUTSTANDING COMMENTS FROM PREVIOUS REVIEW:
  
 1-4. OK
  
 5. DOCUMENTS PREPARED BY AN ENGINEER ARE TO INCLUDE A
 TITLE BLOCK, FS471.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-05-12 Cont ID  
Sent By aclange Date 2015-05-12 Time 18:02 Rev Time 0.00
Received By aclange Date 2015-05-12 Time 18:02 Sent To  
Notes
2015-05-12 18:05:08****CORRECTIONS****
  
 ART LANGE
 BUILDING INSPECTOR
 [email protected]
 561-805-6724
  
 OUTSTANDING COMMENTS FROM PREVIOUS REVIEW:
  
 1. REVISE THE FLOOR PLAN TO SHOW ROOM DESIGNATIONS FBC
 107.
  
 2. FOR BEDROOM WINDOWS WHICH ARE LESS THAN 51" IN
 HEIGHT, NOTE EXISTING CONDITIONS (TYPE OF WINDOW) AND
 OPENING SIZE FOR BEDROOMS, FBC R310, FBC EB 604.1. THE
 CLEAR OPENING CANNOT BE REDUCED BY MORE THAN 5%.
  
 TO PROVIDE FURTHER CLARIFICATION REGARDING INFORMATION
 NEEDED FOR BEDROOM WINDOWS WHICH ARE LESS THAN 51" IN
 HEIGHT:
  
 STATE WHAT TYPE OF WINDOW IS THERE NOW IN THE BEDROOMS
 - AWNING, CASEMENT, SINGLE HUNG?
  
 STATE WHAT THE EXISTING CLEAR OPENING DIMENSIONS ARE.
 CLEAR OPENING IS THE OPENING WHICH EXISTS WHEN THE
 WINDOW IS FULLY OPEN.
  
 STATE WHAT THE PROPOSED CLEAR OPENING DIMENSIONS ARE.
 THIS CAN BE OBTAINED FROM THE MANUFACTURER.
  
 3. THE PRODUCT APPROVAL FOR THE DOOR IS ILLEGIBLE AS IT
 WAS PRINTED "PORTRAIT" ORIENTATION RATHER THAN
 "LANDSCAPE". PROVIDE A LEGIBLE PRODUCT APPROVAL.
  
 4. PROVIDE THE FLORIDA STATE PRODUCT APPROVAL COVER
 SHEET FOR THE DOOR. THIS INCLUDES THE APPROVAL NUMBER
 AND STATUS, FAC9N-3.
  
 5. DOCUMENTS PREPARED BY AN ENGINEER ARE TO INCLUDE A
 TITLE BLOCK, FS471.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-05-04 Cont ID  
Sent By shill Date 2015-05-04 Time 17:37 Rev Time 0.00
Received By shill Date 2015-05-04 Time 17:37 Sent To  
Notes
2015-05-04 17:39:34****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. REVISE THE FLOOR PLAN TO SHOW ROOM DESIGNATIONS FBC
 107.
  
 2. FOR BEDROOM WINDOWS WHICH ARE LESS THAN 51" IN
 HEIGHT, NOTE EXISTING CONDITIONS (TYPE OF WINDOW) AND
 OPENING SIZE FOR BEDROOMS, FBC R310, FBC EB 604.1. THE
 CLEAR OPENING CANNOT BE REDUCED BY MORE THAN 5%.
  
 TO PROVIDE FURTHER CLARIFICATION REGARDING INFORMATION
 NEEDED FOR BEDROOM WINDOWS WHICH ARE LESS THAN 51" IN
 HEIGHT:
  
 STATE WHAT TYPE OF WINDOW IS THERE NOW IN THE BEDROOMS
 - AWNING, CASEMENT, SINGLE HUNG?
  
 STATE WHAT THE EXISTING CLEAR OPENING DIMENSIONS ARE.
 CLEAR OPENING IS THE OPENING WHICH EXISTS WHEN THE
 WINDOW IS FULLY OPEN.
  
 STATE WHAT THE PROPOSED CLEAR OPENING DIMENSIONS ARE.
 THIS CAN BE OBTAINED FROM THE MANUFACTURER.
  
 3. THE PRODUCT APPROVAL FOR THE DOOR IS ILLEGIBLE AS IT
 WAS PRINTED "PORTRAIT" ORIENTATION RATHER THAN
 "LANDSCAPE". PROVIDE A LEGIBLE PRODUCT APPROVAL.
  
 4. PROVIDE THE FLORIDA STATE PRODUCT APPROVAL COVER
 SHEET FOR THE DOOR. THIS INCLUDES THE APPROVAL NUMBER
 AND STATUS, FAC9N-3.
  
 5. DOCUMENTS PREPARED BY AN ENGINEER ARE TO INCLUDE A
 TITLE BLOCK, FS471.
  
 6. VALUE IS TOO LOW. THIS IS TO INCLUDE THE MARKET
 VALUE OF LABOR, MATERIALS, OVERHEAD, PROFIT,
 ENGINEERING. PROVIDE A COST BREAKDOWN, FBC 109.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-10-21 Cont ID  
Sent By shill Date 2015-10-21 Time 18:02 Rev Time 0.00
Received By shill Date 2015-10-16 Time 07:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-05-12 Cont ID  
Sent By shill Date 2015-05-12 Time 18:05 Rev Time 0.00
Received By aclange Date 2015-05-06 Time 16:23 Sent To B
Notes
2015-05-06 16:24:00ROUTE TO S.HILL'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-05-04 Cont ID  
Sent By shill Date 2015-05-04 Time 17:40 Rev Time 0.00
Received By shill Date 2015-04-15 Time 13:28 Sent To Z
Notes
***NONE***