Plan Review Details - Permit 15040565
Plan Review Stops For Permit 15040565
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-06-09 Cont ID  
Sent By rlecky Date 2015-06-09 Time 11:20 Rev Time 0.00
Received By rlecky Date 2015-05-21 Time   Sent To  
Notes
2015-05-22 15:10:22SENT TO ELECTRIC

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-04-30 Cont ID  
Sent By rlecky Date 2015-04-30 Time 13:26 Rev Time 0.00
Received By rlecky Date 2015-04-30 Time 12:58 Sent To M
Notes
2015-04-30 13:26:03WIRE SIZES AND PANEL SCHEDUELS FOR "EML2 " AND "EMP2"
 ARE INCORRECT. NEC 215.5
  
 RL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-06-09 Cont ID  
Sent By rlecky Date 2015-06-09 Time 11:20 Rev Time 0.00
Received By rlecky Date 2015-05-21 Time   Sent To  
Notes
2015-05-22 15:17:30SENT TO ELECTRIC

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-05-07 Cont ID  
Sent By hmoser Date 2015-05-07 Time 13:06 Rev Time 0.00
Received By hmoser Date 2015-04-30 Time 13:27 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2015-05-07 Cont ID  
Sent By hmoser Date 2015-05-07 Time 12:53 Rev Time 0.00
Received By hmoser Date 2015-05-07 Time 09:26 Sent To  
Notes
2015-05-07 12:53:01PASS PROVISO
 1) ACCESS DOOR REQUIRED FOR DUCT DETECTOR. PER SECTION
 603.3 INSTALLATION 2010 FBC (M)
 2) PROVIDE A ENGINEER DETAIL SHOWING TYPE AND SIZE
 OF ANCHOR USED FOR CONDENSER TIE DOWN. PER SECTION
 301.12 WIND RESISTANCE 2010 FBC (M)
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676