Plan Review Details - Permit 15040562
Plan Review Stops For Permit 15040562
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-08-24 Cont ID  
Sent By albarran Date 2015-08-24 Time 14:11 Rev Time 0.00
Received By albarran Date 2015-08-24 Time 13:10 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-06-29 Cont ID  
Sent By ccole Date 2015-06-30 Time 10:36 Rev Time 0.00
Received By dhayes Date 2015-06-29 Time 11:59 Sent To  
Notes
2015-06-29 13:33:496/29/2015
 PROJECT: PBC MJC FTR CENTRAL RECORDING ROOM UPGRADES
 PERMIT#: 15040562
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 2ND ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1) PROVIDE PANEL SCHEDULES FOR ALL NEW EQUIPMENT
 INSTALLED. NEC 408.4
  
 2) PROVIDE AN ACTUAL LOAD CALCULATION OR PROVIDE A
 YEARS WORTH OF DOCUMENTED USAGE FROM THE LOCAL UTILITY.
 NEC 220.87
  
 3) PROVIDE LOAD SHEDDING DESIGN THAT INDICATE HOW THE
 LOADS WILL BE DIVERSIFIED AND SEQUENCED TO PROVIDE FULL
 GENERATOR BACK UP TO NEW UPS LOAD.
  
 4) CLARIFY RISER DIAGRAM. THE 250AMP FEEDER FROM SSDP3
 IS 3, 250 KCMIL UNTILL IT REACHES THE 5TH FL AFTER THE
 JUNCTION BOX ABOVE THE NEW UPS IT IS INDICATED THAT IT
 CHANGES TO 600 KCMIL AND ONE #3 GRND. THIS APPREARS TO
 BE A MIS IDENTIFIED FEEDER AND THE 600 KCMIL WAS MEANT
 FOR THE FEEDER TO THE PDU SEC 1 AND SEC 2
  
 5) PROVIDE UL APPROVED CONDUIT PENETRATION FIRE STOP
 DETAILS FOR FLOOR TO FLOOR PENETRATIONS. NEC 300.21
  
 6) CLARIFY CONFLICTS ON THE PLANS AS TO THE SYSTEM
 PHASE AND VOLTAGE FOR THE NEW A/C EQUIPMENT TO BE
 INSTALLED. PAGE E-201 INDICATES THE NEW CU ON THE ROOF
 IS A 480V / 3PHASE 40AMP. PAGE E-301 INDICATES TO
 CHANGE OUT A 3PHASE BREAKER TO A 1PHASE BREAKER. THE
 EQUIPMENT SUBMITTALS CALL FOR 208/230/60/3PH FOR BOTH
 INDOOR AND OUTDOOR EQUIPMENT. PROVIDING ALL PANEL
 SCHEDULES WILL HELP BUT EQUIPMENT SUBMITTALS AND SYSTEM
 VOLTAGE MUST MATCH.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-04-30 Cont ID  
Sent By rlecky Date 2015-04-30 Time 12:36 Rev Time 0.00
Received By rlecky Date 2015-04-30 Time 12:17 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2015-08-24 Cont ID  
Sent By albarran Date 2015-08-24 Time 14:30 Rev Time 0.00
Received By albarran Date 2015-08-21 Time 16:49 Sent To  
Notes
2015-08-24 14:32:398/24/15 - PASSED ELECTRICAL REVIEW. CONTRACTOR NOTIFIED
 VIA EMAIL. SENT TO SMALL "TBD" BIN. MA
2015-08-21 16:49:43CCOLE DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-08-21 Cont ID  
Sent By cpuell Date 2015-08-21 Time 16:48 Rev Time 0.00
Received By cpuell Date 2015-06-12 Time 14:41 Sent To  
Notes
2015-06-15 14:42:28RE-SUBMITTAL SENT TO HAROLD MOSER FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-05-27 Cont ID  
Sent By   Date 2015-05-27 Time   Rev Time 0.00
Received By   Date 2015-05-18 Time   Sent To  
Notes
2015-05-19 09:38:34SENT TO MECHANICAL BOX.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-05-07 Cont ID  
Sent By hmoser Date 2015-05-07 Time 14:25 Rev Time 0.00
Received By hmoser Date 2015-04-30 Time 12:52 Sent To  
Notes
2015-04-30 12:53:064/30 TO MECH BOX
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2015-08-24 Cont ID  
Sent By ccole Date 2015-08-24 Time 10:00 Rev Time 0.00
Received By ccole Date 2015-08-24 Time 10:00 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2015-06-30 Cont ID  
Sent By DAHAYES Date 2015-06-30 Time 10:36 Rev Time 0.00
Received By ccole Date 2015-06-30 Time 10:25 Sent To E
Notes
2015-06-30 10:42:27MECHANICAL PROVISO 6/30/15:
  
 THE NEW DUCTLESS AC SYSTEM IN THE UPS ROOM SHALL BE
 CONNECTED TO THE FIRE ALARM, AND SHALL SHUT DOWN IN
 SEQUENCE WITH THE EXISTING SYSTEM IN THE EVENT OF SMOKE
 OR FIRE DETECTION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  
2015-06-25 11:59:39SENT TO D.HAYES DESK FOR ELECTRICAL REVIEW.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-05-27 Cont ID  
Sent By ccole Date 2015-05-27 Time 09:20 Rev Time 0.00
Received By ccole Date 2015-05-27 Time   Sent To  
Notes
2015-05-27 09:44:241ST REVIEW: FBC 2010 MECHANICAL
  
 1) SHEET M-201: PROVIDE DETAILS AND SEQUENCE OF
 OPERATION FOR SMOKE DETECTION AND FAN SHUT DOWN FOR THE
 NEW AND EXISTING SYSTEMS IN THE UPS ROOM.
 2) M-201: PLEASE CLARIFY HOW RETURN AIR IS FUNCTIONING
 IN THE ROOM: THE PLAN IS INDICATING ONLY SUPPLY AIR
 BEING PROVIDED.
 3) M-101: PROVIDE AC LOAD CALCULATIONS FOR THE NEW
 DUCTLESS SYSTEMS IN COMPLIANCE WITH SECTION 503.2.1
 FBC-10 ENERGY CONSERVATION.
 PLEASE NOTE THE NEW UNITS SIZED AT 15 TONS TOTAL EXCEED
 THE ADDED HEAT REJECTION LOAD OF 11.2 TONS AS SHOWN IN
 THE SCHEDULE: OVERSIZING OF SYSTEMS IS NOT PERMITTED
 PER SECTION 503.2.2 FBC-10 ENERGY CONSERVATION.
 4) PROVIDE A UL TESTED AND APPROVED THROUGH-PENETRATION
 FIRE STOPPING ASSEMBLY ON THE PLAN FOR THE PIPES
 PENETRATING RATED WALLS AND CEILINGS.
  
 CHRISTOPHER COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-05-07 Cont ID  
Sent By hmoser Date 2015-05-07 Time 14:25 Rev Time 0.00
Received By hmoser Date 2015-05-07 Time 13:10 Sent To  
Notes
2015-05-07 14:24:57PLAN DENIED
 1) PROVIDE A DETAIL FROM THE ENGINEER SHOWING THE
 TYPE AND SIZE ANCHOR USED TO TIE DOWN ALL
 EQUIPMENT ON THE ROOF . PER SECTION 301.12
 WIND RESISTANCE. 2010 FBC (M)
 2) SHOW THE FIRE DAMPERS ON EXISTING DUCT
 28X12 AND 24X14 SECTION 607.5.1 FBC (M)
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-05-26 Cont ID  
Sent By tklarge Date 2015-05-26 Time 10:43 Rev Time 0.00
Received By tklarge Date 2015-05-26 Time 10:43 Sent To  
Notes
***NONE***