| 2015-06-29 13:33:49 | 6/29/2015 |
| | PROJECT: PBC MJC FTR CENTRAL RECORDING ROOM UPGRADES |
| | PERMIT#: 15040562 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 2ND ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW |
| | COMMENTS: |
| | |
| | 1) PROVIDE PANEL SCHEDULES FOR ALL NEW EQUIPMENT |
| | INSTALLED. NEC 408.4 |
| | |
| | 2) PROVIDE AN ACTUAL LOAD CALCULATION OR PROVIDE A |
| | YEARS WORTH OF DOCUMENTED USAGE FROM THE LOCAL UTILITY. |
| | NEC 220.87 |
| | |
| | 3) PROVIDE LOAD SHEDDING DESIGN THAT INDICATE HOW THE |
| | LOADS WILL BE DIVERSIFIED AND SEQUENCED TO PROVIDE FULL |
| | GENERATOR BACK UP TO NEW UPS LOAD. |
| | |
| | 4) CLARIFY RISER DIAGRAM. THE 250AMP FEEDER FROM SSDP3 |
| | IS 3, 250 KCMIL UNTILL IT REACHES THE 5TH FL AFTER THE |
| | JUNCTION BOX ABOVE THE NEW UPS IT IS INDICATED THAT IT |
| | CHANGES TO 600 KCMIL AND ONE #3 GRND. THIS APPREARS TO |
| | BE A MIS IDENTIFIED FEEDER AND THE 600 KCMIL WAS MEANT |
| | FOR THE FEEDER TO THE PDU SEC 1 AND SEC 2 |
| | |
| | 5) PROVIDE UL APPROVED CONDUIT PENETRATION FIRE STOP |
| | DETAILS FOR FLOOR TO FLOOR PENETRATIONS. NEC 300.21 |
| | |
| | 6) CLARIFY CONFLICTS ON THE PLANS AS TO THE SYSTEM |
| | PHASE AND VOLTAGE FOR THE NEW A/C EQUIPMENT TO BE |
| | INSTALLED. PAGE E-201 INDICATES THE NEW CU ON THE ROOF |
| | IS A 480V / 3PHASE 40AMP. PAGE E-301 INDICATES TO |
| | CHANGE OUT A 3PHASE BREAKER TO A 1PHASE BREAKER. THE |
| | EQUIPMENT SUBMITTALS CALL FOR 208/230/60/3PH FOR BOTH |
| | INDOOR AND OUTDOOR EQUIPMENT. PROVIDING ALL PANEL |
| | SCHEDULES WILL HELP BUT EQUIPMENT SUBMITTALS AND SYSTEM |
| | VOLTAGE MUST MATCH. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |