Plan Review Details - Permit 15040554
Plan Review Stops For Permit 15040554
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2016-03-14 Cont ID  
Sent By jwitmer Date 2016-03-14 Time 06:31 Rev Time 0.00
Received By jwitmer Date 2016-03-14 Time 06:02 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-02-04 Cont ID  
Sent By jwitmer Date 2016-02-04 Time   Rev Time 0.00
Received By jwitmer Date 2016-02-04 Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-10-30 Cont ID  
Sent By jwitmer Date 2015-10-30 Time   Rev Time 0.00
Received By jwitmer Date 2015-10-30 Time 08:15 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-04-25 Cont ID  
Sent By jwitmer Date 2015-04-25 Time 11:59 Rev Time  
Received By jwitmer Date 2015-04-25 Time 11:30 Sent To  
Notes
2015-04-25 11:48:57BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15040554
 ADD: 460 S. ROSEMARY AVE. SUITE # 1801
 CONT: TBD
 TEL: (954)914-9848/ TABITHA
 E-MAIL: TABITHA. [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SAT. APRIL 25/ 2015
 ACTION: DENIED
  
 1) PLANS APPEAR TO BE CODE COMPLIANT BUT THE PLANS ARE
 NOT STAMPED BY CITY PLACE MANAGEMENT REVIEWED AND
 APPROVED.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-02-16 Cont ID  
Sent By rlecky Date 2016-02-16 Time 14:37 Rev Time 0.00
Received By rlecky Date 2016-02-16 Time 14:26 Sent To  
Notes
2016-02-16 14:38:09REVIEW DONE BY M. VALDES

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-03-07 Cont ID  
Sent By rlecky Date 2015-11-23 Time 12:53 Rev Time 0.00
Received By rlecky Date 2015-11-23 Time 16:08 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-05-18 Cont ID  
Sent By dhayes Date 2015-05-18 Time 13:33 Rev Time 0.00
Received By dhayes Date 2015-05-18 Time 12:44 Sent To  
Notes
2015-05-18 14:02:375/18/2015
 PROJECT: NAIL SALON
 PERMIT#: 15040554
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1) REVISE THE LIGHTING PLAN AND THE PANEL SCHEDULE TO
 INCLUDE THE EMERGENCY/EXIT LIGHT CIRCUIT IS THE SAME
 BRANCH CIRCUIT AS THAT SERVING THE NORMAL LIGHTING IN
 THE AREA AND CONNECTED AHEAD OF ANY LOCAL SWITCHES. NEC
 700.12.
  
 2) REVISE THE FLOOR PLAN AND THE PANEL SCHEDULE FOR THE
 WATER HEATER CIRCUIT. IT APPEARS TO BE A TYPO BUT THE
 CIRCUIT IS IDENTIFIED AS A 3POLE CIRCUIT BUT HAS ONE
 POLE IDENTIFIED AS 50AMP AND THE OTHER TWO AS 30AMP.
 PLEASE CLARIFY.
  
 3) INDICATE OR VERIFY THE REQUIRED GFI RECEPTACLE ON
 THE ROOF WITHIN SIGHT OF THE MECHANICAL EQUIPMENT. NEC
 210.63 SEE 210.8(A)(3),
  
 4) PROVIDE SUBMITTALS ON EQUIPMENT SUCH AS PEDICURE
 CHAIRS, NAIL DRYERS,
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2016-03-09 Cont ID  
Sent By pleduc Date 2016-03-09 Time   Rev Time 0.00
Received By pleduc Date 2016-03-09 Time 10:59 Sent To  
Notes
2016-03-09 11:55:22THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 1. SHEET A 2.00 & 2.01 INDICATES A DOOR SWING THAT
 SWINGS AGAINST THE PATH OF EGRESS.
 PER SECTION NFPA 101, DOOR SWING DIRECTION, 7.2.1.4.2,
 DOOR IS REQUIRED TO SWING IN THE DIRECTION OF EGRESS
 TRAVEL FOR AN OCCUPANT LOAD OF 50 OR GREATER PERSONS.
 THE LIFE SAFETY PLANS SHOWS THE REQUIRED PATH OF TRAVEL
 THROUGH THAT DOOR.
  
 2. SHEET A 2.01 INDICATES THE SINGLE MAN DOOR AS BRING
 LOCKED AND HANDLES REMOVED. THIS IS A REQUIRED EXIT AND
 PER SHEET A 2.00 IS INDICATED AS "EXIT B". ENSURE THIS
 DOOR IS FULLY OPERATION AND FUNCTIONING AS A REQUIRED
 EXIT DOOR.
  
 3. SHEET E2 INDICATES NO EXIT SIGNS OVER REQUIRED EXT
 DOORS # 2 AND EXIT B. INSTALL EXIT SIGNS OVER THESE
 REQUIRED EXIT DOORS.
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-10-28 Cont ID  
Sent By pleduc Date 2015-10-28 Time   Rev Time 0.00
Received By pleduc Date 2015-10-28 Time 10:26 Sent To  
Notes
2015-10-28 11:03:49THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 1. SHEET A 2.00 & 2.01 INDICATES A DOOR SWING THAT
 SWINGS AGAINST THE PATH OF EGRESS.
 PER SECTION NFPA 101, DOOR SWING DIRECTION, 7.2.1.4.2,
 DOOR IS REQUIRED TO SWING IN THE DIRECTION OF EGRESS
 TRAVEL FOR AN OCCUPANT LOAD OF 50 OR GREATER PERSONS.
 THE LIFE SAFETY PLANS SHOWS THE REQUIRED PATH OF TRAVEL
 THROUGH THAT DOOR.
  
 2. SHEET A 2.01 INDICATES THE SINGLE MAN DOOR AS BRING
 LOCKED AND HANDLES REMOVED. THIS IS A REQUIRED EXIT AND
 PER SHEET A 2.00 IS INDICATED AS "EXIT B". ENSURE THIS
 DOOR IS FULLY OPERATION AND FUNCTIONING AS A REQUIRED
 EXIT DOOR.
  
 3. SHEET E2 INDICATES NO EXIT SIGNS OVER REQUIRED EXT
 DOORS # 2 AND EXIT B. INSTALL EXIT SIGNS OVER THESE
 REQUIRED EXIT DOORS.
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-04-17 Cont ID  
Sent By pleduc Date 2015-04-17 Time   Rev Time 0.00
Received By pleduc Date 2015-04-16 Time 16:48 Sent To  
Notes
2015-04-17 10:55:03THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET A2.00 INDICATES AN EXIT EGRESS LAYOUT THAT IS
 NOT APPROVED. THESE EXITS ARE NOT REMOTELY LOCATED. THE
 SEPARATION DISTANCE DOES NOT MEET THE REQUIREMENTS OF
 NFPA 101, CHAPTER 7, 7.5.1.3.3. THE SEPARATION DISTANCE
 SHALL BE 1/3 OF THE DIAGONAL MEASURED IN A STRAIGHT
 LINE BETWEEN THE NEAREST EDGE OF THE EXITS, EXIT
 ACCESS, OR EXIT DISCHAGES. AN ADDITIONAL EXIT IS
 REQUIRED THAT IS REMOTELY LOCATED AND MEETING THE
 DISTANCE REQUIRMENT.
  
 2) SHEET A0.01 INDICATES AN INCORRECT FIRE CODE
 REFERENCE. THE PROPOSED PROJECT SHALL MEET THE
 REQUIREMENTS OF THE 5TH EDITION OF FLORIDA FIRE
 PREVENTION CODE INCLUDING THE 2012 EDITION OF NFPA 1
 AND NFPA 101 AND ALL OTHER APPLICABLE CODES OR
 STANDARDS.
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2010 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2010 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2009 EDITION.
 FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 10, 2010 EDITION.
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION.
  
 3) SHEET A2.00 THE NATURE OF THE REMODEL REQUIRES AN
 EVALUATION OF THE FIRE ALARM AND SPRINKLER SYSTEM FOR
 CODE COVERAGE AND COMPLIANCE.
 PROVIDE A NOTE STATING: THE LIFE SAFETY SYSTEMS, FIRE
 ALARM AND/OR FIRE SPRINKLER SHALL REMAIN ACTIVE
 THROUGHOUT THE CONSTRUCTION PERIOD.
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-03-23 Cont ID  
Sent By gjohnson Date 2016-03-23 Time 13:51 Rev Time 0.00
Received By gjohnson Date 2016-03-04 Time 14:02 Sent To  
Notes
2016-03-04 14:03:23B33

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-02-16 Cont ID  
Sent By rlecky Date 2016-02-16 Time 14:39 Rev Time 0.00
Received By rlecky Date 2016-01-26 Time 10:33 Sent To  
Notes
2016-01-27 10:34:08B33

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-11-24 Cont ID  
Sent By cpuell Date 2015-11-24 Time 14:02 Rev Time 0.00
Received By cpuell Date 2015-10-16 Time 07:29 Sent To  
Notes
2015-10-19 07:31:42B29

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-10-20 Cont ID  
Sent By skennedy Date 2015-06-01 Time 16:43 Rev Time 0.00
Received By skennedy Date 2015-04-15 Time 16:56 Sent To  
Notes
2015-04-15 16:57:02B34

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2016-03-11 Cont ID  
Sent By ccole Date 2016-03-11 Time 07:43 Rev Time 0.00
Received By ccole Date 2016-03-10 Time 17:46 Sent To  
Notes
2016-03-11 07:48:51MECHANICAL PROVISIOS:
 PERMIT #15040554
 3/11/16
  
 1) UNDERSLAB PVC EXHAUST DUCTS SHALL BE INSPECTED PRIOR
 TO CLOSING SLAB TRENCHES.
 2) PROVIDE A SUBMITTAL FOR THE PVC DUCTS REVIEWED AND
 APPROVED BY THE ENGINEER OF RECORD.
 3) PROVIDE A TEST AND BALANCE REPORT FOR THE SYSTEMS,
 AND PERFORM AN EXHAUST SYSTEM TEST AT FINAL INSPECTION.
 4) SUBMIT A REVISED ENERGY EFFICIENCY COMPLIANCE FORM
 IN INK (CURRENT SUBMITTAL IS IN PENCIL).
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2016-02-08 Cont ID  
Sent By ccole Date 2016-02-08 Time 09:37 Rev Time 0.00
Received By ccole Date 2016-02-08 Time 09:37 Sent To  
Notes
2016-02-08 10:19:423RD REVIEW: FBC 2014 MECHANICAL
 PERMIT #15040554
 2/8/16
  
 1) THE PEDICURE AREA EXHAUST SYSTEM DESIGN DOES NOT
 APPEAR TO BE A "SOURCE CAPTURE SYSTEM" AS REQUIRED BY
 FOOTNOTE H. TABLE 403.3. THE PLAN IS INDICATING EXHAUST
 GRILLS AT THE CEILING LEVEL, HOWEVER THE SOURCE OF THE
 FUMES AND ODORS ARE AT FLOOR LEVEL.
 2) PROVIDE ENLARGED DETAILS OF THE UNDERSLAB DUCT.
 REFER TO SECTION 603.8 AND INDICATE THE TYPE AND GAGE
 OF DUCT MATERIAL, HOW IT WILL BE PROTECTED AND SEALED,
 THE MINIMUM SLOPE AND ACCESS TO THE DRAINAGE POINT.
 PROVIDE A SUBMITTAL REVIEWED AND APPROVED BY THE EOR.
 3) PROVIDE ENLARGED DETAILS OF THE EXHAUST RISERS AT
 THE MANICURE TABLES- SHOW THE TYPE AND GAGE OF DUCT
 MATERIAL, HOW CONNECTIONS TO THE UNDERSLAB DUCT AND
 TABLE TOP WILL BE MADE.
 4) PLEASE PROVIDE NOTE TO CLARIFY THE SEQUENCE OF
 OPERATION FOR THE NAIL EXHAUST SYSTEMS. ARE THESE
 SYSTEMS DESIGNED TO RUN CONTINUOUSLY? ARE THE EXHAUST
 FANS LINKED WITH THE AC SYSTEMS WHICH ARE PROVIDING THE
 MAKE-UP AIR FOR THE SYSTEMS?
 5) THE AC COOLING AND HEATING CALCULATIONS ARE
 INDICATING APPROXIMARELY 10-TONS OF COOLING FOR THE
 NAIL AREA AND THE FRONT RETAIL, BREAKROOM, TOILET ROOMS
 AND AREAS ETC, HOWEVER THE TWO SYSTEMS SELECTED PROVIDE
 A TOTAL OF 11.5- TONS OF COOLING FOR THOSE AREAS.
 SENSIBLE COOLING LOAD INDICATED IN THE CALCS IS 62239
 BTUH, HOWEVER TOTAL SENSIBLE LOAD OF THE UNITS COMBINED
 IS APPROX. 83,000 BTUH- SEE SECTION 503.2.2 FBC-10
 ENERGY CONSERVATION.
 6) PLEASE CORRECT THE NOTE INDICATING FIRE DAMPERS FOR
 THE DRYER EXHAUST DUCTS- THEY ARE PROHIBITED PER
 SECTION 504.2 FBC-10 MECHANICAL.
 7) PROVIDE THE MIAMI-DADE NOA'S OR FLORIDA PRODUCT
 APPROVALS FOR EF-2, EF-3, AND THE AIR INTAKE LOUVERS.
 VERFIY ALL REQUIRED CLEARANCES AS REQUIRED BY 401.4,
 AND 501.2.1.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-10-29 Cont ID  
Sent By ccole Date 2015-10-29 Time 12:48 Rev Time 0.00
Received By ccole Date 2015-10-29 Time 12:48 Sent To  
Notes
2015-10-29 13:01:232ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #15040554
 10/29/15
  
 1) COMMENTS #2, 3, & 4 FROM THE 1ST REVIEW STILL EXIST.
 I AM REPRINTING THEM BELOW FOR RE-REVIEW:
  
 2) M2: GENERAL NOTE #12 INDICATES THAT CO2 SENSORS WILL
 MONITOR THE QUALITY OF AIR IN THE SPACE, HOWEVER NO
 SENSORS ARE SHOWN ON THE PLANS.
 PLEASE CLARIFY HOW THIS SYSTEM DESIGN IS MEETING THE
 INTENT OF TABLE 403.3 FMC-10, AND TABLE 6-4 ASHRAE 62.1
 WHICH REQUIRES CAPTURING THE CHEMICAL FUMES AT THEIR
 SOURCES AND EXHAUSTING THEM FROM THE SPACE (SEE
 FOOTNOTE H PRINTED BELOW).
 THE DESIGN DOES NOT INDICATE ANY EXHAUST HOODS OR DUCTS
 AT THE STATIONS. IN ADDITION, PLEASE CLARIFY IF THE CO2
 SENSORS WILL ACTIVATE THE SYSTEM UPON DETECTION OF
 CHEMICAL FUMES.
 3) PROVIDE TWO COPIES OF MIAMI-DADE NOA'S OR FL.
 PRODUCT APPROVALS FOR THE AC STAND, AND THE INTAKE AND
 EXHAUST LOUVERS.
 4) PROVIDE MANUFACTURER'S SPECIFICATIONS (CUT SHEET)
 FOR THE EXHAUST FAN.
  
 5) THE REVISED PLAN INDICATES A TRANSFER DUCT FROM THE
 NAIL AREA TO THE RETAIL AREA. PLEASE REFER TO TABLE
 403.3 FOOTNOTE B AND H, AND REVISE THE PLAN TO MEET
 COMPLIANCE.
 B. MECHANICAL EXHAUST REQUIRED AND THE RECIRCULATION OF
 AIR FROM SUCH SPACES IS PROHIBITED (SEE SECTION
 403.2.1, ITEM 3).
 H. FOR NAIL SALONS, EACH NAIL STATION SHALL BE PROVIDED
 WITH A SOURCE CAPTURE SYSTEM CAPABLE OF EXHAUSTING NOT
 LESS THAN 50 CFM PER STATION.
  
 PLEASE CORRECT THE PLANS IN ACCORDANCE WITH THE
 COMMENTS LISTED ABOVE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-05-29 Cont ID  
Sent By ccole Date 2015-05-29 Time 16:57 Rev Time 0.00
Received By ccole Date 2015-05-29 Time 16:57 Sent To  
Notes
2015-05-29 17:23:001ST REVIEW: FBC 2010 MECHANICAL
  
 1) SHEET M1: PER NOTES 6 & 7 ON THE PLAN, SHOW THE
 MOTORIZED DAMPER FOR EF2.
 2) M2: GENERAL NOTE #12 INDICATES THAT CO2 SENSORS WILL
 MONITOR THE QUALITY OF AIR IN THE SPACE, HOWEVER NO
 SENSORS ARE SHOWN ON THE PLANS.
 PLEASE CLARIFY HOW THIS SYSTEM DESIGN IS MEETING THE
 INTENT OF TABLE 403.3 FMC-10, AND TABLE 6-4 ASHRAE 62.1
 WHICH REQUIRES CAPTURING THE CHEMICAL FUMES AT THEIR
 SOURCES AND EXHAUSTING THEM FROM THE SPACE.
 THE DESIGN DOES NOT INDICATE ANY EXHAUST HOODS OR DUCTS
 AT THE STATIONS. IN ADDITION, PLEASE CLARIFY IF THE CO2
 SENSORS WILL ACTIVATE THE SYSTEM UPON DETECTION OF
 CHEMICAL FUMES.
 3) PROVIDE TWO COPIES OF MIAMI-DADE NOA'S OR FL.
 PRODUCT APPROVALS FOR THE AC STAND, AND THE INTAKE AND
 EXHAUST LOUVERS.
 4) PROVIDE MANUFACTURER'S SPECIFICATIONS (CUT SHEET)
 FOR THE EXHAUST FAN.
  
 CHRISTOPHER COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2016-03-23 Cont ID  
Sent By gjohnson Date 2016-03-23 Time 13:50 Rev Time 0.00
Received By gjohnson Date 2016-03-23 Time 13:50 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2016-01-30 Cont ID  
Sent By tklarge Date 2016-01-30 Time 10:12 Rev Time 0.00
Received By tklarge Date 2016-01-30 Time 09:23 Sent To  
Notes
2016-01-30 09:48:201) ONE OF THE WASHING MACHINES & DRYERS SHALL COMPLY
 WITH 2010 FBC-ACCESSIBILITY,SEC.611.2, 611.3,611.4.
 SHOW ON THE PLANS.3RD REQUEST
 2) SHT. A8.01 - "A" ELEVATION - THE GRAB BARS SHALL BE
 MEASURED TO THE TOP OF THE GRIPPING SURFACE.FBC-
 ACCESSIBILITY, SEC. 609.4. REFER TO ACCESSORY MOUNTING
 SCHEDULE ALSO.3RD REQUEST.
 3) DISPENSERS SHALL BE MEASURED TO THE CENTERLINE OF
 THE DISPENSER, NOT TO THE EDGE AS SHOWN PER FAC
 SEC.604.7.3RD REQUEST.
 4) BREAKROOM SINK SHALL COMPLY W/ 2010 FAC SEC.606.3.
 3RD REQUEST.
 5) FOUR TIMES THE PLAN REVIEW FEE SHALL BE IMPOSED ON
 THE NEXT PLAN REVIEW SUBMITTAL PER F.S. 553.80 (2) (B).
 THE ABOVE COMMENTS HAVE NOT BEEN CORRECTED IN THREE
 REVIEWS.
  
 NOTE: CONTACT ME TO REVIEW THE COMMENTS SO THE PLANS
 CAN GET CORRECTED AND APPROVED.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2015-10-26 Cont ID  
Sent By gjohnson Date 2015-10-26 Time 16:01 Rev Time 0.00
Received By gjohnson Date 2015-10-26 Time 16:01 Sent To  
Notes
2015-10-26 16:13:57 
 1ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS: 2ND REQUEST
  
 1. SHOW ON PLANS ONE OF THE WASHIN MACHINES & DRYERS
 SHALL COMPLY WITH 2010 FBC-ACCESSIBILITY,SEC.61 1.2,
 611.3,611.4.
 2. SHT. A8. 0L - ''A" ELEVATION - THE GRAB BARS SHALL
 BE MEASURED TO THE TOP OF THE GRIPPING SURFACE.FBC?
 ACCESSIBILITY, SEC. 609.4. REFER TO ACCESSORY MOUNTING
 SCHEDULE ALSO.
 3. SHOW ON PLANS DISPENSERS SHALL BE MEASURED TO THE
 CENTERLINE OF THE DISPENSER, NOT TO THE EDGE AS SHOWN
 PER FAC SEC.604.7.
 4. SHOW ON PLANS BREAKROOM SINK SHALL COMPLY W/ 2010
 FAC SEC.606.3.
 5. SUBMIT MANUFACTURER'S SPECIFICATIONS/INSTALLATION
 MANUAL (2 COPIES) FOR THE PEDICURE CHAIRS. WPB AMEND.
 TO 2010 FBC SEC. 107.2.1.
 6. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE LINT
 TRAP . WPB AMEND. TO 2010 FBC SEC. 107.2.1 .
 7. SHT. P-5 - SHOWS THE P & T LINE TO THE EXTERIOR. THE
 P & T LINE SHALL DISCHARGE TO AN AIR GAP LOCATED IN THE
 SAME ROOM AS THE WATER HEATER.2010 FPC SEC.504.6 (2).
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-05-18 Cont ID  
Sent By tklarge Date 2015-05-18 Time 08:23 Rev Time 0.00
Received By tklarge Date 2015-05-18 Time 05:32 Sent To  
Notes
2015-05-18 08:17:151) SHT. A 2.01 - CLEARLY SHOW THE WIDTH OF THE TOILET
 ROOMS. A MINIMUM OF 85 INCHES IS REQUIRED. 2010
 FBC-ACCESSIBILITY, SEC.604.3.1, 606.2.
 2) ONE OF THE WASHING MACHINES & DRYERS SHALL COMPLY
 WITH 2010 FBC-ACCESSIBILITY,SEC.611.2, 611.3,611.4.
 3) SHT. A8.01 - "A" ELEVATION - THE GRAB BARS SHALL BE
 MEASURED TO THE TOP OF THE GRIPPING SURFACE.FBC-
 ACCESSIBILITY, SEC. 609.4. REFER TO ACCESSORY MOUNTING
 SCHEDULE ALSO.
 4) DISPENSERS SHALL BE MEASURED TO THE CENTERLINE OF
 THE DISPENSER, NOT TO THE EDGE AS SHOWN PER FAC
 SEC.604.7.
 5) BREAKROOM SINK SHALL COMPLY W/ 2010 FAC SEC.606.3.
 6) SUBMIT MANUFACTURER'S SPECIFICATIONS/INSTALLATION
 MANUAL (2 COPIES) FOR THE PEDICURE CHAIRS. WPB AMEND.
 TO 2010 FBC SEC. 107.2.1.
 7) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE LINT
 TRAP. WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 8) SHT. P-5 - SHOWS THE P & T LINE TO THE EXTERIOR. THE
 P & T LINE SHALL DISCHARGE TO AN AIR GAP LOCATED IN THE
 SAME ROOM AS THE WATER HEATER.2010 FPC SEC.504.6 (2).
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop Z ZONING
Rev No 3 Status P Date 2016-03-18 Cont ID  
Sent By aaponte Date 2016-03-18 Time 16:15 Rev Time 0.00
Received By aaponte Date 2016-03-18 Time 16:15 Sent To  
Notes
2016-03-18 16:16:57PROVISO: RETAIL USES SHALL BE MAINTAINED ALONG AT LEAST
 26 FEET OF FRONTAGE AS DEPICTED ON DRAWINGS.
 THE CALCULATION FOR RETAIL USES WAS DONE BASED ON THE
 ENTIRE BUILDING FROM FERN TO GARDENIA WITH A TOTAL
 FRONTAGE OF 281 FEET. NON RETAIL PERMITTED ARE THE
 RESIDENTIAL ENTRANCE AND THE VENETIAN SALON (20% OF
 FRONTAGE)

Review Stop Z ZONING
Rev No 2 Status P Date 2015-11-20 Cont ID  
Sent By aaponte Date 2015-11-20 Time 15:55 Rev Time 0.00
Received By aaponte Date 2015-11-20 Time 15:55 Sent To  
Notes
2015-11-20 15:58:33PROVISO: RETAIL USES SHALL BE MAINTAINED ALONG AT LEAST
 26 FEET OF FRONTAGE AS DEPICTED ON DRAWINGS.
 THE CALCULATION FOR RETAIL USES WAS DONE BASED ON THE
 ENTIRE BUILDING FROM FERN TO GARDENIA WITH A TOTAL
 FRONTAGE OF 281 FEET. NON RETAIL PERMITTED ARE THE
 RESIDENTIAL ENTRANCE AND THE VENETIAN SALON (20% OF
 FRONTAGE)

Review Stop Z ZONING
Rev No 1 Status F Date 2015-05-21 Cont ID  
Sent By aaponte Date 2015-05-21 Time 16:09 Rev Time 0.00
Received By aaponte Date 2015-05-21 Time 16:09 Sent To  
Notes
2015-05-21 16:15:46THE USE AS PRESENTED IS NOT ALLOWED AT THIS LOCATION.
 ROSEMARY AVENUE REQUIRES RETAIL USES ALONG 80% OF ITS
 FRONTAGE. A NAIL SALON IS CONSIDERED A PERSONAL SERVICE
 AND NOT A RETAIL USE.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.