Plan Review Details - Permit 15040501
Plan Review Stops For Permit 15040501
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2015-04-25 Cont ID  
Sent By jwitmer Date 2015-04-25 Time 10:59 Rev Time  
Received By jwitmer Date 2015-04-25 Time 10:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-05-14 Cont ID  
Sent By rlecky Date 2015-05-14 Time 11:55 Rev Time 0.00
Received By rlecky Date 2015-05-14 Time 11:49 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-04-15 Cont ID  
Sent By pleduc Date 2015-04-15 Time   Rev Time 0.00
Received By pleduc Date 2015-04-15 Time 16:51 Sent To  
Notes
2015-04-15 16:54:23THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF THE
 FIRE ALARM AND SPRINKLER SYSTEM FOR CODE COVERAGE AND
 COMPLIANCE.
  
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-05-14 Cont ID  
Sent By tklarge Date 2015-05-14 Time 14:47 Rev Time 0.00
Received By tklarge Date 2015-04-14 Time 09:32 Sent To  
Notes
2015-04-15 09:33:23SENT TO B28 SHELF FOR REVIEW. JG.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2015-05-18 Cont ID  
Sent By skennedy Date 2015-05-18 Time 13:26 Rev Time 0.00
Received By ccole Date 2015-05-18 Time 07:13 Sent To  
Notes
2015-05-18 07:15:48MECHANICAL PROVISO:
 REMOVE BATH EXHAUST FAN AND EXHAUST DUCTS. CAP AND SEAL
 EXTERIOR OPENINGS.
  
 CHRISTOPHER COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
2015-05-13 13:34:18REVIEW BY CHRIS COLE 5/12/15.
  
 1) SHEET D-1: PROVIDE NOTES AND DETAILS CLARIFYING
 SCOPE OF WORK FOR MECHANICAL DEMOLITION.
 2) A NEW TENANT SPACE IS BEING CREATED: PROVIDE A
 VENTILATION CALCULATION PER TABLE 404.3 FMC-10,
 AND AN AC LOAD CALULATION PER SECTION 503.2.1 FBC-10
 ENERGY CONSERVATION, OR INDICATE IT WILL BE DONE UNDER
 THE BUILD-OUT PERMIT.

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-05-14 Cont ID  
Sent By tklarge Date 2015-05-14 Time 14:42 Rev Time 0.00
Received By tklarge Date 2015-05-14 Time 14:31 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2015-04-24 Cont ID  
Sent By ajones Date 2015-04-24 Time 15:40 Rev Time 0.00
Received By ajones Date 2015-04-24 Time 15:40 Sent To  
Notes
***NONE***