Plan Review Details - Permit 15040499
Plan Review Stops For Permit 15040499
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-08-14 Cont ID  
Sent By jgomez Date 2015-08-14 Time 16:57 Rev Time 0.00
Received By jgomez Date 2015-08-14 Time 16:57 Sent To  
Notes
2015-08-14 16:57:25RESIDENTIAL (R3) ADDITION/ALTERATION SECOND BUILDING
 REVIEW CHECKLIST.
 CODE: 2010 FBC.
  
 NOTE:
 AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
  
  
 1- PROVIDE ENERGY CALCULATIONS. SEC. 1006 OF 2010
 FBC-EXISTING BUILDING. NOTE: PLEASE COORDINATE ENERGY
 CALCULATIONS WITH PLANS AND PRODUCT APPROVALS TO AVOID
 CONFLICTS AND/OR UN-NECESSARY DELAYS.
  
 RESPONSE:
 WRONG ENERGY CALCULATIONS FORM WAS SUBMITTED. FORM
 502-2010 SUBMITTED IS FOR COMMERCIAL BUILDINGS. PROVIDE
 CORRECT FORM SEE SEC. 103.2.1.1 OF 2010 FBC-ENERGY
 CONSERVATION. PLEASE MAKE SURE ALL THE INFORMATION IS
 COMPLETED AND FORM IS SIGNED BY ALL REQUIRED PARTIES.
 ARCHITECT LISTED ON THE FORM TO SIGN AND SEAL THE
 DOCUMENT AS REQUIRED BY CHAPTER 481 FLORIDA STATUTE.
  
 2- PROVIDE COMPLETE DESIGN INFORMATION: BUILDING
 EXPOSURE, ULTIMATE AND NOMINAL WIND SPEED. SEC.
 R301.2.1.3 AND SEC. R301.2.1.4 OF 2010 FBC-RESIDENTIAL.
  
 RESPONSE:
 THIS BUILDING IS NO LOCATED IN EXPOSURE "B". REVISE AS
 REQUIRED. IT LOOKS MORE LIKE EXPOSURE "D". SEE SEC.
 R301.2.1.4 AND EXPOSURE "D" ON SEC. R301.2.1.4.3.
 REVISE AS REQUIRED OR PROVIDE COMPLETE RATIONAL
 ANALYSIS CALCULATIONS AS SPECIFIED ON THE EXCEPTION OF
 SEC. R301.2.1.4.
 AND REVISE ALL THE BUILDING AND COMPONENTS AND CLADDING
 DESIGN PRESSURES ACCORDINGLY.
  
 3- PROPERTY IS LOCATED IN FLOOD ZONE A5. CITY FLOOD
 PREVENTION AND CONTROL SEC. 94-541 REQUIRES FINISH
 FLOOR ELEVATION TO BE 6" ABOVE THE BASE FLOOR
 ELEVATION. THE BASE FLOOD ELEVATION FOR FLOOD ZONE A5
 IS 7'-0". PROVIDE COMPLETE INFORMATION SHOWING
 COMPLIANCE WITH THE FLOOD RESISTANT CONSTRUCTION AS
 REQUIRED BY SEC. R322 OF 2010 FBC-RESIDENTIAL. PROVIDE
 SURVEY SHOWING THE FINISH FLOOR ELEVATION OF EXISTING
 HOUSE AND GARAGE AND THE PROPOSED ADDITION.
  
 RESPONSE:
 (A) REVISE SURVEY SUBMITTED. THIS PROPERTY IS LOCATED
 IN FLOOD ZONE "A" NOT "B".
  
 (B) SURVEY SUBMITTED DOESN'T SPECIFY THE FINISHED FLOOR
 OF THE PROPOSED ADDITION.
  
 (C) INFORMATION SHOWN ON SURVEY AND ARCHITECTURAL PLANS
 DON'T MATCH. SURVEY CALLS FOR FINISH FLOOR ELEVATION OF
 8.4 FOR ENTIRE HOUSE AND 6.3 FOR THE GARAGE.
 ARCHITECTURAL PLANS CALLS FOR 7.9 AT FAMILY ROOM AREA
 AND THE PROPOSED ADDITION. INFORMATION NEED TO MATCH.
 SURVEY NEEDS TO BE CLEAR ON ALL FINISHED FLOOR
 ELEVATIONS. THIS INFORMATION WILL BE REQUIRED FOR THE
 ELEVATION CERTIFICATES DURING CONSTRUCTION. CORRECT ALL
 THE INFORMATION AS REQUIRED TO MATCH.
  
 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) ALL WINDOW TYPES SHOWN ON PLANS.
 RESPONSE:
 NOT INFORMATION SUBMITTED.
  
 B) FLAT ROOF. AND CLEARLY IDENTIFY SELECTED ASSEMBLY.
 PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS IF THE
 SELECTED ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES
 REQUIRED BY SEC. R301 OF 2010 FBC-RESIDENTIAL.
 RESPONSE:
 ARCHITECT SPECIFIED NOA ON SHEET A-1.1. NEED TO SUBMIT
 NOA. IDENTIFY APPROVED ASSEMBLY AND NEED THE SIGNED AND
 SEALED RAS 117 CALCULATIONS.
  
 C) HUGHES, SEMCO AND SIMPSON STRUCTURAL CONNECTORS
 SPECIFIED ON ALL DETAILS. PROVIDE ONLY THE FLORIDA
 PRODUCT APPROVAL COVER PAGE AND THE PAGE SHOWING THE
 SPECIFIED CONNECTOR. OR, LIST THE FLORIDA PRODUCT
 APPROVAL NUMBER NEXT TO EACH SPECIFIED CONNECTOR.
 RESPONSE:
 UNABLE TO FIND THE MIAMI-DADE NOA'S LISTED ON THE
 DETAILS. ALSO, HUGHES TP6X SPECIFIED ON DETAIL #4 OF
 SHEET A-1.1 DOESN'T HAVE ANY NOA NUMBER.
  
 D) HARDIEBOARD FASCIA, SOFFIT AND SIDING SPECIFIED ON
 PLANS.
 RESPONSE:
 NO INFORMATION SUBMITTED. ARCHITECT SPECIFIED NOA'S ON
 DRAWINGS BUT NO INFORMATION WAS SUBMITTED.
  
 E) NEW INSWING DOOR SHOWN IN THE HOME OFFICE.
 RESPONSE:
 NO INFORMATION WAS SUBMITTED.
  
 5- DESIGN PROFESSIONAL TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 6- SHEET A-1.0: SPECIFY TYPE AND SIZE OF BEDROOM #1
 WINDOW TO VERIFY COMPLIANCE WITH THE EGRESS
 REQUIREMENTS OF SEC. 604 OF 2010 FBC-EXISTING BUILDING.
 NOTE: THERE WERE SOME WINDOWS ON BEDROOM #1 THAT WERE
 ELIMINATED. EGRESS OPENINGS WERE REDUCED. NOW, THIS
 WINDOW IS THE ONLY MEANS OF EGRESS FOR THIS BEDROOM.
 NEED COMPLIANCE WITH SEC. R310 OF 2010 FBC-RESIDENTIAL.
  
 RESPONSE:
 SPECIFY SIZE AND TYPE OF EXISTING WINDOW ON PLANS.
  
 7- PROVIDE ICC CURRENT EVALUATION REPORT FOR THE
 ICYNENE INSULATION SPECIFIED ON THE WALL SECTION ON
 SHEET A-1.1. SEC. R316 2010 FBC-RESIDENTIAL AND SEC.
 103.2.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 IMPORTANT: PROPERTY IS LOCATED IN FLOOD ZONE A5:
 ELEVATION CERTIFICATES WILL BE REQUIRED DURING
 CONSTRUCTION.
  
 *** PLEASE PROVIDE A RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 *** PLEASE REPLACE AND REMOVE ANY REVISED DRAWING.
 SUBMIT A COPY OF ORIGINAL DRAWINGS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-06-10 Cont ID  
Sent By jgomez Date 2015-06-10 Time 09:18 Rev Time 0.00
Received By jgomez Date 2015-06-10 Time 09:11 Sent To  
Notes
2015-06-10 09:28:17RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
  
 2- ARCHITECT TO PROVIDE ALL HIS INFORMATION ON THE
 TITLE BLOCK AS REQUIRED BY FLORIDA ADMINISTRATIVE CODE
 SEC. 61G1-16.004 AND CHAPTER 481 F.S.
  
 3- PROVIDE ENERGY CALCULATIONS. SEC. 1006 OF 2010
 FBC-EXISTING BUILDING. NOTE: PLEASE COORDINATE ENERGY
 CALCULATIONS WITH PLANS AND PRODUCT APPROVALS TO AVOID
 CONFLICTS AND/OR UN-NECESSARY DELAYS.
  
 4- PROVIDE COMPLETE DESIGN INFORMATION: BUILDING
 EXPOSURE, ULTIMATE AND NOMINAL WIND SPEED. SEC.
 R301.2.1.3 AND SEC. R301.2.1.4 OF 2010 FBC-RESIDENTIAL.
  
 5- ARCHITECT TO SPECIFY ALTERATION TYPE AS REQUIRED BY
 SEC. 401.4 OF 2010 FBC-EXISTING BUILDING. NOTE: CLARIFY
 NOTE SHOWN ON DETAIL #2 BACKYARD VIEW OF WORK ON SHEET
 A-0.0. WHAT'S "SUNROOM REPLACED WITH ADDITION - ALT
 ONE"?. IS THIS ALTERATION LEVEL ONE?. IF SO, THEN IT'S
 INCORRECT. REVISE AS REQUIRED. SEE CHAPTER 4 OF 2010
 FBC-EXISTING BUILDING.
  
 6- PROPERTY IS LOCATED IN FLOOD ZONE A5. CITY FLOOD
 PREVENTION AND CONTROL SEC. 94-541 REQUIRES FINISH
 FLOOR ELEVATION TO BE 6" ABOVE THE BASE FLOOR
 ELEVATION. THE BASE FLOOD ELEVATION FOR FLOOD ZONE A5
 IS 7'-0". PROVIDE COMPLETE INFORMATION SHOWING
 COMPLIANCE WITH THE FLOOD RESISTANT CONSTRUCTION AS
 REQUIRED BY SEC. R322 OF 2010 FBC-RESIDENTIAL. PROVIDE
 SURVEY SHOWING THE FINISH FLOOR ELEVATION OF EXISTING
 HOUSE AND GARAGE AND THE PROPOSED ADDITION. NOTE:
 SUBSTANTIAL IMPROVEMENTS MAY TRIGGER THE HOUSE TO BE
 RAISED IF THE FINISH FLOOR ELEVATION IS BELOW 7'-6".
 THE FOLLOWING IS THE DEFINITION OF SUBSTANTIAL
 IMPROVEMENTS: SUBSTANTIAL IMPROVEMENT MEANS ANY
 COMBINATION OF REPAIRS, RECONSTRUCTION, ALTERATION, OR
 IMPROVEMENTS TO A STRUCTURE, TAKING PLACE DURING THE
 LIFE OF A STRUCTURE, IN WHICH THE CUMULATIVE COST
 EQUALS OR EXCEEDS 50 PERCENT OF THE MARKET VALUE OF THE
 STRUCTURE. THE MARKET VALUE OF THE STRUCTURE SHOULD BE
 THE APPRAISED VALUE OF THE STRUCTURE PRIOR TO THE START
 OF THE INITIAL REPAIR OR IMPROVEMENT, OR IN THE CASE OF
 DAMAGE, THE VALUE OF THE STRUCTURE PRIOR TO THE DAMAGE
 OCCURRING. FOR THE PURPOSES OF THIS DEFINITION,
 "SUBSTANTIAL IMPROVEMENT" IS CONSIDERED TO OCCUR WHEN
 THE FIRST ALTERATION OF ANY WALL, CEILING, FLOOR, OR
 OTHER STRUCTURAL PART OF THE BUILDING COMMENCES,
 WHETHER OR NOT THAT ALTERATION AFFECTS THE EXTERNAL
 DIMENSIONS OF THE STRUCTURE. THE TERM "SUBSTANTIAL
 IMPROVEMENT" DOES NOT, HOWEVER, INCLUDE ANY IMPROVEMENT
 OF A STRUCTURE TO COMPLY WITH EXISTING HEALTH,
 SANITARY, OR SAFETY CODES WHICH ARE SOLELY NECESSARY TO
 ENSURE SAFE LIVING CONDITIONS.
  
 7- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) ALL WINDOW TYPES SHOWN ON PLANS.
  
 B) WINDOW MULLIONS. AND, SPECIFY SIZE TO VERIFY
 COMPLIANCE WITH THE DESIGN PRESSURES.
  
 C) FLAT ROOF. AND CLEARLY IDENTIFY SELECTED ASSEMBLY.
 PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS IF THE
 SELECTED ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES
 REQUIRED BY SEC. R301 OF 2010 FBC-RESIDENTIAL.
  
 D) HUGHES, SEMCO AND SIMPSON STRUCTURAL CONNECTORS
 SPECIFIED ON ALL DETAILS. PROVIDE ONLY THE FLORIDA
 PRODUCT APPROVAL COVER PAGE AND THE PAGE SHOWING THE
 SPECIFIED CONNECTOR. OR, LIST THE FLORIDA PRODUCT
 APPROVAL NUMBER NEXT TO EACH SPECIFIED CONNECTOR.
  
 E) HARDIEBOARD FASCIA, SOFFIT AND SIDING SPECIFIED ON
 PLANS.
  
 F) NEW INSWING DOOR SHOWN IN THE HOME OFFICE.
  
 8- DESIGN PROFESSIONAL TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 9- PROVIDE FOUNDATION AND ROOF FRAMING PLAN WITH
 COMPLETE INFORMATION. SEC. 107.3.5.3(5) CITY
 AMENDMENTS.
  
 10- SHEET A-1.0: SPECIFY TYPE AND SIZE OF BEDROOM #1
 WINDOW TO VERIFY COMPLIANCE WITH THE EGRESS
 REQUIREMENTS OF SEC. 604 OF 2010 FBC-EXISTING BUILDING.
 NOTE: THERE WERE SOME WINDOWS ON BEDROOM #1 THAT WERE
 ELIMINATED. EGRESS OPENINGS WERE REDUCED. NOW, THIS
 WINDOW IS THE ONLY MEANS OF EGRESS FOR THIS BEDROOM.
 NEED COMPLIANCE WITH SEC. R310 OF 2010 FBC-RESIDENTIAL.
  
 11- WALL SECTION #1 ON SHEET A-1.1 :
 A) SPECIFY SIZE OF RING SHANK NAILS SPECIFIED FOR THE
 ROOF SHEATHING AS REQUIRED BY SEC. R803.2.3.1 OF 2010
 FBC-RESIDENTIAL.
  
 B) CLARIFY HOW TO INSTALL R-35 FGB INSULATION ON A 2X10
 ROOF JOIST?. IT LOOKS LIKE IT DOESN'T FIT ON A 2X10.
 PROVIDE SPECS FOR THE R-35 FGB. SEC. 103.2.2 OF 2010
 FBC-ENERGY CONSERVATION. NOTE: COORDINATE WITH ROOF
 CROSS VENTILATION ON ITEM #12 BELOW.
  
 C) SPECIFY CONNECTOR FOR 2X10 ROOF JOISTS. NOTE:
 SPECIFY CONNECTORS AT BOTH ENDS. SEC. R301.1 OF 2010
 FBC-RESIDENTIAL.
  
 D) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 INSTALLATION OF THE DROPPED CEILING. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 E) CLARIFY WALL INSULATION. R-19 OR R-21. ONLY THE
 VALUE OF THE INSULATION CAN BE ACCOUNTED FOR. SEE SEC.
 304.1.2 OF 2010 FBC-RESIDENTIAL.
  
 F) CLARIFY SIZE OF SS-J-BOLT ANCHOR SPECIFIED TO FASTEN
 THE BOTTOM PLATE. 12"???. ALSO, SPECIFY HOW MUCH
 EMBEDMENT IS REQUIRED INTO THE CONCRETE SLAB. SEC.
 R301.1 OF 2010 FBC-RESIDENTIAL.
  
 12- SPECIFY ROOF CROSS VENTILATION OR PROVIDE COMPLETE
 DETAILS AND SPECIFICATIONS IF DESIGNING A NON VENTED
 ROOF AS REQUIRED BY SEC. R806 OF 2010 FBC-RESIDENTIAL.
  
 13- HURRICANE CLIPS DETAIL #3 ON SHEET A-1.1 IS NOT
 LEGIBLE. LETTERING AND DRAWINGS ARE TOO SMALL. REVISE
 AS REQUIRED. SEC. 107.2.1.4 CITY AMENDMENTS.
  
 14- SPECIFY CARBON MONOXIDE ALARMS FOR ALL BEDROOMS AS
 REQUIRED BY SEC. R315 OF 2010 FBC-RESIDENTIAL.
  
 IMPORTANT: PROPERTY IS LOCATED IN FLOOD ZONE A5:
 ELEVATION CERTIFICATES WILL BE REQUIRED DURING
 CONSTRUCTION.
  
 *** PLEASE PROVIDE A RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 *** PLEASE REPLACE AND REMOVE ANY REVISED DRAWING.
 SUBMIT A COPY OF ORIGINAL DRAWIING FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-08-18 Cont ID  
Sent By albarran Date 2015-08-18 Time 14:03 Rev Time 0.00
Received By albarran Date 2015-08-18 Time 13:30 Sent To Z
Notes
2015-08-18 14:05:47ALL PREVIOUSLY MENTIONED DEFICIENCIES HAVE BEEN
 ADDDRESSED WITH THE EXCEPTION OF THE OUTLET SPACING IN
 THE KITCHEN HAVE BEEN ADDRESSED ON THE NARRATIVE.
 PROPER OUTLET SPACING WILL BE DIFFERED TO FIELD
 INSPECTOR FOR APPROVAL.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-06-01 Cont ID  
Sent By albarran Date 2015-06-01 Time 17:28 Rev Time 0.00
Received By albarran Date 2015-06-01 Time 17:06 Sent To  
Notes
2015-06-01 17:37:21THE FOLLOWING ITEMS SHALL BE CORRECTED AND THE PLANS
 RESUBMITTED FOR A SECOND REVIEW:
  
 THESE PLANS WERE REVIEWED FOR COMPLIANCE WITH THE 2008
 EDITION OF THE NEC, THE 2013 EDITION OF THE NFPA72, THE
 APPLICABLE CHAPTERS OF THE 2010 EDITION OF THE FLORIDA
 BUILDING CODE, FLORIDA BUILDING CODE RESIDENTIAL AND
 FLORIDA BUILDING CODE ENERGY CONSERVATION.
 1. KITCHEN OUTLETS AS INDICATED ON DRAWINGS DO NOT MEET
 MINIMUM CODE SPACING REQUIREMENTS. NEC 210.52(C)
 2. IN THE OFFICE AND GAME ROOM THE RECEPTACLES SHALL BE
 SPACES AS I9NDICATED IN NEC 210.52(A)
 3. THE A/C IN THE ATTIC REQUIRES A PERMANENT LADDER BE
 INSTALLED PER NEC 110.33(B)
 4. AN OUTLET IS REQUIRED ON THE AREA OF THE TERRACE PER
 NEC 210.52(E)
 5. ALL NEWLY INSTALLED RECEPTACLES SHALL BE
 TAMPER-RESISTANT PER NEC 406.11
 6. ALL NEW CIRCUITS SHALL BE PROTECTED W/ARC-FAULT
 BREAKERS AS PER NEC 210.12
 7. IF NOT ALREADY IN COMPLIANCE, YOU SHALL INSTALL
 SMOKE DETECTORS TO COMPLY W/FBC-R 314 & 315
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS
  
 FOR QUESTIONS ON THE ABOVE, PLEASE CONTACT:
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 PH: (561) 805-6743
 EMAIL: [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-08-21 Cont ID  
Sent By jgomez Date 2015-08-21 Time 15:04 Rev Time 0.00
Received By jgomez Date 2015-07-24 Time 13:07 Sent To  
Notes
2015-07-24 13:07:54R03

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-06-10 Cont ID  
Sent By jgomez Date 2015-06-10 Time 09:54 Rev Time 0.00
Received By jgomez Date 2015-04-14 Time 10:28 Sent To  
Notes
2015-04-15 10:28:41SENT TO R15 SHELF FOR REVIEW. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2015-08-14 Cont ID  
Sent By jgomez Date 2015-08-14 Time 17:22 Rev Time 0.00
Received By jgomez Date 2015-08-14 Time 17:21 Sent To  
Notes
2015-08-14 17:22:341- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-06-10 Cont ID  
Sent By jgomez Date 2015-06-10 Time 09:54 Rev Time 0.00
Received By jgomez Date 2015-06-10 Time 09:54 Sent To  
Notes
2015-06-10 09:54:341- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-08-17 Cont ID  
Sent By ccole Date 2015-08-17 Time 13:54 Rev Time 0.00
Received By ccole Date 2015-08-17 Time 13:54 Sent To  
Notes
2015-08-17 14:04:422ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #15040499
 8/17/15
  
 1) 2ND REQUEST FOR AC COOLING AND HEATING CALCULATIONS-
 REFER TO SECTION 403.6.1 FBC-10 ENERGY CONSERVATION.
 2) 2ND REQUEST FOR ENERGY CALCULATIONS- THE SUBMITTED
 FORMS ARE FOR COMMERCIALS BUILDINGS. PLEASE REFER TO
 TABLE 103.2.1 FBC-10 ENERGY CONSERVATION- SUBMIT TWO
 COPIES OF FORM 402 (PRESCRITPTIVE COMPLIANCE PATH), OR
 FORM 405 (PERFROMANCE COMPLIANCE PATH USING COMMISSION
 APPROVED COMPUTER SOFTWARE SUCH AS ENERGY GAUGE).
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-05-15 Cont ID  
Sent By skennedy Date 2015-05-15 Time 07:32 Rev Time 0.00
Received By skennedy Date 2015-04-14 Time 07:32 Sent To  
Notes
2015-05-15 07:43:59 
 1ST REVIEW: FBC 2010 MECHANICAL
 CHRISTOPHER COLE
  
 1) PROVIDE AC LOAD CALCULATIONS FOR THE NEW GAME
 ROOM/HOME OFFICE ADDTIIONS- SECTION 403.6.1 FBC-10
 ENERGY CONSERVATION.
 2) PROVIDE ENERGY CALCULATIONS PER SECTION 101.4.3
 FBC-10 ENERGY CONSERVATION. SUBMIT TWO COPIES OF EITHER
 FORM 402, OR ENERGY GAUGE FORM 405.
 3) SHEET A-3.0: A MEANS OF RETURN AIR MUST BE PROVIDED
 FROM THE NEW ADDITION ROOMS- SECTION M1602.4 FBC-10
 RESIDENTIAL.
  
 CHRISTOPHER COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status N Date 2015-08-14 Cont ID  
Sent By jgomez Date 2015-06-10 Time 18:51 Rev Time 0.00
Received By jgomez Date 2015-06-10 Time 18:51 Sent To  
Notes
2015-06-10 18:51:53PLEASE E-MAIL SAMANTHA HILL WHEN PERMIT IS ISSUED.

Review Stop P PLUMBING
Rev No 1 Status N Date 2015-05-14 Cont ID  
Sent By tklarge Date 2015-05-14 Time 10:13 Rev Time 0.00
Received By tklarge Date 2015-05-14 Time 09:43 Sent To  
Notes
2015-05-14 10:15:17REPLACEMENT OF KIT. SINK & DISHWASHER EXEMPT FROM
 PERMIT.WPB AMEND. TO 2010 FBC SEC.105.2.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2015-08-14 Cont ID  
Sent By jgomez Date 2015-08-14 Time 19:14 Rev Time 0.00
Received By jgomez Date 2015-08-14 Time 19:14 Sent To  
Notes
2015-08-14 19:14:331- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) FLAT ROOF. AND CLEARLY IDENTIFY SELECTED ASSEMBLY.
 PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS IF THE
 SELECTED ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES
 REQUIRED BY SEC. R301 OF 2010 FBC-RESIDENTIAL.
  
 RESPONSE:
 ARCHITECT SPECIFIED NOA ON SHEET A-1.1. NEED TO SUBMIT
 NOA SHOWING THE SELECTED APPROVED ASSEMBLY. AND NEED
 THE SIGNED AND SEALED RAS 117 CALCULATIONS.
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2015-06-10 Cont ID  
Sent By jgomez Date 2015-06-10 Time 18:52 Rev Time 0.00
Received By jgomez Date 2015-06-10 Time 18:52 Sent To  
Notes
2015-06-10 18:53:501- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) FLAT ROOF. AND CLEARLY IDENTIFY SELECTED ASSEMBLY.
 PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS IF THE
 SELECTED ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES
 REQUIRED BY SEC. R301 OF 2010 FBC-RESIDENTIAL.
  

Review Stop Z ZONING
Rev No 3 Status P Date 2015-08-20 Cont ID  
Sent By sgraham Date 2015-08-20 Time 16:07 Rev Time 0.00
Received By sgraham Date 2015-08-21 Time 14:32 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2015-05-19 Cont ID  
Sent By sgraham Date 2015-05-19 Time 16:14 Rev Time 0.00
Received By sgraham Date 2015-05-19 Time 16:14 Sent To  
Notes
2015-05-19 16:15:455/19/15 ZONING FAILED 2ND CHECKLIST
  
 1. SUBMIT TWO UP TO DATE SURVEYS.

Review Stop Z ZONING
Rev No 1 Status F Date 2015-05-08 Cont ID  
Sent By sgraham Date 2015-05-08 Time 12:43 Rev Time 0.00
Received By sgraham Date 2015-05-08 Time 12:43 Sent To  
Notes
2015-05-08 12:44:085/8/15 ZONING FAILED
 1. SUBMIT TWO UP TO DATE SURVEYS