| 2015-04-15 08:48:38 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FOR YOUR CONVENIENCE, A SUMMARY OF THE DOCUMENTS |
| | SUBMITTED ARE AT THE END OF THIS PLAN REVIEW. |
| | |
| | 1. DUE TO THE NUMBER OF PERMITS, IT IS RECOMMENDED THAT |
| | A "MASTER" BE GENERATED. THE PERMIT DOCUMENTS WOULD BE |
| | STORED UNDER THE MASTER, PERMIT CARDS WOULD REFERENCE |
| | THE MASTER, AND CONTRACTOR WOULD PROVIDE A FEW SETS OF |
| | DOCUMENTS - ONE FOR THIS DEPARTMENT TO RETAIN, AND A |
| | FEW SETS FOR INSPECTION PURPOSES (THE NUMBER WOULD |
| | DEPEND ON THE NUMBER OF BUILDINGS FOR WHICH INSPECTIONS |
| | WOULD BE CALLED IN ON ONE DAY AS IT IS A REQUIREMENT TO |
| | HAVE THE PLANS PROVIDED ON THE JOBSITE AT TIME OF |
| | INSPECTION). A MINIMUM OF THREE INSPECTION SETS ARE |
| | RECOMMENDED. |
| | |
| | IF CONTRACTOR ELECTS NOT TO USE A MASTER, EACH PERMIT |
| | PACKAGE IS TO BE REVISED TO ADDRESS ALL COMMENTS. THE |
| | NOA WAS SUBMITTED WITH SHEET 2 ON THE TOP OF THE |
| | PACKAGE. WHEN RESUBMITTING, PLEASE PUT NOA PAGES IN |
| | ORDER. THIS HAS BEEN DONE FOR YOU FOR APPROXIMATELY |
| | HALF OF THE APPLICATIONS. |
| | |
| | 2. PROVIDE INFORMATION REGARDING THE EXISTING ROOF. THE |
| | PERMIT DOCUMENTS SHOULD INCLUDE ALL INFORMATION |
| | REQUIRED TO DEMONSTRATE CODE COMPLIANCE, FBC 107. |
| | |
| | BASED ON TWO RECORDS, (PERMIT #01041400 FOR ADDRESSES |
| | 7113,7114 71ST WAY AND 7223 7224 72ND WAY, ALSO SEE |
| | 01041405, 01041403), IT APPEARS THAT THE EXISTING ROOF |
| | SYSTEM IS TPO, INSULATED DECK (NOA 98-0305.02, JPS |
| | ELASTOMERIC CORPORATION, STEVENS ROOFING SYSTEMS, |
| | SINGLE PLY ROOFING SYSTEM OVER CONCRETE DECK, NOA |
| | SUB-TYPE TPO). DESCRIPTIONS OF ADDRESSES INCLUDED IN |
| | THESE THREE PERMITS ARE AVAILABLE ON THE INTERNET. I |
| | HAVE VERIFIED THAT BOTH 01041400 AND 01041405 WERE |
| | ISSUED WITH THE TPO ROOF NOA REFERENCED. EXISTING ROOF |
| | TYPE SHOULD BE FIELD VERIFIED BY CONTRACTOR. |
| | |
| | 3. SEE PAGE 3, PVC SINGLE PLY ROOF SYSTSMS IS |
| | UNDERLINED. BASED ON OUR PERMIT RECORDS FOR THIS |
| | PROJECT, THE ROOF IS TPO. TPO IS NOT ONE OF THE SYSTEMS |
| | INCLUDED IN THE MIAMI DADE NOA. PLEASE ADDRESS BY |
| | PROVIDING INFORMATION FROM THE MANUFACTURER WHICH |
| | DOCUMENTS THE SUITABILITY OF THIS APPLICATION. |
| | |
| | 4. PROVIDE SPEC SHEETS FOR THE GACOWASH. THIS SHOULD |
| | PROVIDE INFORMATION ABOUT THE PRODUCT AS WELL AS |
| | RECOMMENDED DILUTION RATE, FBC 107. |
| | |
| | 5. E5320 IS SPECIFIED AS A "PRIMER COAT" IN THE |
| | PROPOSAL. PROVIDE MANUFACTURER SPEC SHEETS/INSTALLATION |
| | INSTRUCTIONS, FBC 107. APPLICATION PROPOSES "PRIMER" AT |
| | A RATE OF 1 GALLON / 250 SF. SINCE THIS PRODUCT DOES |
| | NOT APPEAR TO HAVE A PRODUCT APPROVAL (IT IS ONLY |
| | REFERENCED IN THE ROOF COATING SYSTEMS IN THE NOA), |
| | PROVIDE MANUFACTURER SPEC SHEETS WHICH INCLUDE |
| | INFORMATION ABOUT THE PRODUCT AND THE RECOMMENDED |
| | APPLICATION METHOD AND RATE. ALTHOUGH IT DOES NOT HAVE |
| | A PRODUCT APPROVAL, IT APPEARS THAT THIS IS THE PRODUCT |
| | WHICH ASSURES THE BOND REQUIRED FOR WIND RESISTANCE FBC |
| | 1609. |
| | |
| | 6. APPLICATION AND PROPOSAL SPECIFY GACO FLEX S2000, |
| | 1.5 GALLONS PER 100 SF. SEE PAGE 3 OF THE NOA; TWO |
| | COATS AT A MINIMUM RATE OF .75 GAL / 100' EACH ARE |
| | REQUIRED. ALTHOUGH THE TOTAL GALLONS PER SF IS |
| | CONSISTENT WITH THE NOA, THE APPLICATION METHOD |
| | PROPOSED ("A TOP COAT") DOES NOT COMPLY WITH THE |
| | REQUIREMENTS OF THE NOA. |
| | |
| | 7. ONLY ONE PAGE OF A THREE PAGE CONTRACT WAS PROPOSED. |
| | PROVIDE THE COMPLETE CONTRACT, FBC 109. |
| | |
| | 8. IF METHOD OF INSTALLATION AS PROPOSED ON THE |
| | APPLICATION IS NOT APPROVED, NEW APPLICATIONS WILL BE |
| | REQUIRED. IT IS RECOMMENDED TO HAVE ONLY INFORMATION |
| | DESCRIBING THE PROJECT ON THE PERMIT APPLICATION (WHICH |
| | SHOULD INCLUDE ROOF AREA, TYPE OF ROOF PROPOSED, MEAN |
| | ROOF HEIGHT, DECK TYPE), AND HAVE SPECIFICATIONS FOR |
| | INSTALLATION IN THE PERMIT DOCUMENTS. IT IS NOT TYPICAL |
| | TO SPEC INSTALLATION IN THE PERMIT DESCRIPTION. AS THE |
| | PERMIT DESCRIPTION ON THE PERMIT APPLICATION DOES NOT |
| | APPEAR TO BE CODE COMPLIANT, A NEW PERMIT APPLICATION |
| | WILL BE REQUIRED UNLESS IT IS DETERMINED THAT THE |
| | INSTALLATION METHOD PROPOSED ON THE APPLICATION IS |
| | ACCEPTABLE AND A PERMIT IS ISSUED WITH THIS SPEC. |
| | |
| | 9. PERMIT 02090676 FOR 7404 74TH WAY IS EXPIRED (DID |
| | NOT OBTAIN A FINAL INSPECTION). IF THIS PROJECT |
| | INCLUDES THIS ADDRESS, THIS PERMIT IS TO BE RESOLVED |
| | PRIOR TO ISSUANCE OF THE PERMIT FOR THAT BUILDING. |
| | |
| | TO RESOLVE THE EXPIRED PERMIT: |
| | |
| | APPLICATION WITH THE DESCRIPTION: "FINAL INSPECTION |
| | ONLY TO CLOSE EXPIRED PERMIT #02090676" TO BE SUBMITTED |
| | AT THE BUILDING DIVISION USING THE STANDARD COUNTY WIDE |
| | BUILDING PERMIT APPLICATION. A RECORDS RESEARCH REQUEST |
| | SHOULD BE SUBMITTED AT THE SAME TIME TO OBTAIN A COPY |
| | OF THAT PERMIT. IF AVAILABLE, IT WILL BE SUPPLIED FOR |
| | YOU. |
| | |
| | AFTER ISSUANCE, A FINAL INSPECTION SHOULD BE SCHEDULED. |
| | |
| | ******************************************************* |
| | ************ |
| | INFORMATION REGARDING DOCUMENTS SUBMITTED WITH |
| | APPLICATION: |
| | |
| | NOA 12-0426.06 WAS SUBMITTED. |
| | |
| | APPLICATION PROPOSED INSTALLATION STATES: "APPLY PRIMER |
| | AT RATE OF 1 GALLON PER 250 SQ FT APPLY G4CO FLEX S-200 |
| | AT RATE OF 1.5 GALLONS PER 100 SQ FT." |
| | |
| | SYSTEM "S-2000" IS UNDERLINED ON PAGE 3 OF THE NOA. |
| | |
| | PAGE 2 OF THE NOA HAS BEEN PULLED OUT OF ORDER AND PUT |
| | ON THE TOP OF EACH PACKAGE. IT IS NOT CLEAR WHY THIS |
| | WAS DONE; IT APPEARS THAT THE SYSTEM SELECTED IS ON |
| | PAGE 3. NOA SHOULD BE PUT IN ORDER. |
| | |
| | THE CONTRACT PROVIDED PROPOSES THE FOLLOWING, WHICH IS |
| | CONSISTENT WITH THE APPLICATION: |
| | |
| | PRIMER COAST OF GACOFLEX E-5320 PRIMER AT A RATE OF 1 |
| | GALLON PER 250 SF |
| | TOP COAT OF GACOFLEX S-2000 COATING AT A RATE OF 1.5 |
| | GALLONS PER 100 SF |
| | ******************************************************* |
| | ************ |