Plan Review Details - Permit 15040458
Plan Review Stops For Permit 15040458
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2015-06-26 Cont ID  
Sent By jgomez Date 2015-06-26 Time 15:55 Rev Time 0.00
Received By jgomez Date 2015-06-26 Time 15:54 Sent To  
Notes
2015-07-01 09:41:36NOTE:
 ANY A/C EQUIPMENT REMOVAL REQUIRES SEPARATE PERMIT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2015-06-24 Cont ID  
Sent By jgomez Date 2015-06-24 Time 17:15 Rev Time 0.00
Received By jgomez Date 2015-06-24 Time 17:15 Sent To  
Notes
2015-06-24 17:20:20RECOVERY ROOF FOURTH BUILDING REVIEW CHECKLIST.
 CODE: 2010 FBC.
  
 1- NEW FLORIDA PRODUCT APPROVAL FL5680-R14 SUBMITTED:
 SELECTED RECOVERY ASSEMBLY R-28 CAN NOT BE USED BECAUSE
 THIS ASSEMBLY MAXIMUM DESIGN PRESSURE IS - 75 PSF. THIS
 DESIGN PRESSURE DOESN'T MEET THE DESIGN PRESSURES
 CALCULATED BY THE ENGINEER ON THE ECS REPORT SUBMITTED.
 NOTE #9 ON PAGE 2 OF 76 STATES "FOR FULLY BONDED
 ASSEMBLIES, THE MAXIMUM DESIGN PRESSURE FOR THE
 SELECTED ASSEMBLY SHALL MEET OR EXCEED CRITICAL DESIGN
 PRESSURE DETERMINED IN ACCORDANCE WITH FBC CHAPTER 16,
 AND NO RATIONAL ANALYSIS IS PERMITTED."
  
 NOTE: PER CONVERSATION WITH ROBERT BROWN (BUILDING
 OFFICIAL) THERE ARE TWO OPTIONS SINCE THE PROPOSED
 RECOVERY ASSEMBLY IS A FULLY BONDED ASSEMBLY:
  
 A) PROVIDE AN APPROVED ASSEMBLY THAT MEETS THE DESIGN
 PRESSURES FOR ALL ROOF ZONES. OR
  
 B) HIRE AN STATE CERTIFIED ROOFING CONSULTANT TO
 PROVIDE COMPLETE ANALYSIS OF PROPOSED ROOFING ASSEMBLY.
 FOR THIS OPTION, PLEASE CONTACT ROBERT BROWN
 (561)805-6652 FOR PROPER DOCUMENTATION.
  
  
 NOTE:
 MOISTURE TEST SUBMITTED DOESN'T MEET THE STANDARD
 PROCEDURES FOR ROOF MOISTURE SURVEYS (TAS 126-95).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2015-06-12 Cont ID  
Sent By jgomez Date 2015-06-12 Time 16:25 Rev Time 0.00
Received By jgomez Date 2015-06-12 Time 15:48 Sent To  
Notes
2015-06-12 16:41:28RECOVERY ROOF THIRD BUILDING REVIEW CHECKLIST.
 CODE: 2010 FBC.
  
 NOTE: BASED ON THE ROOFING PRODUCT APPROVAL SUBMITTED
 THE INFORMATION BELOW IS REQUIRED. THAT'S WHY THE
 PRODUCT APPROVAL WAS REQUESTED SINCE THE FIRST REVIEW,
 BUT IT WAS NEVER SUBMITTED UNTIL NOW.
  
 1- FLORIDA PRODUCT APPROVAL SUBMITTED:
 A) FLORIDA PRODUCT APPROVAL FL16730-R3 SUBMITTED WAS
 REVISED BY FLORIDA PRODUCT APPROVAL FL 16730-R4.
 PROVIDE COPY OF CURRENT FLORIDA PRODUCT APPROVAL
 FL16730-R4. FL16730-R3 IS NO LONGER VALID.
  
 B) SELECTED ASSEMBLY R-20 CAN NOT BE USED BECAUSE THIS
 ASSEMBLY MAXIMUM DESIGN PRESSURE IS -45PSF. THIS DESIGN
 PRESSURE DOESN'T MEET THE DESIGN PRESSURES CALCULATED
 BY THE ENGINEER ON THE ECS REPORT SUBMITTED. IN
 ADDITION, THIS ASSEMBLY HAS AN ASTERISK AFTER THE
 DESIGN PRESSURE OF -45PSF. NOTE #10 OF THE FLORIDA
 PRODUCT APPROVAL FL16730-R4 (AND FL16730-R3) STATES
 THAT "FOR ASSEMBLIES MARKED WITH AN ASTERISK*, THE
 MAXIMUM DESIGN PRESSURE (MDP) LIMITATION LISTED SHALL
 BE APPLICABLE TO ALL ROOF PRESSURE ZONES (I.E., FIELD,
 PERIMETERS AND CORNERS). NEITHER RATIONAL ANALYSIS, NOR
 EXTRAPOLATION IS PERMITTED FOR ENHANCED ATTACHMENT AT
 ENHANCED PRESSURE ZONES (I.E., PERIMETERS, CORNERS AND
 EXTENDED CORNERS)."
  
 NOTES:
 (1) NEED TO SELECT AN ASSEMBLY THAT MEETS THE
 CALCULATED DESIGN PRESSURES OR THAT ALLOWS RAS 117
 CALCULATIONS (NAIL ENHANCING CALCULATIONS TO INCREASE
 THE DESIGN PRESSURES).
  
 (2) IF RAS 117 CALCULATIONS ARE REQUIRED, THEN THEY
 NEED TO BE SIGNED AND SEALED.
  
 C) LIMITATION #5.7 OF FLORIDA PRODUCT APPROVAL
 FL16730-R4 STATES THAT " FOR RECOVER INSTALLATIONS, THE
 EXISTING ROOF SHALL BE EXAMINED IN ACCORDANCE WITH FBC
 1521.". SECTION 1521.12 REQUIRES A MOISTURE CONTENT
 TEST (TAS 126). NEED TO PROVIDE COPY OF THIS TEST.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-06-02 Cont ID  
Sent By jgomez Date 2015-06-02 Time 17:13 Rev Time 0.00
Received By jgomez Date 2015-06-02 Time 17:13 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-04-16 Cont ID  
Sent By jgomez Date 2015-04-16 Time 16:44 Rev Time 0.00
Received By jgomez Date 2015-04-16 Time 10:54 Sent To  
Notes
2015-04-16 16:50:47RECOVERY ROOF THIRD BUILDING REVIEW CHECKLIST.
 CODE: 2010 FBC.
  
 1- FLORIDA PRODUCT APPROVAL SUBMITTED:
 A) FLORIDA PRODUCT APPROVAL FL16730-R3 SUBMITTED WAS
 REVISED BY FLORIDA PRODUCT APPROVAL FL 16730-R4.
 PROVIDE COPY OF CURRENT FLORIDA PRODUCT APPROVAL
 FL16730-R4. FL16730-R3 IS NO LONGER VALID.
  
 B) SELECTED ASSEMBLY R-20 CAN NOT BE USED BECAUSE THIS
 ASSEMBLY MAXIMUM DESIGN PRESSURE IS -45PSF. THIS DESIGN
 PRESSURE DOESN'T MEET THE DESIGN PRESSURES CALCULATED
 BY THE ENGINEER ON THE ECS REPORT SUBMITTED. IN
 ADDITION, THIS ASSEMBLY HAS AN ASTERISK AFTER THE
 DESIGN PRESSURE OF -45PSF. NOTE #10 OF THE FLORIDA
 PRODUCT APPROVAL FL16730-R4 (AND FL16730-R3) STATES
 THAT "FOR ASSEMBLIES MARKED WITH AN ASTERISK*, THE
 MAXIMUM DESIGN PRESSURE (MDP) LIMITATION LISTED SHALL
 BE APPLICABLE TO ALL ROOF PRESSURE ZONES (I.E., FIELD,
 PERIMETERS AND CORNERS). NEITHER RATIONAL ANALYSIS, NOR
 EXTRAPOLATION IS PERMITTED FOR ENHANCED ATTACHMENT AT
 ENHANCED PRESSURE ZONES (I.E., PERIMETERS, CORNERS AND
 EXTENDED CORNERS)."
  
 NOTES:
 (1) NEED TO SELECT AN ASSEMBLY THAT MEETS THE
 CALCULATED DESIGN PRESSURES OR THAT ALLOWS RAS 117
 CALCULATIONS (NAIL ENHANCING CALCULATIONS TO INCREASE
 THE DESIGN PRESSURES).
  
 (2) IF RAS 117 CALCULATIONS ARE REQUIRED, THEN THEY
 NEED TO BE SIGNED AND SEALED.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2015-06-26 Cont ID  
Sent By jgomez Date 2015-06-26 Time 15:55 Rev Time 0.00
Received By jgomez Date 2015-06-26 Time 12:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2015-06-24 Cont ID  
Sent By jgomez Date 2015-06-24 Time 17:15 Rev Time 0.00
Received By jgomez Date 2015-06-24 Time 10:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-06-12 Cont ID  
Sent By jgomez Date 2015-06-12 Time 15:48 Rev Time 0.00
Received By jgomez Date 2015-06-11 Time 08:17 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-06-02 Cont ID  
Sent By jgomez Date 2015-06-02 Time 17:13 Rev Time 0.00
Received By jgomez Date 2015-05-19 Time 09:33 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-04-17 Cont ID  
Sent By jgomez Date 2015-04-17 Time 11:57 Rev Time 0.00
Received By jgomez Date 2015-04-14 Time 12:46 Sent To  
Notes
***NONE***