Plan Review Details - Permit 15040310
Plan Review Stops For Permit 15040310
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-05-22 Cont ID  
Sent By JWITMER Date 2015-05-22 Time 07:50 Rev Time 0.00
Received By jwitmer Date 2015-05-22 Time 05:33 Sent To  
Notes
2015-05-22 07:50:03BUILDING PLAN REVIEW
 MECHANICAL PLAN REVIEW
 W. P. B. PERMIT: 15040310
 ADD: 111 S. SAPODILLA AVE.
 CONT: TURNER
 TEL: (786)229-4036
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: FRI. MAY 22/2015
 ACTION: PROVISO
  
 BUILDING / MECHANICAL APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES
  
 REVISION IS REQUIRED BEFORE THE 1ST INSPECTION. PROVIDE
 ANCHORING DETAILS FOR THE ROOF TOP FAN, TO CURB,
 PROVIDE CURB DETAILS, PROVIDE CURB ANCHORING TO THE
 STRUCTURAL ROOF DECK.
  
 RULE 9N-3.31(D).
 2010 FBC-B 1609.6.4.4.1 COMPONENTS AND CLADDING
 2010 FBC-M 301.12 WIND RESISTANCE
  
 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-04-22 Cont ID  
Sent By jwitmer Date 2015-04-22 Time 08:45 Rev Time  
Received By jwitmer Date 2015-04-22 Time 05:55 Sent To  
Notes
2015-04-22 07:13:59BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15040310
 ADD: 111 S. SAPODILLA AVE.
 CONT: TURNER
 TEL: (786)229-4036
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 IMPORTANT NOTICE: EFFECTIVE MARCH 30, 2015
 ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED
 ELECTRONICALLY
 UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS
 SUBMISSION OPTIONS ARE AS FOLLOWS:
 1 UPLOAD VIA THE PROJECT DOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL
 SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED
 NAMING CONVENTION FOR EACH DOCUMENT
 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER
 DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE
 REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT
 TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS
 ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES
 AVAILABLE.
  
 1ST REVIEW
 DATE: WED. APRIL 22/2015
 ACTION: DENIED
  
 1) SHEET S-1.0 THE WIND ROOF DIAGRAM SHOWS IN THE
 SOUTHEAST CORNER WIND ZONE # 3 AN ROOF TOP EXHAUST FAN.
 THE MIAMI-DADE NOA 13-0708.12 ACE ALUMINUM ROOF TOP FAN
 NEGATIVE PRESSURES ARE ONLY GOOD FOR -112 WHERE AS THE
 PRESSURES SHOWN IN VASD ARE -150 FOR ROOF ZONE # 3 FOR
 10 SQ. FT. AND LESS.
  
 2) SHEET S-2.0 DETAIL # 3 SHOWS STEEL L ANGLES
 REQUIRING WELDING. THE CITY WILL REQUIRE 3RD PARTY
 CERTIFICATION OF WELDS, THE ENGINEER OF RECORD CAN
 CERTIFY WELDS AT JOBSITE, PLEASE SUBMIT PAPERWORK FOR
 INSPECTION, NO FEE SUBMITTAL.
  
 3) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
 NOA: 13-1205.01 TUBULAR SKYLIGHT, POLYCARBONATE DOMED
 TUBULAR SKYLIGHT. EXPIRED 12/18/2014
 NOA: 13-0708.02 LOREN ACE ALUMINUM ROOFTOP FAN.
 NOA: 12-1113.24 JM PVC ROOF SYSTEMS OVER CONCRETE DECKS
  
 4) NOA: 12-1113.24 JM PVC ROOF SYSTEMS OVER CONCRETE
 DECKS DOES NOT IDENTIFY (CIRCLE) WHICH SUB-SYSTEM IS TO
 BE APPLIED, THE MAXIMUM DESIGN PRESSURES FOR THE
 SUB-SYSTEM ARE UNKNOWN, AS WELL AS LIMITATIONS 7 OR 9.
 MAY REQUIRE ENHANCED FASTENING BY A DESIGN
 PROFESSIONAL.
 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, THE
 CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND
 DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS,
 FASTENING REQUIREMENTS, FLASHING REQUIREMENTS AND WIND
 RESISTANCE RATING THAT ARE REQUIRED TO BE INSTALLED.
 PRODUCT EVALUATION AND INSTALLATION SHALL INDICATE
 COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR THE
 SPECIFIC SITE OR A STATEMENT BY AN ARCHITECT OR
 ENGINEER FOR THE SPECIFIC SITE MUST BE SUBMITTED WITH
 THE CONSTRUCTION DOCUMENTS.
  
 5) NOTE THE NOA: 13-0708.02 LOREN ACE ALUMINUM ROOFTOP
 FAN IS FOR THE FAN ONLY ,NOT THE CURB, PLEASE PROVIDE
 THE PRODUCT APPROVAL FOR THE ATTACHMENT OF THE CURB TO
 THE FRAMING MEMBERS ON THE ROOF SYSTEM. NEITHER SHEET
 S-1.0 OR S-2.0 SHOW THE ROOF FRAMING REQUIRED FOR THE
 ROOF TOP EXHAUST FAN AND CURB. FLORIDA DEPARTMENT OF
 COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(D) ROOFING PRODUCTS AND ASSEMBLIES ,CURBS, & ROOF
 TOP FANS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-04-23 Cont ID  
Sent By rlecky Date 2015-04-23 Time 13:15 Rev Time 0.00
Received By rlecky Date 2015-04-23 Time 13:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-05-22 Cont ID  
Sent By jwitmer Date 2015-05-22 Time 08:01 Rev Time 0.00
Received By jwitmer Date 2015-05-08 Time   Sent To  
Notes
2015-05-08 18:18:57C14

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2015-05-08 Time   Rev Time 0.00
Received By shill Date 2015-04-09 Time 14:20 Sent To  
Notes
2015-04-09 14:21:37****EXPEDITED****
 C14
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2015-05-22 Cont ID  
Sent By jwitmer Date 2015-05-22 Time 07:50 Rev Time 0.00
Received By jwitmer Date 2015-05-22 Time 07:50 Sent To  
Notes
2015-05-22 08:01:44BUILDING PLAN REVIEW
 MECHANICAL PLAN REVIEW
 W. P. B. PERMIT: 15040310
 ADD: 111 S. SAPODILLA AVE.
 CONT: TURNER
 TEL: (786)229-4036
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: FRI. MAY 22/2015
 ACTION: PROVISO
  
 BUILDING / MECHANICAL APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES
  
 REVISION IS REQUIRED BEFORE THE 1ST INSPECTION. PROVIDE
 ANCHORING DETAILS FOR THE ROOF TOP FAN, TO CURB,
 PROVIDE CURB DETAILS, PROVIDE CURB ANCHORING TO THE
 STRUCTURAL ROOF DECK.
  
 RULE 9N-3.31(D).
 2010 FBC-B 1609.6.4.4.1 COMPONENTS AND CLADDING
 2010 FBC-M 301.12 WIND RESISTANCE
  
 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-05-21 Cont ID  
Sent By HMOSER Date 2015-05-21 Time 15:15 Rev Time 0.00
Received By ccole Date 2015-04-09 Time 15:14 Sent To  
Notes
2015-05-21 16:19:102ND MECHANICAL REVIEW
  
 1) SHEET MP-101: THE PREVIOUSLY REQUESTED WIND LOAD TIE
 DOWN ENGINEERING FOR THE CONDENSER PIPING CURB (KEY
 NOTE #4), AND THE OUTSIDE AIR INTAKE CURB (KEY NOTE
 #10)
 HAS NOT BEEN PROVIDED. PLEASE COMPLY.
 2) SHEET A-200: KEY NOTE #6 CALLS OUT NEW EXHAUST FAN
 AND CURB, HOWEVER THIS ITEM IS NOT SHOWN ON SHEET
 MP-101.
 REVISE THE SHEET AND NOTES ACCORDINGLY, PROVIDE A CUT
 SHEET FOR THE FAN, AND WIND LOAD TIE DOWN ENGINEERING.
  
 CHRISTOPHER COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-04-25 Cont ID  
Sent By hmoser Date 2015-04-25 Time 09:11 Rev Time 0.00
Received By hmoser Date 2015-04-25 Time 08:10 Sent To  
Notes
2015-04-25 09:11:46PLAN DENIED
 1) PROVIDE ENGINEER DETAIL ON THE PLAN SHOWING
 ALL NEW CURB TIE DOWN TO ROOF AND EQUIPMENT TIE DOWN
 TO CURB. PER SECTION 301.12 WIND RESISTANCE 2010 FBC
 (M)
 2) NOTE #10 PROVIDE DUCT SIZE, AND ENGINEERING ON DUCT
 AND CURB PER SECTION 301.12 WIND RESISTANCE
 3) REFER TO SECTION 503.2.5.4 SHUTOFF DAMPER CONTROLS
 2010 FLORIDA ENERGY CODE.
 4) PROVIDE THE TYPE OF MATERIAL USED FOR CONDENSER
 WATER
 PIPING MUST MEAT TABLE 1202.4 AND 1202.5 ALSO PROVIDE
 ASTM
 LISTING ON PIPE
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-05-05 Cont ID  
Sent By tklarge Date 2015-05-05 Time 06:55 Rev Time 0.00
Received By tklarge Date 2015-05-05 Time 06:37 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2015-05-28 Cont ID  
Sent By aaponte Date 2015-05-28 Time 10:20 Rev Time 0.00
Received By ajones Date 2015-05-18 Time 11:12 Sent To  
Notes
2015-05-18 11:13:27PROVISO: ANY NEW MECHANICAL EQUIPMENT SHALL NOT EXCEED
 THE HEIGHT OF THE EXISTING PARAPET WALL OR MECHANICAL
 ENCLOSURE.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.