| 2015-04-25 14:30:08 | BUILDING PLAN REVIEW |
| | W. P. B. REVISION: 15040273 |
| | W. P. B. PERMIT: 12050519 |
| | ADD: 4748 FRED GLADSTONE DR. |
| | CONT: THE WEITZ CO. |
| | TEL: ( |
| | E-MAIL: |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: SUNDAY APRIL 26/ 2015 |
| | ACTION: DENIED |
| | |
| | 1) SHEETS 000-G1.02 & 018-E-A101 IN STAIRWELL # 1 BOTH |
| | INDICATE A NOTE PROVIDE 2 HOUR SHAFT AND A 2 HOUR |
| | ACCESS PANEL. PLEASE PROVIDE WHAT THIS (2) HOUR FIRE |
| | RATED ACCESS PANEL WILL BE USED FOR? PLEASE SEE THE |
| | ONLY ITEMS THAT ARE ALOUD IN THE EXIT STAIRWELL, |
| | ASSUMING THIS IS AN REQUIRED EXIT? 2010 FBC-B 1022.4 |
| | PENETRATIONS. PENETRATIONS INTO AND OPENINGS THROUGH AN |
| | EXIT ENCLOSURE ARE PROHIBITED EXCEPT FOR REQUIRED EXIT |
| | DOORS, EQUIPMENT AND DUCTWORK NECESSARY FOR INDEPENDENT |
| | VENTILATION OR PRESSURIZATION, SPRINKLER PIPING, |
| | STANDPIPES, ELECTRICAL RACEWAY FOR FIRE DEPARTMENT |
| | COMMUNICATION SYSTEMS AND ELECTRICAL RACEWAY SERVING |
| | THE EXIT ENCLOSURE AND TERMINATING AT A STEEL BOX NOT |
| | EXCEEDING 16 SQUARE INCHES (0.010 M2). SUCH |
| | PENETRATIONS SHALL BE PROTECTED IN ACCORDANCE WITH |
| | SECTION 713. THERE SHALL BE NO PENETRATIONS OR |
| | COMMUNICATION OPENINGS, WHETHER PROTECTED OR NOT, |
| | BETWEEN ADJACENT EXIT ENCLOSURES. |
| | |