| 2015-04-07 16:04:15 | BUILDING PLAN REVIEW |
| | W. P. B. REVISION: 15040185 |
| | W. P. B. PERMIT: 14050575 |
| | ADD: 951 HANK AARON DR. |
| | CONT: NUNNO BUILDERS |
| | TEL: (954)422-3593 |
| | E-MAIL: |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. APRIL 07/ 2015 |
| | ACTION: DENIED |
| | |
| | 1) THIS SUBMITTAL IS FOR GLAZING PRODUCT APPROVALS, |
| | STRUCTURAL CALCULATIONS AND SHOP DRAWINGS. BOTH THE |
| | STRUCTURAL WIND CALCS DO NOT PROVIDE THE WIND DESIGN |
| | FOR THE PROPOSED PRESSURES ON THE CALCULATIONS NOR THE |
| | SHOP DRAWINGS. THE PRESSURES APPEAR TO BE LOW. |
| | WIND DESIGN CRITERIA |
| | 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN- |
| | CHAPTER 6 OF ASCE 7-10. |
| | 1609.3 BASIC WIND SPEED FIGURE 1609.A-C |
| | 1609.3 WIND SPEED CONVERSION |
| | |
| | 1.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.3.1 & ASCE 7-10 |
| | |
| | 1.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10. |
| | |
| | 1.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.4 & ASCE 7-10 THE PLANS DO NOT |
| | INDICATE THE EXPOSURE NOR THE MEAN ROOF HEIGHT. |
| | |
| | 1.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * |
| | SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10. |
| | |
| | 1.5) COMPONENTS & CLADDING PRESSURES POSITIVE & |
| | NEGATIVE TABLE 1609.2(2). |
| | |
| | 2) THE DESIGNER OF RECORDS SHOP DRAWING OF REVIEW AND |
| | APPROVAL IS ONLY ON THE SHOP DRAWINGS, THEY ARE NOT ON |
| | EACH OF THE PRODUCT APPROVALS NOR IS THEIR STAMP OF |
| | REVIEWAND APPROVAL ON THE CALCULATIONS. 2010 FBC |
| | 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE |
| | REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |