Plan Review Details - Permit 15040163
Plan Review Stops For Permit 15040163
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-08-14 Cont ID  
Sent By jwitmer Date 2015-08-14 Time 16:37 Rev Time 0.00
Received By jwitmer Date 2015-08-14 Time 16:36 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-05-27 Cont ID  
Sent By jwitmer Date 2015-05-27 Time 12:02 Rev Time 0.00
Received By jwitmer Date 2015-05-27 Time 12:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-04-08 Cont ID  
Sent By jwitmer Date 2015-04-08 Time 07:02 Rev Time 0.00
Received By jwitmer Date 2015-04-08 Time 06:23 Sent To  
Notes
2015-04-08 07:08:39BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15040163
 ADD: 1610 PALM BEACH LAKES BLVD
 CONT: DOSDOVRIAN ENTERPRISES
 TEL: (561)844-2990
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE:
 ACTION: DENIED
  
 IMPORTANT NOTICE: EFFECTIVE MARCH 30, 2015
 ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED
 ELECTRONICALLY
 UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS
 SUBMISSION OPTIONS ARE AS FOLLOWS:
 1 UPLOAD VIA THE PROJECT DOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL
 SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED
 NAMING CONVENTION FOR EACH DOCUMENT
 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER
 DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE
 REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT
 TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS
 ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES
 AVAILABLE.
  
 1) PLEASE PROVIDE A OVERALL FLOOR PLAN OF WHERE THE
 JUMBO VIEWING SCREENS ARE GOING TO BE INSTALLED. THE
 1ST SHEET LIST PLATFORM PLAN AND ENTRY PLAN. SHEET A.02
 SHOWS SECTION A AND SECTION B, SECTION BSHOWS THE JUMBO
 VIEWING SCREEN BEING ADDED INFRONT OF THE GUARDRAIL,
 JUST TO THE LEFT IS 2 ELEVATIONS THAT SHOWS 4 PAIR OF
 ENTRY DOORS THAT DOES NOT APPEAR IN THE SECTION B CUT
 SECTION VIEW. THE ENTRY PLAN SHOWS THE JUMBO SCREEN
 WITHIN 10'-0" OF THE ENTRY DOORS. THE ASSEMBLY
 OCCUPANCY DORS SHOULD SWING OUT IF THIS IS THE CASE
 THIS SCREEN SHOULD BE ON THE OUTSIDE OF THE BUILDING
 PLEASE PROVIDE HOW MANY JUMBO SCREENS ARE BEING
 INSTALLED AND LOCATION. FOR EACH LOCATION IDENTIFY BY
 FRAMING TYPE ALSO, IT APPEARS THERE MAYBE (3) FRAMING
 TYPES AND MULTIPLE LOCATIONS THAT ARE NOT AS CLEAR.
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 2) PLANS INDICATE THE USE OF BOLTS, THE PLANS DO NOT
 INDICATE THAT THERE WILL BE ANY WELDING DONE, BASE
 PLATES TO COLUMNS? 107.2.1.3.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2015-08-14 Cont ID  
Sent By dhayes Date 2015-08-14 Time 12:41 Rev Time 0.00
Received By dhayes Date 2015-08-14 Time 12:41 Sent To  
Notes
2015-08-14 12:44:56THE PREVIOUS (4TH) OPEN ELECTRICAL STOP WAS LOCKED DUE
 TO A COMPUTER PROGRAM MALFUNCTION. THE ELECTRICAL
 REVIEW IS COMPLETE AND PASSED.

Review Stop E ELECTRICAL
Rev No 4 Status N Date 2015-08-19 Cont ID  
Sent By spalmer Date 2015-08-19 Time 16:13 Rev Time 0.00
Received By spalmer Date 2015-08-11 Time 13:38 Sent To  
Notes
2015-08-19 16:14:35PASSED BY DAVID HAYES ON 8/14/15
2015-08-11 14:26:408/11/2015
 PROJECT: A/V AT CONVENTION CENTER
 PERMIT#: 15040163
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 4TH ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1) FEEDER SCHEDULE IDENTIFICATION NUMBERS HAVE BEEN CUT
 OFF FROM THE REVISED SHEET.
  
 2) INDICATE THE SIZES OF THE DISCONNECTS AND OCPD ON
 THE PRIMARY AND SECONDARY SIDE OF EACH TRANSFORMER IN
 COMPLIANCE WITH NEC 450
  
 3) INDICATE THE SIZE AND TYPE OF ALL SPEAKER CABLING IN
 COMPLIANCE WITH THE EQUIPMEENT IT IS CONNECTED TO.
  
 4) CLEARLIY IDENTIFY ALL EQUIPMENT AND PANEL LOCATIONS
 ON THE FLOOR PLAN. INDICATE THE SIZE AND TYPE OF
 CONDUIT AND WIRE BETWEEN EACH PEICE OF EQUIPMENT. THERE
 ARE SEVERAL CONDUITS AN SHEET E.02 THAT ARE NOT
 IDENTIFIED.
  
 5)
  
 6)
  
 7)
  
 8) .
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2015-07-15 Cont ID  
Sent By dhayes Date 2015-07-15 Time 12:39 Rev Time 0.00
Received By dhayes Date 2015-07-15 Time 08:21 Sent To  
Notes
2015-07-15 10:16:187/15/2015
 PROJECT: AV UPGRADE AT CHRSTIAN CONVENTION CENTER 1610
 PALM BEACH LAKES BLVD
 PERMIT#: 15040163
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC,
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER ONE,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 3RD ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1) CLARIFY THE OVERALL SCOPE OF ELECTRICAL WORK. SHEET
 E.04 INDICATES TWO NEW 2000AMP SECTIONS OF SWITCHBOARD
 SECTIONS. THESE NEW SECTIONS APPEAR TO BE RESPONSIBLE
 FOR FEEDING PORTIONS OF THE NEW PANELS AND TRANSFORMERS
 PROPOSED TO BE INSTALLED AS A PART OF THE UPGRADE.
 1A) INDICATE ON AN ELECTRICAL FLOOR PLAN THE LOCATION
 OF THE 4000AMP SERVICE DISTRIBUTION SWITCHBOARD AS WELL
 AS ALL OTHER ASSOCIATED ELECTRICAL EQUIPMENT .
  
 2) ADDITIONAL DETAILED CLARIFICATION REQUIRED. CREATE
 AN ELECTRICAL PAGE TO INDICATE THE CIRCUITRY DIAGRAM
 FOR SHEET THE VIDEO WALLS DEPICTED ON PAGE A.08. WPB
 AMENDMENTS TO THE FBC 107.2.1
  
 3) INCLUDE THE REQUIRED WORKING ACCESS AND ILLUMINATION
 TO THE SPACE BEHIND THE VIDEO WALLS FOR SERVICING THE
 ELECTRICAL EQUIPMENT AS REQUIRED BY NEC 110.33(B) AND
 110.34(D)
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-06-04 Cont ID  
Sent By dhayes Date 2015-06-04 Time 17:11 Rev Time 0.00
Received By dhayes Date 2015-06-04 Time 16:43 Sent To  
Notes
2015-06-04 17:11:296/4/2015
 PROJECT: A/V AT CONVENTION CENTER
 PERMIT#: 15040163
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1) FEEDER SCHEDULE MARK 5 AND 6 CALLS FOR A 1" CONDUIT
 FOR FEEDERS TOO LARGE FOR A 1" CONDUIT. PLEASE REVISE
 ACCORDINGLY.
  
 2) PANEL VW2, CIRCUIT #2 INDICATES #10 WIRE CONNECTED
 TO A 40AMP OCPD . #10 CU WIRE IS NOT APPROVED FOR
 40AMPS.
  
 3) CABLES INSTALLED IN CABLE TRAY TO BE APPROVED FOR
 USE IN A CABLE TRAY AND BE LISTED AND IDENTIFIED FOR
 THIS USE.
  
 4) INDICATE THE SIZE OF THE TRANSFORMERS.
  
 5) PROVIDE MANUFACTURER LISTING INFORMATION FOR THE A/V
 EQUIPMENT.
  
 6) PANEL M5, CIRCUIT # 40/42 IS IDENTIFIED AS A 100AMP
 3POLE CIRCUIT CONNECTED TO #6 WIRE FOR LC2. FIRST OF
 ALL IS IT A 3PHASE OR SINGLE PHASE CIRCUIT? THE CLARIFY
 THE CIRCUIT SIZE AND WIRE CONNECTED TO IT. #6CU WIRE IS
 NOT APPROVED FOR 100AMPS.
  
 7) THERE IS A SIMILAR ISSUE IN PANEL EM8 ON CIRCUIT 2
 CALLS FOR THE USE OF A 100AMP OCPD WITH #6 WIRE. #6CU
 WIRE IS NOT APPROVED FOR 100AMPS.
  
 8) CLEARLIY IDENTIFY ALL EQUIPMENT AND PANEL LOCATIONS
 ON THE FLOOR PLAN.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-04-07 Cont ID  
Sent By dhayes Date 2015-04-07 Time 14:52 Rev Time 0.00
Received By dhayes Date 2015-04-07 Time 14:52 Sent To  
Notes
2015-04-07 14:59:58NO ELECTRICAL PLANS HAVE BEEN INCLUDED IN THIS
 SUBMITTAL PACKAGE. AN ELECTRICAL APPLICATION WITH THE
 DESCRIPTION HIGH AND LOW VOLTAGE WIRING FOR NEW SOUND
 BOOTH AND SPEAKERS. PROVIDE COMPLETE ELECTRICAL PLANS
 REQUIRED TO INDICATE COMPLIANCE WITH THE FBC AND THE
 NEC
 PROVIDE A FLOOR PLAN INDICATING LOCATIONS FOR THE
 ELECTRICAL SERVICE, ELECTRICAL PANEL(S) SOUND BOOTH AND
 SPEAKERS. LWPB AMENDMENTS TO FBC 107.3.2, NEC 110.26
 PROVIDE A PANEL SCHEDULE INDICATING ALL NEW CIRCUITS
 FOR NEW SOUND BOOTH. NEC 408.4
 PROVIDE A LOAD CALCULATION THAT INCLUDES ALL EXISTING
 PLUS ADDITIONAL BRANCH CIRCUITS REQUIRED FOR NEW SOUND
 BOOTH EQUIPMENT.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2015-08-14 Cont ID  
Sent By dhayes Date 2015-08-14 Time 16:37 Rev Time 0.00
Received By jwitmer Date 2015-08-06 Time 16:39 Sent To  
Notes
2015-08-06 16:39:52RESUB ROUTED TO DHAYES

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-07-15 Cont ID  
Sent By dhayes Date 2015-07-15 Time 12:39 Rev Time 0.00
Received By dhayes Date 2015-07-10 Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-06-04 Cont ID  
Sent By dhayes Date 2015-06-04 Time 17:11 Rev Time 0.00
Received By dhayes Date 2015-05-22 Time   Sent To  
Notes
2015-05-22 18:21:32SENT TO J WITMER

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-04-13 Cont ID  
Sent By   Date 2015-04-13 Time   Rev Time  
Received By   Date 2015-04-06 Time   Sent To  
Notes
2015-04-06 15:39:09B-08.

Review Stop Z ZONING
Rev No 1 Status P Date 2015-04-13 Cont ID  
Sent By ajones Date 2015-04-13 Time 17:17 Rev Time 0.00
Received By ajones Date 2015-04-13 Time 17:17 Sent To  
Notes
***NONE***