Plan Review Details - Permit 15040124
Plan Review Stops For Permit 15040124
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-05-05 Cont ID  
Sent By dhayes Date 2015-05-05 Time 10:25 Rev Time 0.00
Received By dhayes Date 2015-05-05 Time 07:46 Sent To  
Notes
2015-05-05 10:25:42APPROVED WITH EXCEPTION.
 THE PLANS HAVE BEEN APPROVED PROVISIONALLY. THE
 FOLLOWING DEFICIENCIES SHALL BE VERIFIED TO BE CODE
 COMPLIANT BY THE ELECTRICAL INSPECTOR ON SITE.
 FAILURE TO CORRECT THE LISTED DEFICIENCIES PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S).
  
 1) THE FAULT CURRENT CALCULATION ON SHEET E-0 INDICATES
 A 22,000AMP AIC MIN RATING IS REQUIRED AT THE SERVICE
 EQUIPMENT. HOWEVER THE PANELS INDICATE A MINIMUM OF
 ONLY10,000AMPS.
  
 2) THE LOAD SUMARY IS IN CONFLICT WITH THE TOTAL
 CONNECTED LOADS INDICATED IN THE PANEL SCHEDULES. LOADS
 FOR NEW CIRCUITS OR EXTENDED CIRCUITS IN PREVIOUSLY
 WIRED DWELLING UNITS SHALL BE CALCULATED IN ACCORDANCE
 WITH 220.12 OR 220.14, NEC 220.16(2)
  
 3) VERIFY THE WORKING CLEARANCES FOR ELECTRICAL PNAEL
 "A" ARE IN COMPLIANCE WITH THE NEC 110.26
  
 4) VERIFY COMPLIANCE WITH THE LUMINAIRES IN THE CLOTHES
 CLOSETS. THE NEC STATES LUMINAIRES SHALL BE INSTALLED
 IN ACCORDANCE WITH THE PROVISIONS OF THE NEC 410.16(A)
 AND (B).
  
 5) VERIFY THE FLOOR BOXES ARE DESIGNED SPECIFICALLY FOR
 USE IN THIS APPLICATION. "BOXES LISTED SPECIFICALLY FOR
 THIS APPLICATION SHALL BE USED FOR RECEPTACLES LOCATED
 IN THE FLOOR." NEC 314.27(C)
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-04-27 Cont ID  
Sent By dhayes Date 2015-04-27 Time 09:36 Rev Time 0.00
Received By dhayes Date 2015-04-27 Time 09:23 Sent To  
Notes
2015-04-27 09:45:214/27/2015
 PROJECT: 312 BARCELONA
 PERMIT#: 15040124
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1STELECTRICAL PLAN REVIEW OF REVISION #15040124
 ACTION: DENIED
  
 DUPLICATE COMMENTS:
  
 1) PROVIDE A REVISED FLOOR PLAN INDICATING THE
 ELECTRICAL SERVICE AND EACH OF THE PANEL LOCATIONS. THE
 RISER INDICATES PANEL "B" IS A PART OF THE SERVICE
 ENTRANCE SWITCHGEAR HOWEVER THE PANEL SCHEDULE FOR
 PANEL "B" INDICATES THE LOCATION BEING IN THE LAUNDRY
 ROOM. PLEASE CLARIFY THIS. WPB AMENDMENTS TO FBC
 107.3.2
  
 2) FULL SIZE FEEDERS ARE REQUIRED TO FEED PANELS A AND
 B. NEC 210.15(B)(6)
 "FOR APPLICATION OF THIS SECTION, THE MAIN POWER FEEDER
 SHALL BE THE FEEDER BETWEEN THE MAIN DISCONNECT AND THE
 PANELBOARD THAT SUPPLIES, EITHER BY BRANCH CIRCUITS OR
 BY FEEDERS, OR BOTH, ALL LOADS THAT ARE PART OR
 ASSOCIATED WITH THE DWELLING UNIT."
  
 3) PROVIDE A PANEL SCHEDULE FOR EACH OF THE PANELS ON
 THE RISER DIAGRAM. NEC 215.5
  
 4) PROVIDE A LOAD CALCULATION FOR THE SERVICE. NEC
 220.16
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-04-13 Cont ID  
Sent By dhayes Date 2015-04-13 Time 12:50 Rev Time 0.00
Received By dhayes Date 2015-04-13 Time 12:13 Sent To  
Notes
2015-04-13 12:50:014/13/2015
 PROJECT: 312 BARCELONA
 PERMIT#: 15040124
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1STELECTRICAL PLAN REVIEW OF REVISION #15040124
 ACTION: DENIED
  
 1) REVISE RISER DIAGRAM FOR CLARIFICATION. IT APPEARS
 FROM THE ONLY TWO PANEL SCHEDULES PROVIDED THAT THERE
 ARE ONLY 2 PANELS INSTALLED. HOWEVER THE RISER
 INDICATES THE USE OF A 400A COMBINATION METER/MAIN WITH
 PANEL "B" INCLUDED WITH A 400AMP RATED BUSS AND TWO
 200A MAINS? ONE FEEDING PANEL "A" AND THE OTHER FEEDING
 PANEL "B1". PLEASE CLARIFY IS THERE A B1? OR ONLY A AND
 B EACH FED FROM A 200AMP MAIN?
  
 2) IF THERE IS A PANEL B1 PROVIDE THE FEEDER SIZE, A
 PANEL SCHEDULE AND THE LOCATION. THERE IS A SUB-FEED
 LUG KIT INDICATED IN PANEL SCHEDULE "A" IS THIS
 SUPPOSED TO FEED PANEL "A1"?
  
 3) PROVIDE A REVISED FLOOR PLAN INDICATING THE
 ELECTRICAL SERVICE AND EACH OF THE PANEL LOCATIONS. THE
 RISER INDICATES PANEL "B" IS A PART OF THE SERVICE
 ENTRANCE SWITCHGEAR HOWEVER THE PANEL SCHEDULE FOR
 PANEL "B" INDICATES THE LOCATION BEING IN THE LAUNDRY
 ROOM. PLEASE CLARIFY THESE
  
 4) FULL SIZE FEEDERS ARE REQUIRED TO FEED PANELS A AND
 B. NEC 210.15(B)(6)
 "FOR APPLICATION OF THIS SECTION, THE MAIN POWER FEEDER
 SHALL BE THE FEEDER BETWEEN THE MAIN DISCONNECT AND THE
 PANELBOARD THAT SUPPLIES, EITHER BY BRANCH CIRCUITS OR
 BY FEEDERS, OR BOTH, ALL LOADS THAT ARE PART OR
 ASSOCIATED WITH THE DWELLING UNIT."
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-05-05 Cont ID  
Sent By dhayes Date 2015-05-05 Time 10:25 Rev Time 0.00
Received By dhayes Date   Time   Sent To  
Notes
2015-05-01 16:10:50SENT TO D HAYES

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-04-27 Cont ID  
Sent By dhayes Date 2015-04-27 Time 09:45 Rev Time 0.00
Received By dhayes Date 2015-04-23 Time 12:34 Sent To  
Notes
2015-04-23 12:34:32TO DAH DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-04-13 Cont ID  
Sent By dhayes Date 2015-04-13 Time 12:50 Rev Time 0.00
Received By dhayes Date 2015-04-03 Time 08:14 Sent To  
Notes
2015-04-04 08:14:48SENT TO D HAYES


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved