| 2015-04-13 12:50:01 | 4/13/2015 |
| | PROJECT: 312 BARCELONA |
| | PERMIT#: 15040124 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1STELECTRICAL PLAN REVIEW OF REVISION #15040124 |
| | ACTION: DENIED |
| | |
| | 1) REVISE RISER DIAGRAM FOR CLARIFICATION. IT APPEARS |
| | FROM THE ONLY TWO PANEL SCHEDULES PROVIDED THAT THERE |
| | ARE ONLY 2 PANELS INSTALLED. HOWEVER THE RISER |
| | INDICATES THE USE OF A 400A COMBINATION METER/MAIN WITH |
| | PANEL "B" INCLUDED WITH A 400AMP RATED BUSS AND TWO |
| | 200A MAINS? ONE FEEDING PANEL "A" AND THE OTHER FEEDING |
| | PANEL "B1". PLEASE CLARIFY IS THERE A B1? OR ONLY A AND |
| | B EACH FED FROM A 200AMP MAIN? |
| | |
| | 2) IF THERE IS A PANEL B1 PROVIDE THE FEEDER SIZE, A |
| | PANEL SCHEDULE AND THE LOCATION. THERE IS A SUB-FEED |
| | LUG KIT INDICATED IN PANEL SCHEDULE "A" IS THIS |
| | SUPPOSED TO FEED PANEL "A1"? |
| | |
| | 3) PROVIDE A REVISED FLOOR PLAN INDICATING THE |
| | ELECTRICAL SERVICE AND EACH OF THE PANEL LOCATIONS. THE |
| | RISER INDICATES PANEL "B" IS A PART OF THE SERVICE |
| | ENTRANCE SWITCHGEAR HOWEVER THE PANEL SCHEDULE FOR |
| | PANEL "B" INDICATES THE LOCATION BEING IN THE LAUNDRY |
| | ROOM. PLEASE CLARIFY THESE |
| | |
| | 4) FULL SIZE FEEDERS ARE REQUIRED TO FEED PANELS A AND |
| | B. NEC 210.15(B)(6) |
| | "FOR APPLICATION OF THIS SECTION, THE MAIN POWER FEEDER |
| | SHALL BE THE FEEDER BETWEEN THE MAIN DISCONNECT AND THE |
| | PANELBOARD THAT SUPPLIES, EITHER BY BRANCH CIRCUITS OR |
| | BY FEEDERS, OR BOTH, ALL LOADS THAT ARE PART OR |
| | ASSOCIATED WITH THE DWELLING UNIT." |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |