Plan Review Details - Permit 15040093
Plan Review Stops For Permit 15040093
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-06-17 Cont ID  
Sent By skennedy Date 2015-06-17 Time 14:59 Rev Time 0.00
Received By skennedy Date 2015-06-17 Time 14:59 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-05-04 Cont ID  
Sent By skennedy Date 2015-05-04 Time 09:54 Rev Time 0.00
Received By skennedy Date 2015-05-04 Time 09:54 Sent To  
Notes
2015-05-04 10:01:391ST REVIEW FBC 2010
  
 FBC 107 MINIMUM PLAN SUBMITTAL CRITERIA:
  
 PROVIDE ENERGY FORM 400D OR 402 UNLESS THE HOME IS
 HISTORIC DESIGNATED.
  
 PROVIDE WALL FRAMING AND FINISH DETAILS FOR WINDOW
 MODIFICATIONS REMOVAL.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY
 FAC RULE 9N-3 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. SPECIFICALLY, PROVIDE WINDOW, AND
 DOOR SUBMITTALS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-05-04 Cont ID  
Sent By skennedy Date 2015-05-04 Time 10:01 Rev Time 0.00
Received By skennedy Date 2015-05-04 Time 10:01 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2015-05-20 Cont ID  
Sent By fmittner Date 2015-05-20 Time 15:25 Rev Time 0.00
Received By fmittner Date 2015-05-20 Time 15:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-06-17 Cont ID  
Sent By skennedy Date 2015-06-17 Time 14:59 Rev Time 0.00
Received By skennedy Date 2015-05-28 Time 11:12 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-05-20 Cont ID  
Sent By lmarchan Date 2015-05-20 Time 15:33 Rev Time 0.00
Received By lmarchan Date 2015-04-02 Time 16:41 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2015-06-17 Cont ID  
Sent By skennedy Date 2015-06-17 Time 14:59 Rev Time 0.00
Received By skennedy Date 2015-06-17 Time 14:59 Sent To  
Notes
2015-06-17 14:59:51BY SEPARATE SUBMITTAL.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-05-04 Cont ID  
Sent By skennedy Date 2015-05-04 Time 09:48 Rev Time 0.00
Received By skennedy Date 2015-05-04 Time 09:48 Sent To  
Notes
2015-05-04 09:53:591ST REVIEW: FBC 2010
  
 FBC 107, MINIMUM PLAN REVIEW SUBMITTAL CRITERIA.
  
 PROVIDE THE AHRI FOR THE NEW MECHANICAL SYSTEM. PROVIDE
 ENERGY FORM 400D OR 402 UNLESS THE HOME IS HISTORIC
 DESIGNATED.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-05-04 Cont ID  
Sent By skennedy Date 2015-05-04 Time 09:47 Rev Time 0.00
Received By skennedy Date 2015-05-04 Time 09:47 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2015-06-17 Cont ID  
Sent By skennedy Date 2015-06-17 Time 14:59 Rev Time 0.00
Received By skennedy Date 2015-06-17 Time 14:59 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2015-05-04 Cont ID  
Sent By skennedy Date 2015-05-04 Time 09:47 Rev Time 0.00
Received By skennedy Date 2015-05-04 Time 09:47 Sent To  
Notes
2015-05-04 09:48:06GOOD SO FAR, WILL NEED TO CHECK UPON RE-SUB,

Review Stop Z ZONING
Rev No 1 Status P Date 2015-05-20 Cont ID  
Sent By sgraham Date 2015-05-20 Time 15:25 Rev Time 0.00
Received By fmittner Date 2015-05-20 Time 15:25 Sent To  
Notes
***NONE***