Plan Review Details - Permit 15040052
Plan Review Stops For Permit 15040052
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-04-07 Cont ID  
Sent By rmcdouga Date 2015-04-07 Time 16:47 Rev Time 0.00
Received By rmcdouga Date 2015-04-07 Time 16:47 Sent To  
Notes
2015-04-07 17:08:36PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PROJECT HAS A 25' MRH, A 5/12 SLOPED ROOF AND IS
 LOCATED IN EXPOSURE C IN A 170 MPH VULT WIND ZONE. THE
 REQUIRED UPLIFT MOMENT FOR THE ROOF TILE (FIELD) IS
 35.9 FT-LB F AND THE ATTACHMENT SPECIFIED IN THE
 PRODUCT APPROVAL FOR THE 'S' TILE (NOA NO. 12-0210.01)
 HAS AN ATTACHMENT RESISTANCE OF 28.5 FT-LB F.