| 2015-05-01 06:14:23 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15031368 |
| | ADD: 625 N. FLAGLER DR. # 700 |
| | CONT: CHANDLIER CONSTRUCTION |
| | TEL: ( 561-791-6934 |
| | E-MAIL: |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE:FRI. MAY 01/ 2015 |
| | ACTION: DENIED |
| | |
| | NOTICE PLANS WILL NOT BE APPROVED WITH VOIDED SHEETS |
| | INSERTED INTO THE PLANS. WHEN RESUBMITTING PLANS PLEASE |
| | INDICATE THE REVISION & REMOVE ANY VOIDED SHEETS & |
| | REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH A |
| | DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE SHEET |
| | OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | |
| | 1) 2ND REQUEST. THE COVERSHEET A-0.1 LIST THIS PROJECT |
| | AS A BUSINESS OCCUPANCY, THAT IT IS NOT A MIXED USE |
| | OCCUPANCY. THE SHEET DOES NOT HAVE THE OCCUPANCY |
| | SEPARATION CHECKED OR THE EXCEPTIONC CHECKED EITHER. |
| | SHEET A-2.1 SHOWS THE TENANTCY AS A SINGLE TENANT FULL |
| | FLOOR BUILD-OUT. THE FLOOR PLATE APPROXIMATELY 12,992 |
| | SQ. FT. OF BUSINESS OCCUPANCY. THE ROOMS NUMBERS |
| | IDENTIFIED AS 704,708,710 & 720 ARE ALL CONSIDERED A |
| | ASSEMBLY USAGE NOT BUSINESS. WHEN THE SQUARE FOOT AREAS |
| | ARE TOTALED TOGETHER(1,927 SQ. FT.) THEY ARE OVER THE |
| | 10 % OF THE FLOOR PLATE AND THE FLOOR PLATE BECOMES A |
| | MIXED USE OCCUAPANCY. |
| | |
| | 2010 FBC-B 508.2.1 AREA LIMITATIONS. AGGREGATE |
| | ACCESSORY OCCUPANCIES SHALL NOT OCCUPY MORE THAN 10 |
| | PERCENT OF THE BUILDING AREA OF THE STORY IN WHICH THEY |
| | ARE LOCATED AND SHALL NOT EXCEED THE TABULAR VALUES IN |
| | TABLE 503, WITHOUT BUILDING AREA INCREASES IN |
| | ACCORDANCE WITH SECTION 506 FOR SUCH ACCESSORY |
| | OCCUPANCIES. |
| | |
| | THE DESIGNER OF RECORD WILL NEED TO INDICATE THE DESIGN |
| | REQUIREMENTS AS EITHER COMPLYING WITH: |
| | FBC-B 508.3 NONSEPARATED OCCUPANCIES. BUILDINGS OR |
| | PORTIONS OF BUILDINGS THAT COMPLY WITH THE PROVISIONS |
| | OF THIS SECTION SHALL BE CONSIDERED AS NONSEPARATED |
| | OCCUPANCIES. |
| | OR |
| | FBC-B 508.4 SEPARATED OCCUPANCIES. BUILDINGS OR |
| | PORTIONS OF BUILDINGS THAT COMPLY WITH THE PROVISIONS |
| | OF THIS SECTION SHALL BE CONSIDERED AS SEPARATED |
| | OCCUPANCIES. |
| | ------------------------------------------------------- |
| | ------------------------------------------------------- |
| | ------------------------------------------------------- |
| | ------------------------------------------------------- |
| | BUILDING OFFICIALS ASSOCIATION OF FLORIDA INFORMAL |
| | INTERPRETATION REPORT NUMBER 6506 |
| | DATE: THU JUN 3 2010 |
| | REPORT: 6506 |
| | CODE: BUILDING CODE YEAR: 2007 |
| | SECTION: 508.3.1 |
| | QUESTION: |
| | IS IT THE INTENT OF FLORIDA BUILDING CODE - BUILDING |
| | SECTION 508.3.1, EXCEPTION 1, TO NOT REQUIRE FIRE |
| | SEPARATION BETWEEN THE |
| | PRIMARY OCCUPANCY AND MULTIPLE ACCESSORY OCCUPANCIES, |
| | WHEN EACH ACCESSORY OCCUPANCY IS LESS THAN 750 SQ. FEET |
| | EACH OR |
| | ONLY WHEN THE TOTAL OF ALL ACCESSORY OCCUPANCIES IS |
| | LESS THAN 750 SQ. FEET IN AREA? |
| | COMMENT: |
| | AN EXAMPLE WOULD BE A BUSINESS OCCUPANCY WITH ONE |
| | ACCESSORY AREA OF 700SF FOR GATHERINGS AND MEETINGS AND |
| | A SECOND |
| | ACCESSORY AREA OF 650SF FOR FITNESS AND WORKOUT. IS THE |
| | EXCEPTION LIMITATION OF 750 S.F. MAX APPLIED TO EACH |
| | ACCESSORY AREA, IN |
| | WHICH CASE THIS BUILDING WOULD COMPLY, OR TO THE |
| | COMBINED TOTAL OF THE TWO ACCESSORY AREAS, IN WHICH |
| | CASE IT WOULD NOT? |
| | ANSWER: |
| | NO. CONSIDERING BOTH SPACES TO BE ASSEMBLY USES LOCATED |
| | ON THE SAME FLOOR, THE EXCEPTION TO FLORIDA BUILDING |
| | CODE - BUILDING |
| | SECTION 508.3.1 WOULD NOT REQUIRE SEPARATION OF EITHER |
| | SPACE. HOWEVER, THE SECTION TO WHICH THE EXCEPTION |
| | RELATES WOULD LIMIT |
| | THE AGGREGATE ACCESSORY OCCUPANCIES TO 10% OF THE AREA |
| | OF THE FLOOR ON WHICH THEY ARE LOCATED. IF THE AREA OF |
| | TWO COMBINED |
| | ASSEMBLY USES EXCEEDED 10%, THEN AT LEAST ONE OF THE |
| | ASSEMBLY USES WOULD REQUIRE FIRE RESISTANT RATED |
| | SEPARATION OF 2 HOURS IN |
| | A NON-SPRINKLED BUILDING AND 1 HOUR IN A BUILDING |
| | SPRINKLED THROUGHOUT. |
| | COMMENTARY: |
| | NONE. |
| | NOTICE: |
| | THE BUILDING OFFICIALS ASSOCIATION OF FLORIDA, IN |
| | COOPERATION WITH THE FLORIDA BUILDING COMMISSION, THE |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, ICC, |
| | AND INDUSTRY AND PROFESSIONAL EXPERTS OFFER THIS |
| | INTERPRETATION OF THE FLORIDA BUILDING CODE IN THE |
| | INTEREST OF CONSISTENCY IN THEIR APPLICATION STATEWIDE. |
| | THIS INTERPRETATION IS INFORMAL, NON-BINDING AND |
| | SUBJECT TO ACCEPTANCE AND APPROVAL BY THE LOCAL |
| | BUILDING OFFICIAL. |
| | ------------------------------------------------------- |
| | ------------------------------------------------------- |
| | ------------------------------------------------------- |
| | --------------------------------------------- |
| | |
| | 2) COMPLIED. SHEET A2.2 SHOWS THE INSTALATION OF MARBLE |
| | AND TILE FLOORING. THE PLANS DO NOT INDICATE IF THERE |
| | IS A INTENT TO INSTALL A CRACK ISOLATION MEMBRANE |
| | BEFORE THE INSTALATION OF EITHER MARBLE OR TILE. IF SO |
| | THE CRACK ISOLATION MEMBRANE INSULATION WILL NEED TO |
| | COMPLY WITH FLAME SPREAD- FBC-B 2010 603.1.2 EXCEPTION |
| | 2. INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND |
| | SOLID DECKING WITHOUT INTERVENING AIRSPACE SHALL BE |
| | ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN |
| | 200. PLEASE PROVIDE TESTING REPORTS IN COMPLIANCE WITH |
| | SECTION 2010 FBC-B 603.1.2 EXCEPTION # 2, FLAMESPREAD. |
| | |
| | 3) 2ND REQUEST. SHEET A-2-1 THE CONFERENCE ROOM # 720, |
| | 1927 SQ. FT./ 15= 46 OCCUPANTS. SHEET A-3.1 THE DOOR |
| | SCHEDULE LIST THIS DOOR IDENTIED AS DOOR D4 AND A |
| | ALTERNATE SLIDING DOOR DESIGN. THE 2010 FBC-B 1008.1.2 |
| | DOES NOT ALLOW FOR SLIDDING DOORS AS A PART OF A MEANS |
| | OF EGRESS WHEN THE OCCUPANT LOAD IS GREATER THAN 10. |
| | |
| | THE USE OF THE WORDS ALTERNATE AND OR CAN NOT BE USED, |
| | INFORMATION ON PLANS HAS TO BE SPECIFIC TO THE |
| | TECHNICAL CODES. 2010 WEST PALM BEACH AMENDMENTS TO THE |
| | FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION,107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. SUCH DRAWINGS AND SPECIFICATIONS SHALL |
| | CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, |
| | AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS |
| | ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH |
| | INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES |
| | SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE |
| | TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE |
| | FOR SPECIFIC INFORMATION. |
| | |
| | 4-5) COMPLIED> |
| | |
| | 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |