Plan Review Details - Permit 15031318
Plan Review Stops For Permit 15031318
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-05-30 Cont ID  
Sent By jgomez Date 2015-05-30 Time 12:48 Rev Time 0.00
Received By jgomez Date 2015-05-30 Time 12:48 Sent To  
Notes
2015-05-30 12:49:28BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- NEED TO SPECIFY CARBON MONOXIDE ALARMS WITHIN 10
 FEET OF EACH SLEEPING ROOM AS REQUIRED BY SEC. R315 OF
 2010 FBC-RESIDENTIAL. NOTE: THERE IS A CARBON MONOXIDE
 ALARM SPECIFIED IN THE NEW KITCHEN, BUT THIS IS NOT
 WHAT IT WAS REQUESTED.
  
 2- ENERGY CALCULATIONS ARE TAKING THE CROSS VENTILATION
 CREDIT. PLANS TO PROVIDE COMPLETE INFORMATION SHOWING
 COMPLIANCE WITH ALL THE REQUIREMENTS OF SEC. 405.6.4 OF
 2010 FBC-ENERGY CONSERVATION.
 ENERGY CALCULATIONS WERE NOT REVISED AS PER ARCHITECT'S
 RESPONSE LETTER STATED.
  
 3- PROVIDE COMPLETE REVISED TRUSS PACKAGE TO BUILDING
 INSPECTOR AT TIME OF FRAMING INSPECTION.
  
 NOTE: REVISION FEES WILL APPLY AFTER PERMIT IS ISSUED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-04-30 Cont ID  
Sent By jgomez Date 2015-04-30 Time 09:43 Rev Time 0.00
Received By jgomez Date 2015-04-30 Time 09:29 Sent To  
Notes
2015-04-30 09:50:55RESIDENTIAL (R3) ADDITION/ALTERATION, BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.
  
 2- DESIGNER OF RECORD TO PROVIDE ROOF FRAMING PLAN.
 SEC. 107.3.5.3(50 CITY AMENDMENTS. NOTE: PLAN SUBMITTED
 IS A TRAY LAYOUT ONLY NOT A DESIGN OF THE ROOF FRAMING
 SYSTEM. THE ROOF FRAMING SYSTEM IS DESIGNED BY THE
 DESIGNER OF RECORD.
  
 3- NEED TO SPECIFY CARBON MONOXIDE ALARMS WITHIN 10
 FEET OF EACH SLEEPING ROOM AS REQUIRED BY SEC. R315 OF
 2010 FBC-RESIDENTIAL.
  
 4- DESIGNER OF RECORD TO REVIEW GEOTECHNICAL
 ENGINEERING EVALUATION FOR FOOTING SIZE
 RECOMMENDATIONS. SIZE OF FOOTINGS SPECIFIED BY THE
 DESIGNER OF RECORD ARE SMALLER ON ONE AREA. DESIGNER OF
 RECORD TO ACKNOWLEDGE REVIEW OF THE RECOMMENDATIONS AND
 ADDRESS ISSUE. SEC. 107.2.1.3 CITY AMENDMENTS.
  
 5- TRUSS PACKAGE:
 A) ENGINEER NEEDS TO SIGN AND SEAL EACH TRUSS SHEET OR
 SIGN AND SEAL COMPLYING WITH ALL THE REQUIREMENTS OF
 SEC. 61G15-31.003 F.A.C. NOTE: INFORMATION SUBMITTED
 DOESN'T HAVE EVEN THE NAME OF THE TRUSS ENGINEER. NOTE:
 TRUSS PACKAGE MAY NOT NEED TO BE SUBMITTED NOW. IT MAY
 BE RENDERED TO THE BUILDING INSPECTOR AT TIME OF
 FRAMING INSPECTION.
  
 B) DESIGNER OF RECORD TO APPROVE TRUSS PACKAGE PRIOR TO
 SUBMITTAL.
  
 6- ENERGY CALCULATIONS ARE TAKING THE CROSS VENTILATION
 CREDIT. PLANS TO PROVIDE COMPLETE INFORMATION SHOWING
 COMPLIANCE WITH ALL THE REQUIREMENTS OF SEC. 405.6.4 OF
 2010 FBC-ENERGY CONSERVATION.
  
 7- NEW ADDITION SHOWS A NEW KITCHEN. CLARIFY WHAT'S
 HAPPENING WITH THE EXISTING KITCHEN. THERE IS NOT WORK
 SHOWN ON THE EXISTING KITCHEN. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 8- A) INFORMATION ON PLANS AND ENERGY CALCULATIONS NEED
 TO MATCH. COORDINATE AS REQUIRED. FOR EXAMPLE CHECK
 INSULATION IN CEILINGS AND WALLS (EXTERIOR AND
 ADJACENT). SEC. 103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION.
 NOTE: COORDINATE WITH ICYNENE ESR REPORT AND ICYNENE
 MANUFACTURER TECHNICAL INFORMATION SUBMITTED REGARDING
 R-VALUE AND ICYNENE THICKNESS.
  
 9- PROVIDE COPY OF CURRENT ICYNENE INSULATION ICC
 EVALUATION REPORT. ESR REPORT EXPIRED ON FEB 2013. SEC.
 103.2.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 10- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTORS OVERHEAD AND PROFIT AND ALL DESIGN
 PROFESSIONAL FEES. VALUATION WAS UPDATED TO $139,800.
 THE PERMIT FEE BALANCE IS $2943.92.
  
 11- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9N-3 FOR:
 A) GARAGE DOOR SIZE AS SPECIFIED ON PLANS. PRODUCT
 APPROVAL SUBMITTED IS FOR 16 FEET WIDE DOORS. THERE IS
 A SEPARATE PRODUCT APPROVAL FOR SIZE SHOWN ON PLANS.
  
 B) WINDOW MULLIONS AS SHOWN ON PLANS. AND SPECIFY
 MULLION SIZE.
  
 12- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1
 CITY AMENDMENTS.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS...
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-05-27 Cont ID  
Sent By dhayes Date 2015-05-27 Time 13:04 Rev Time 0.00
Received By dhayes Date 2015-05-27 Time 12:49 Sent To  
Notes
2015-05-27 12:50:285/27/2015
 PROJECT: SNED ADDITION
 PERMIT#: 15031318
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 ELECTRICAL PLAN REVIEW
 ACTION: APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN
 APPROVED PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED
 INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION
 FEE(S).
  
 1) SMOKE DETECTORS TO BE INSTALLED IN ACCORDANCE WITH
 THE FBC-R 314, AND 315 THROUGHOUT THE DWELLING UNIT,
 NOT JUST THE RENOVATION. THE LOCATIONS INDICATED ON THE
 PLAN FOR THE INSTALLATION OF SMOKE DETECTORS ARE NOT
 REQUIRED ACCORDING TO THE FBC-R 314, 315. PLEASE REFER
 TO THE PREVIOUS REVIEW COMMENT:
 1A) INDICATE OR VERIFY THAT ALL REQUIRED SMOKE
 DETECTORS ARE EXISTING OR PROPOSED TO BE INSTALLED.
 THERE IS A NOTE ON THE PLAN THAT SAY THERE SHALL BE
 SMOKE DETECTORS OUTSIDE OF SLEEPING AREAS. THIS IS ONLY
 PARTLY COMPLIANT. PLEASE READ THE FBC-R 314 AND 315
 WHICH STATES, IN PART, WHEN ALTERATIONS, REPAIRS, OR
 ADDITIONS REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE
 SLEEPING ROOMS ARE ADDED OR CREATED IN EXISTING
 DWELLINGS, THE INDIVIDUAL DWELLING UNIT SHALL BE
 EQUIPPED WITH SMOKE ALARMS LOCATED AS REQUIRED FOR NEW
 DWELLINGS. FBC-RESIDENTIAL 314 AND 315
  
 2) GFI PROTECTION SHALL BE INSTALLED AT ALL LOCATIONS
 INDICATED IN THE NEC 210.8. THE PLAN INDICATES GFI
 PROTECTION TO BE INSTALLED ONLY IN THE GARAGE, BATHROOM
 OR OUTDOORS. THE NEC 210.8 INDICATES ADDITIONAL
 LOCATION WHERE GFI PROTECTION IS REQUIRED, SPECIFICALLY
 (6) KITCHENS ? WHERE THE RECEPTACLES ARE INSTALLED TO
 SERVE THE COUNTERTOP SURFACES. (7) LAUNDRY, UTILITY,
 AND WET BAR SINKS ? WHERE THE RECEPTACLES ARE INSTALLED
 WITHIN 1.8 M (6 FT) OF THE OUTSIDE EDGE OF THE SINK.
 NEC 210.8
  
 3) VERIFY #6 ROMEX ON 30AMP OCPD FOR DRYER CIRCUIT?
 REVISE AS NEEDED.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-05-12 Cont ID  
Sent By dhayes Date 2015-05-12 Time 10:48 Rev Time 0.00
Received By dhayes Date 2015-05-12 Time 10:20 Sent To  
Notes
2015-05-12 10:48:295/12/2015
 PROJECT: SNED ADDITION
 PERMIT#: 15031318
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) INDICATE OR VERIFY THAT ALL REQUIRED SMOKE DETECTORS
 ARE EXISTING OR PROPOSED TO BE INSTALLED. THERE IS A
 NOTE ON THE PLAN THAT SAY THERE SHALL BE SMOKE
 DETECTORS OUTSIDE OF SLEEPING AREAS. THIS IS ONLY
 PARTLY COMPLIANT. PLEASE READ THE FBC-R 314 AND 315
 WHICH STATES, IN PART, WHEN ALTERATIONS, REPAIRS, OR
 ADDITIONS REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE
 SLEEPING ROOMS ARE ADDED OR CREATED IN EXISTING
 DWELLINGS, THE INDIVIDUAL DWELLING UNIT SHALL BE
 EQUIPPED WITH SMOKE ALARMS LOCATED AS REQUIRED FOR NEW
 DWELLINGS. FBC-RESIDENTIAL 314 AND 315.
  
 2)THE SYMBOL LOCATED IN THE MEDIA ROOM FLOOR INDICATING
 A "FLOOR PLUG" SHALL BE INSTALLED USING MATERIALS
 LISTED SPECIFICALLY FOR THAT PURPOSE. SEE NEC 314.27(C)
 BOXES LISTED SPECIFICALLY FOR THIS APPLICATION SHALL BE
 USED FOR RECEPTACLES LOCATED IN THE FLOOR. NEC
 314.27(C)
  
 3) VERIFY THE REQUIRED RECEPTACLE CIRCUIT FOR THE
 BATHROOM IS RATED 20AMP AND HAS NO OTHER OUTLETS. SEE
 NEC210.52(C)(3) IN ADDITION TO THE NUMBER OF BRANCH
 CIRCUITS REQUIRED BY OTHER PARTS OF THIS SECTION, AT
 LEAST ONE 20-AMPERE BRANCH CIRCUIT SHALL BE PROVIDED TO
 SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH CIRCUITS
 SHALL HAVE NO OTHER OUTLETS. 210.52(C)(3) BATHROOM
 BRANCH CIRCUITS.
  
 4) INDICATE CIRCUIT NUMBERS ON THE FLOOR PLAN
 CORRESPONDING TO THE CIRCUIT NUMBERS IN THE PANEL
 SCHEDULE. WPB AMENDMENTS 107.3.5.1.2, AND 107.2.1.3
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By dhayes Date 2015-05-11 Time 16:16 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status   Date 2015-06-01 Cont ID  
Sent By lmarchan Date 2015-06-01 Time 11:01 Rev Time 0.00
Received By lmarchan Date 2015-05-21 Time 09:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-05-20 Cont ID  
Sent By cpuell Date 2015-05-20 Time 15:05 Rev Time 0.00
Received By cpuell Date 2015-04-01 Time 15:36 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2015-05-01 Cont ID  
Sent By jgomez Date 2015-05-01 Time 13:44 Rev Time 0.00
Received By jgomez Date 2015-05-01 Time 12:42 Sent To  
Notes
2015-05-01 13:45:57NO IMPACT FEES DUE. MU2015-10045. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-04-30 Cont ID  
Sent By jgomez Date 2015-04-30 Time 09:41 Rev Time 0.00
Received By jgomez Date 2015-04-30 Time 09:39 Sent To  
Notes
2015-04-30 09:43:071-BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2015-05-30 Cont ID  
Sent By jgomez Date 2015-05-30 Time 14:32 Rev Time 0.00
Received By jgomez Date 2015-05-30 Time 14:32 Sent To  
Notes
2015-05-30 14:40:29 
 1- THERE WERE TWO DIFFERENT EQUIPMENT CALCULATIONS
 SUBMITTED ON FIRST REVIEW. NO NEW EQUIPMENT
 CALCULATIONS WERE SUBMITTED AT THIS TIME. PROVIDE
 COMPLETE AND CORRECT INFORMATION THAT MATCHES UNDER A
 SEPARATE PERMIT. (EQUIPMENT ON PLANS, EQUIPMENT
 CALCULATIONS AND ENERGY CALCULATIONS NEED TO MATCH).

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-04-30 Cont ID  
Sent By jgomez Date 2015-04-30 Time 15:22 Rev Time 0.00
Received By jgomez Date 2015-04-30 Time 15:22 Sent To  
Notes
2015-04-30 15:31:31RESIDENTIAL (R3) ADDITION, MECHANICAL REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- THERE ARE TWO DIFFERENT EQUIPMENT SIZING
 CALCULATIONS SUBMITTED. ONE DONE BY KAREN OLIVER AND
 THE OTHER ONE DONE BY ASTRO AIR INC. COORDINATE ALL THE
 INFORMATION. EQUIPMENT SIZING CALCULATIONS AND A/C
 PLANS. SEC. 107.2.1 CITY AMENDMENTS.
 NOTE: CALCULATIONS DONE BY ASTRO AIR INC ARE
 INCOMPLETE. PROVIDE COMPLETE CALCULATIONS NOT JUST THE
 SUMMARY.
  
 2- KAREN OLIVER CALCULATIONS: SUBMIT THE MANUFACTURER
 AND MODEL NUMBER OF THE A/C EQUIPMENT ALONG WITH THE
 EQUIPMENT SIZING CALCULATIONS AS REQUIRED BY SEC.
 403.6.1 OF 2010 FBC-ENERGY CONSERVATION.
  
 3- EQUIPMENT LISTED ON THE MECHANICAL PLAN EXCEEDS THE
 REQUIREMENTS OF SEC. 403.6.1.1 OF 2010 FBC-ENERGY
 CONSERVATION. AND, COORDINATE WITH ITEM #1 ABOVE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]
 .

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-04-30 Cont ID  
Sent By tklarge Date 2015-04-30 Time 11:49 Rev Time 0.00
Received By tklarge Date 2015-04-30 Time 11:48 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2015-06-01 Cont ID  
Sent By lmarchan Date 2015-06-01 Time 10:54 Rev Time 0.00
Received By lmarchan Date 2015-06-01 Time 10:53 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2015-05-14 Cont ID  
Sent By sgraham Date 2015-05-14 Time 15:52 Rev Time 0.00
Received By sgraham Date 2015-05-14 Time 15:52 Sent To  
Notes
***NONE***