| 2015-04-01 05:47:08 | 1) SUBMIT MANUF. SPECIFICATIONS FOR THE TANKLESS WATER |
| | HEATERS AND THE DRYERS. APPLIANCES SHALL BE LISTED AND |
| | LABELED PER THE 2010 FL. FUEL GAS CODE SEC. 301.3. |
| | 2) SHOW THE LOCATION AND DISTANCE OF THE TANKLESS WATER |
| | HEATER'S EXHAUST IN RELATION TO ALL BUILDING OPENINGS |
| | INCLUDING ANY SOFFIT VENTS. SUBMIT 2 COPIES OF THE PAGE |
| | FROM THE MANUF. INSTALLATION MANUAL THAT SHOWS THE |
| | REQUIRED CLEARANCES. WPB AMEND. TO 2010 FBC SEC. |
| | 107.2.1, 2010 FGC SEC.303.1. |
| | 3) THE TANKLESS WATER HEATERS SHALL BE LISTED FOR |
| | OUTDOOR LOCATIONS. FGC SEC.303.6.SUBMIT DOCUMENTATION. |
| | 4) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE DRYERS IN |
| | ACCORDANCE WITH THE 2010 FGC SEC.304. |
| | 5) SUBMIT DETAILS FOR THE DRYER EXHAUSTS PER THE 2010 |
| | SEC.614. SHOW TYPE OF VENT, SIZES, LOCATIONS, ETC. |
| | 6) SIZE THE PIPE SECTION ON THE GAS RISER FROM THE |
| | METER TO THE FIRST BRANCH TO THE WATER HEATERS, WPB |
| | AMEND. TO 2010 FBC SEC. 107.2.1. |
| | 7) INSTALLATIONS EXHAUSTING MORE THAN 200 CFM SHALL BE |
| | PROVIDED WITH MAKEUP AIR PER 2010 FGC SEC.614.5. |
| | 8) SUBMIT A COPY OF THE MANUFACTURER'S INSTALLATION |
| | INSTRUCTIONS FOR THE DRYER'S PER THE 2010 FGC |
| | SEC.614.6.5.2. ARE THESE RESIDENTIAL TYPE DRYERS OR |
| | COMMERCIAL TYPE? INDICATE ON PLAN. |
| | 9) EXHAUST DUCTS SHALL BE EQUIPPED WITH A BACKDRAFT |
| | DAMPER PER THE 2010 FGC SEC.614.4. |
| | |
| | PLUMBING PLAN REVIEW |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | 561-805-6692 |
| | [email protected] |
| | |