Plan Review Details - Permit 15031231
Plan Review Stops For Permit 15031231
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-06-19 Cont ID  
Sent By jwitmer Date 2015-06-19 Time 13:27 Rev Time 0.00
Received By jwitmer Date 2015-06-19 Time 12:15 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-04-10 Cont ID  
Sent By jwitmer Date 2015-04-10 Time 13:53 Rev Time 0.00
Received By jwitmer Date 2015-04-10 Time 08:09 Sent To  
Notes
2015-04-10 13:53:35BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15031231
 ADD: 2901 BROADWAY
 CONT: J M PROPERTIES
 TEL: (561)804-1248
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 IMPORTANT NOTICE: EFFECTIVE MARCH 30, 2015
 ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED
 ELECTRONICALLY
 UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS
 SUBMISSION OPTIONS ARE AS FOLLOWS:
 1 UPLOAD VIA THE PROJECT DOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL
 SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED
 NAMING CONVENTION FOR EACH DOCUMENT
 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER
 DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE
 REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT
 TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS
 ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES
 AVAILABLE.
  
 1ST REVIEW
 DATE: FRIDAY APRIL 10/2015
 ACTION: DENIED
  
 1) THE PLANS SHEET A1.1 INDICATE THE FACILITY IS
 LOCATED IN PALM BEACH GARDENS. SEE THE HEADING
 STATISTICS. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION OF THE
 PROJET.
  
 2) THE COVER SHEET LIST THE OCCUPANCY AS A I-2. THE
 2010 FBC-B SECTION LIST A I-2 OCCUPANCY AS : THIS
 OCCUPANCY SHALL INCLUDE BUILDINGS AND STRUCTURES USED
 FOR MEDICAL, SURGICAL, PSYCHIATRIC, NURSING OR
 CUSTODIAL CARE FOR PERSONS WHO ARE NOT CAPABLE OF
 SELF-PRESERVATION. FROM THE MEETING MONTHS AGO I
 BELIEVE THE GROUP I-1 OCCUPANCY IS A BETTER FIT FOR
 TYPE OF OCCUPANCY. THIS OCCUPANCY SHALL INCLUDE
 BUILDINGS, STRUCTURES OR PARTS THEREOF HOUSING MORE
 THAN 16 PERSONS, ON A 24-HOUR BASIS, WHO BECAUSE OF
 AGE, MENTAL DISABILITY OR OTHER REASONS, LIVE IN A
 SUPERVISED RESIDENTIAL ENVIRONMENT THAT PROVIDES
 PERSONAL CARE SERVICES. THE OCCUPANTS ARE CAPABLE OF
 RESPONDING TO AN EMERGENCY SITUATION WITHOUT PHYSICAL
 ASSISTANCE FROM STAFF.
  
 PERSONNAL CARE SERVICES. THE OCCUPANTS ARE CAPABLE OF
 RESPONDING TO AN EMERGENCY SITUATION WITHOUT PHYSICAL
 ASSISTANCE FROM STAFF. THIS CLASSIFICATION SHALL
 INCLUDE, BUT NOT BE LIMITED TO, THE FOLLOWING:
 RESIDENTIAL BOARD AND CARE FACILITIES, ASSISTED LIVING
 FACILITIES, HALFWAY HOUSES, GROUP HOMES, CONGREGATE
 CARE FACILITIES, SOCIAL REHABILITATION FACILITIES,
 ALCOHOL AND DRUG ABUSE CENTERS AND CONVALESCENT
 FACILITIES.
  
 THIS REVIEW WILL BE COMPLETED AS A TYPE I-1 OCCUPANCY
 WITH COMMENTS. PLANS DO NOT STATE IF THIS IS A CHANGE
 OF OCCUPANCY OR NOT?
  
 3) THE COVER SHEET DOES NOT STATE THAT THE BUILDINGS
 ARE TO BE FIRE SPRINKLERED, SHOW COMPLIANCE WITH [F]
 903.2.6 GROUP I. AN AUTOMATIC SPRINKLER SYSTEM SHALL BE
 PROVIDED THROUGHOUT BUILDINGS WITH A GROUP I FIRE AREA.
 EXCEPTION: AN AUTOMATIC SPRINKLER SYSTEM INSTALLED IN
 ACCORDANCE WITH SECTION 903.3.1.2 OR 903.3.1.3 SHALL BE
 ALLOWED IN GROUP I-1 FACILITIES.
  
 4) SHEET A2.2THE FLOOR PLAN DOES NOT SHOW COMPLIANCE
 WITH FBC-B 439.2 SEPARATION WALLS. WALLS SEPARATING
 DWELLING UNITS IN THE SAME BUILDING, WALLS SEPARATING
 SLEEPING UNITS IN THE SAME BUILDING AND WALLS
 SEPARATING DWELLING OR SLEEPING UNITS FROM OTHER
 OCCUPANCIES CONTIGUOUS TO THEM IN THE SAME BUILDING
 SHALL BE CONSTRUCTED AS FIRE PARTITIONS IN ACCORDANCE
 WITH SECTION 709.
  
 5) THE PLANS DO NOT SHOW COMPLIANCE WITH FBC-B TABLE
 803.9 INTERIOR WALL & CEILING FINISH REQUIREMENTS BY
 OCCUPANCY.
  
 6) PLEASE PROVIDE DOCUMENTATION WITH FBC-B IN GROUPS
 I-1 AND I-2, COMBUSTIBLE DECORATIVE MATERIALS SHALL
 MEET THE FLAME PROPAGATION CRITERIA OF NFPA 701 UNLESS
 THE DECORATIVE MATERIALS, INCLUDING, BUT NOT LIMITED
 TO, PHOTOGRAPHS AND PAINTINGS, ARE OF SUCH LIMITED
 QUANTITIES THAT A HAZARD OF FIRE DEVELOPMENT OR SPREAD
 IS NOT PRESENT.
  
 7) SHOW COMPLIANCE WITH FBC-B F] 907.2.6.1 GROUP I-1.
 AN AUTOMATIC SMOKE DETECTION SYSTEM SHALL BE INSTALLED
 IN CORRIDORS, WAITING AREAS OPEN TO CORRIDORS AND
 HABITABLE SPACES OTHER THAN SLEEPING UNITS AND
 KITCHENS. THE SYSTEM SHALL BE ACTIVATED IN ACCORDANCE
 WITH SECTION 907.5.
  
 8) SHEET A2.4 DETAIL B7 IT APPEARS THERE IS A CURB BUT
 THE DETAIL IS LABELED AS A ROLL-IN SHOWER?
  
 9) SHEET A2.2 SHOWS THE BEDROOM # 7 WITH THE ACCESSIBLE
 BATHROOM. THE PLANS DO NOT SHOW HOW COMPLIANCE WITH
 2010 FBC-ACCESSIBILITY CODE 223.2.1. WILL BE ACHIEVED.
 223.2.1 FACILITIES NOT SPECIALIZING IN TREATING
 CONDITIONS THAT AFFECT MOBILITY.
 IN FACILITIES NOT SPECIALIZING IN TREATING CONDITIONS
 THAT AFFECT MOBILITY, AT LEAST 10 PERCENT, BUT NO FEWER
 THAN ONE, OF THE PATIENT SLEEPING ROOMS SHALL PROVIDE
 MOBILITY FEATURES COMPLYING WITH 805. ACCESSIBLE
 PATIENT BEDROOMS SHALL BE DISPERSED IN A MANNER THAT IS
 PROPORTIONATE BY TYPE OF MEDICAL SPECIALTY.
  
 805.1 GENERAL.
 MEDICAL CARE FACILITY AND LONG-TERM CARE FACILITY
 PATIENT OR RESIDENT SLEEPING ROOMS REQUIRED TO PROVIDE
 MOBILITY FEATURES SHALL COMPLY WITH 805.
  
 805.2 TURNING SPACE.
 TURNING SPACE COMPLYING WITH 304 SHALL BE PROVIDED
 WITHIN THE ROOM.
  
 805.3 CLEAR FLOOR OR GROUND SPACE.
 A CLEAR FLOOR SPACE COMPLYING WITH 305 SHALL BE
 PROVIDED ON EACH SIDE OF THE BED. THE CLEAR FLOOR SPACE
 SHALL BE POSITIONED FOR PARALLEL APPROACH TO THE SIDE
 OF THE BED.
  
 805.4 TOILET AND BATHING ROOMS.
 TOILET AND BATHING ROOMS THAT ARE PROVIDED AS PART OF A
 PATIENT OR RESIDENT SLEEPING ROOM SHALL COMPLY WITH
 603. WHERE PROVIDED, NO FEWER THAN ONE WATER CLOSET,
 ONE LAVATORY, AND ONE BATHTUB OR SHOWER SHALL COMPLY
 WITH THE APPLICABLE REQUIREMENTS OF 603 THROUGH 610.
  
 10) SHEET A2.2 DOES NOT SHOW ANY DINKING FOUNTAINS,
 WITH THE OCCUPANT LOAD GREATER THAN 15 THE PLUMBING
 CODE WILL REQUIRE 1. PLEASE SEE FL ACCESSIBILITY CODE
 211.2 MINIMUM NUMBER.
 NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH
 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 602.7.
  
 11) SHEET A2.2 THE OFFICE DOES NOT INDICATE COMPLIANCE
 WITH ACCESSIBILITY CODE 904.3.3 CHECK WRITING SURFACES.
 WHERE PROVIDED, CHECK WRITING SURFACES SHALL COMPLY
 WITH 902.3.
  
 12) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-07-21 Cont ID  
Sent By dhayes Date 2015-07-21 Time 10:32 Rev Time 0.00
Received By dhayes Date 2015-07-21 Time 09:47 Sent To  
Notes
2015-07-21 10:31:597/21/2015
 PROJECT: BEACHWAY CENTER
 PERMIT#: 15031231
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 3RD ELECTRICAL PLAN REVIEW
 ACTION: APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN
 APPROVED PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED
 INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION
 FEE(S).
  
 1) COORDINATE THE INSTALLATION OF THE A/C EQUIPMENT AND
 THE TANKLESS WATER HEATERS WITH THE MANUFACTURER'S
 DOCUMENTATION FOR THE MAXIMIM OCPD AND THE MINIMUM
 AMPACITY OF THE CIRCUIT CONDUCTORS FEEING EQUIPMENT.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-07-07 Cont ID  
Sent By dhayes Date 2015-07-07 Time 12:59 Rev Time 0.00
Received By dhayes Date 2015-07-07 Time 12:33 Sent To  
Notes
2015-07-07 12:50:197/7/2015
 PROJECT: BEACHWAY CENTER
 PERMIT#: 15031231
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 2ND ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1) THE RISER DIAGRAM INDICATES SIZE 150MCM WIRE FROM
 THE METER TO THE MAIN IN PANEL A AND FROM PANEL A TO
 PANEL A1. PANEL A IS INDICATED TO BE RATED AT 200AMP
 MAX AND PANEL A1 IS ONLY RATED AT 100AMP. THERE IS NO
 SIZE 150MCM. PROVIDE AN APPROVED WIRE SIZE FOR THE LOAD
 TO BE SERVED.
  
 2) THE RISER DIAGRAM INDICATES A 250AMP MAIN BREAKER IN
 PANEL A. PANEL A IS INDICATED TO BE RATED AT 200AMP
 MAX.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-05-15 Cont ID  
Sent By hmoser Date 2015-05-15 Time 09:58 Rev Time 0.00
Received By dhayes Date 2015-05-15 Time 09:09 Sent To M
Notes
2015-05-15 09:32:355/15/2015
 PROJECT: BEACHWAY CENTER
 PERMIT#: 15031231
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION:
  
 REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1) PROVIDE A RISER DIAGRAM AND LOAD CALCULATION FOR
 BOTH BUILDINGS. IF REQUIRED BY THE AUTHORITY HAVING
 JURISDICTION, A DIAGRAM SHOWING FEEDER DETAILS SHALL BE
 PROVIDED PRIOR TO THE INSTALLATION OF THE FEEDERS. SUCH
 A DIAGRAM SHALL SHOW THE AREA IN SQUARE FEET OF THE
 BUILDING OR OTHER STRUCTURE SUPPLIED BY EACH FEEDER,
 THE TOTAL CALCULATED LOAD BEFORE APPLYING DEMAND
 FACTORS, THE DEMAND FACTORS USED, THE CALCULATED LOAD
 AFTER APPLYING DEMAND FACTORS, AND THE SIZE AND TYPE OF
 CONDUCTORS TO BE USED. NEC 215.5. WPB AMENDMENTS TO FBC
 107.3.5.1.2
  
 2) BUILDING A INDICATES A SYMBOL FOR A RECEPTACLE IN
 THE CENTER OF EXISTING ROOM 2. PLEASE INDICATE A
 PURPOSE FOR THIS DEVICE AND WEATHER IT IS TO BE LOCATED
 IN THE CEILING OR THE FLOOR. IF IT IS TO BE LOCATED IN
 THE FLOOR, THE BOXES SHALL BE LISTED SPECIFICALLY FOR
 THIS APPLICATION SHALL BE USED FOR RECEPTACLES LOCATED
 IN THE FLOOR. NEC 314.27(C)
  
 3) AS NOTED ON THE FIRE INSPECTORS COMMENTS, A SMOKE
 DETECTOR SHALL BE INSTALLED IN EACH OF THE NEWLY
 CREATED SLEEPING ROOMS.
  
 4) PROVIDE THE MANUFACTURER DOCUMENTATION FOR THE A/C
 SYSTEMS TO INCLUDE THE WIRING DIAGRAMS AND CIRCUITRTY
 REQUIREMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-06-11 Cont ID  
Sent By pleduc Date 2015-06-11 Time   Rev Time 0.00
Received By pleduc Date 2015-06-11 Time 11:26 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-03-30 Cont ID  
Sent By pleduc Date 2015-03-30 Time   Rev Time 0.00
Received By pleduc Date 2015-03-30 Time 11:52 Sent To  
Notes
2015-03-30 12:05:57THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PROVISO:
  
 THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF THE
 FIRE ALARM AND SPRINKLER SYSTEM FOR CODE COVERAGE AND
 COMPLIANCE.
  
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  
 PROVIDE SMOKE DETECTORS IN EACH NEWLY CREATED SLEEPING
 SPACE.
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-07-21 Cont ID  
Sent By dhayes Date 2015-07-21 Time 10:32 Rev Time 0.00
Received By dhayes Date 2015-07-17 Time 12:51 Sent To  
Notes
2015-07-17 12:51:43ROUTED TO DHAYES

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-07-07 Cont ID  
Sent By dhayes Date 2015-07-07 Time 13:00 Rev Time 0.00
Received By dhayes Date 2015-06-08 Time 10:11 Sent To  
Notes
2015-06-08 10:11:38****EXPEDITED****
 B11
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-05-16 Cont ID  
Sent By hmoser Date 2015-05-16 Time 08:39 Rev Time 0.00
Received By hmoser Date 2015-03-26 Time 17:08 Sent To  
Notes
2015-03-26 17:07:45B26
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2015-07-23 Cont ID  
Sent By ccole Date 2015-07-23 Time 08:24 Rev Time 0.00
Received By ccole Date 2015-07-23 Time 08:23 Sent To  
Notes
2015-07-23 08:27:28MECHANICAL PROVISO: 7/23/15.
 THE PLANS ARE APPROVED WITH EXCEPTION HOWEVER REVISED
 PLANS TO CORRECT THE FOLLOWING LIST OF DEFICIENCIES
 SHALL BE SUBMITTED, REVIEWED AND APPROVED PRIOR TO
 FIRST INSPECTION.
  
 1) PROVIDE OUTDOOR AIR CALCULATIONS FOR ALL OCCUPIED
 ROOMS AND SPACES IN BUILDINGS A & B- TABLE 403.3.
 2) SHOW A MEANS OF PROVIDING THE REQUIRED OUTDOOR AIR
 TO THE ROOMS AND SPACES.
 3) REVISE THE PLANS TO SHOW THAT THE LOCATIONS OF THE
 CONDENSERS AND ZONE ARRANGEMENTS AS SHOWN ON THE NEW AC
 PLANS MATCH THE MAIN ARCHITECTURAL AND ELECTRICAL PLAN
 SETS. PLEASE MAKE THESE PLANS MATCH ONE WAY OR THE
 OTHER.
 4) PROVIDE DUPLICATE SETS OF AC PLANS FOR BUILDINGS A
 AND B ARE REQUIRED: ONLY ONE SET FOR EACH WAS
 SUBMITTED.
 5) PROVIDE CONDENSATE DISPOSAL DETAILS, PRIMARY AND
 SECONDARY- SECTION 307 FBC-10 MECHANICAL.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-07-07 Cont ID  
Sent By ccole Date 2015-07-07 Time 08:14 Rev Time 0.00
Received By ccole Date 2015-07-07 Time 07:41 Sent To  
Notes
2015-07-07 08:17:252ND REVIEW: FBC 2010 MECHANICAL
  
 1) COMMENTS #2, 4, & 5 FROM THE FIRST REVIEW STILL
 EXIST. AS PREVIOUSLY REQUESTED PROVIDE- A) OUTDOOR AIR
 CALCULATIONS FOR ALL OCCUPIABLE ROOMS AND SPACES IN
 BUILDINGS A & B- TABLE 403.3. B) CONDENSATE DISPOSAL
 DETAILS, PRIMARY AND SECONDARY- SECTION 307.
 2) THE LOCATIONS OF THE CONDENSERS AND ZONE
 ARRANGEMENTS SHOWN ON THE NEW AC PLANS DO NOT MATCH
 WITH THE MAIN ARCHITECTURAL AND ELECTRICAL PLAN SETS.
 PLEASE MAKE THESE PLANS MATCH ONE WAY OR THE OTHER.
 3) THE AC PLANS DO NOT SHOW ANY MEANS OF PROVIDING
 OUTDOOR AIR INTO THE ROOMS AND SPACES.
 4) PLEASE NOTE THAT ONLY ONE SET OF AC PLANS WERE
 SUBMITTED FOR BUILDINGS A AND B: DUPLICATE SETS ARE
 REQUIRED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-05-16 Cont ID  
Sent By hmoser Date 2015-05-16 Time 08:38 Rev Time 0.00
Received By hmoser Date 2015-05-16 Time 07:48 Sent To  
Notes
2015-05-16 08:38:51PLAN DENIED
 1) PROVIDE A EQUIPMENT SCHEDULE FOR
 AIR CONDITIONING EQUIPMENT. PER SECTION
 107 FBC 2010
 2) PROVIDE FRESH AIR CALCULATIONS ON
 THE PLAN PER TABLE 403.3 MINIMUM
 VENTILATION RATES FBC (M) 2010
 3) SHOW BATHROOM EXHAUST ON THE PLAN
 PER TABLE 401.3 AND EXHAUST TERMINATION
 4) REFER TO SECTION 307.2.1 CONDENSATE DISPOSAL
 SHOW TERMINATION OF CONDENSATE.
 5) REFER TO SECTION 307.2.3 AUXILIARY AND
 SECONDARY DRAIN SYSTEMS. 2010 FBC (M)
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-04-19 Cont ID  
Sent By tklarge Date 2015-04-19 Time 05:47 Rev Time 0.00
Received By tklarge Date 2015-04-19 Time 05:19 Sent To  
Notes
***NONE***