Plan Review Details - Permit 15031160
Plan Review Stops For Permit 15031160
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-04-16 Cont ID  
Sent By skennedy Date 2015-04-16 Time 14:41 Rev Time 0.00
Received By skennedy Date 2015-04-16 Time 14:41 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-04-04 Cont ID  
Sent By skennedy Date 2015-04-04 Time 13:21 Rev Time 0.00
Received By skennedy Date 2015-04-04 Time 13:21 Sent To  
Notes
2015-04-04 13:23:461ST REVIEW: FBC 2010
  
 PURSUANT TO FBC 107.1, AND FS 481.229 (1) (C), AS THIS
 DESIGN EXCEEDS $25,000.00 IN VALUE, THE DESIGN MUST BE
 PREPARED BY A PROFESSIONAL LICENSED PURSUANT TO FS 481.
 SEE BELOW:
  
 FBC107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF
 CONSTRUCTION DOCUMENTS, STATEMENT OF SPECIAL
 INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA SHALL
 BE SUBMITTED IN TWO OR MORE SETS WITH EACH PERMIT
 APPLICATION. THE CONSTRUCTION DOCUMENTS SHALL BE
 PREPARED BY A REGISTERED DESIGN PROFESSIONAL WHERE
 REQUIRED BY CHAPTER 471, FLORIDA STATUTES& 61G15
 FLORIDA ADMINISTRATIVE CODE OR CHAPTER 481, FLORIDA
 STATUTES& 61G1 FLORIDA ADMINISTRATIVE CODE. WHERE
 SPECIAL CONDITIONS EXIST, THE BUILDING OFFICIAL IS
 AUTHORIZED TO REQUIRE ADDITIONAL CONSTRUCTION DOCUMENTS
 TO BE PREPARED BY A
 REGISTERED DESIGN PROFESSIONAL. ELECTRONIC MEDIA
 DOCUMENTS SHALL BE SUBMITTED WHEN REQUIRED BY THE
 BUILDING OFFICIAL, AND MAY REQUIRE ONLY ONE SET OF
 SUBMITTALS.
  
 FS 481.229 -EXCEPTIONS; EXEMPTIONS FROM LICENSURE.
 (1) NO PERSON SHALL BE REQUIRED TO QUALIFY AS AN
 ARCHITECT IN ORDER TO MAKE PLANS AND SPECIFICATIONS
 FOR, OR SUPERVISE THE ERECTION, ENLARGEMENT, OR
 ALTERATION OF:
 (A) ANY BUILDING UPON ANY FARM FOR THE USE OF ANY
 FARMER, REGARDLESS OF THE COST OF THE BUILDING;
 (B) ANY ONE-FAMILY OR TWO-FAMILY RESIDENCE BUILDING,
 TOWNHOUSE, OR DOMESTIC OUTBUILDING APPURTENANT TO ANY
 ONE-FAMILY OR TWO-FAMILY RESIDENCE, REGARDLESS OF COST;
 OR
 (C) ANY OTHER TYPE OF BUILDING COSTING LESS THAN
 $25,000, EXCEPT A SCHOOL, AUDITORIUM, OR OTHER BUILDING
 INTENDED FOR PUBLIC USE, PROVIDED THAT THE SERVICES OF
 A REGISTERED ARCHITECT SHALL NOT BE REQUIRED FOR MINOR
 SCHOOL PROJECTS PURSUANT TO S. 1013.45.
  
 FBC-107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. ALL
 INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING
 DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN.
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 ELECTRONIC MEDIA DOCUMENTS SHALL BE
 SUBMITTED WHEN APPROVED BY THE BUILDING OFFICIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. (SEE ALSO SECTION 107.3.5).
  
 FBC 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS
 SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON
 SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM.
 THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE,
 SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO
 RECORDS MANAGEMENT.
  
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-04-16 Cont ID  
Sent By dhayes Date 2015-04-16 Time 09:52 Rev Time 0.00
Received By dhayes Date 2015-04-16 Time 09:52 Sent To  
Notes
2015-04-16 09:57:04APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN APPROVED
 PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED
 INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION FEE(S
  
 1) FBC 2704 BONDING METAL FRAMING MEMBERS:
 METAL FRAMING MEMBERS SHALL BE BONDED TO THE EQUIPMENT
 GROUNDING CONDUCTOR FOR THE CIRCUIT THAT MAY ENERGIZE
 THE FRAMING AND BE SIZED IN ACCORDANCE WITH THE NEC
 TABLE 250.122. FOR THE PURPOSE OF THIS SECTION, A
 GROUNDED METAL OUTLET BOX ATTACHED TO THE FRAMING SHALL
 BE PERMITTED.
  
 2) FBC-RESIDENTIAL 314 AND 315.
 VERIFY SMOKE AND CARBON MONIXIDE DETECTORS ARE
 INSTALLED AS REQUIRED. WHEN ALTERATIONS, REPAIRS, OR
 ADDITIONS REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE
 SLEEPING ROOMS ARE ADDED OR CREATED IN EXISTING
 DWELLINGS, THE INDIVIDUAL DWELLING UNIT SHALL BE
 EQUIPPED WITH SMOKE ALARMS LOCATED AS REQUIRED FOR NEW
 DWELLINGS. FBC-RESIDENTIAL 314 AND 315.
  
 3) NEC 210.12, 406.11
 ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER
 RESISTANT AND AFCI PROTECTED. NEC 210.12, 406.11
  
 4) NEC 210.8
 ALL OUTLETS IN THE KITCHEN TO BE GFI. NEC 210.8
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-04-04 Cont ID  
Sent By skennedy Date 2015-04-04 Time 13:23 Rev Time  
Received By skennedy Date   Time   Sent To  
Notes
2015-04-04 13:24:45SEE BUILDING REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-04-17 Cont ID  
Sent By pleduc Date 2015-04-17 Time   Rev Time 0.00
Received By pleduc Date 2015-04-17 Time 13:17 Sent To PC
Notes
2015-04-17 13:23:40THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF THE
 FIRE ALARM AND SPRINKLER SYSTEM FOR CODE COVERAGE AND
 COMPLIANCE.
  
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-04-07 Cont ID  
Sent By pleduc Date 2015-04-07 Time   Rev Time 0.00
Received By pleduc Date 2015-04-07 Time 15:26 Sent To PC
Notes
2015-04-07 15:29:27THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 INCOMPLETE PLANS, SEE BUILDING COMMENTS.
  
 THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF THE
 FIRE ALARM AND SPRINKLER SYSTEM FOR CODE COVERAGE AND
 COMPLIANCE.
  
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-04-17 Cont ID  
Sent By pleduc Date 2015-04-17 Time   Rev Time 0.00
Received By pleduc Date 2015-04-15 Time 09:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-04-07 Cont ID  
Sent By pleduc Date 2015-04-07 Time   Rev Time 0.00
Received By pleduc Date 2015-03-25 Time 16:57 Sent To  
Notes
2015-03-25 16:59:56B01

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2015-04-16 Cont ID  
Sent By skennedy Date 2015-04-16 Time 14:41 Rev Time 0.00
Received By skennedy Date 2015-04-16 Time 14:41 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-04-04 Cont ID  
Sent By skennedy Date 2015-04-04 Time 13:24 Rev Time  
Received By skennedy Date   Time   Sent To  
Notes
2015-04-04 13:25:11SEE BUILDING REVIEW

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-04-16 Cont ID  
Sent By skennedy Date 2015-04-16 Time 14:42 Rev Time 0.00
Received By skennedy Date 2015-04-16 Time 14:42 Sent To FIRE
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-04-04 Cont ID  
Sent By skennedy Date 2015-04-04 Time 13:24 Rev Time  
Received By skennedy Date   Time   Sent To FIRE
Notes
2015-04-04 13:25:22SEE BUILDING REVIEW