| 2015-04-20 10:42:24 | SECOND REVIEW: DUPLICATE COMMENTS |
| | PLEASE PROVIDE PLANS AND INFORMATION TO ADDRESS THE |
| | FOLLOWING ELECTRICAL REVIEW COMMENTS AS PREVIOUSLY |
| | REQUESTED. |
| | |
| | 1.) FBC 107.2.1. SUBMITTED PLAN TO BE SIGNED BY |
| | DESIGNER. THE PLANS HAVE NOT BEEN SIGNED. THIS A |
| | REQUIREMENT OF THE FLORIDA BUILDING CODE AND ALSO IN |
| | OUR WEST PALM BEACH AMENDMENTS TO CHAPTER ONE. SECTION |
| | 107.2.1 PLEASE PROVED TWO COPIES OF PLANS THAT HAVE |
| | BEEN SIGNED BY THE DESIGNER OF RECORD. |
| | |
| | 2.) FBC SECTION 314 LOCATION OF SMOKE ALARMS. WHEN |
| | ALTERATIONS, REPAIRS, OR ADDITIONS REQUIRING A PERMIT |
| | OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE ADDED OR |
| | CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL DWELLING |
| | UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS LOCATED AS |
| | REQUIRED FOR NEW DWELLINGS. FBC-RESIDENTIAL 314 AND |
| | 315. A PLAN HAS BEEN SUBMITTED THAT INDICATES SOME |
| | SMOKE DETECTORS UNFORTUNATELY THE LOCATIONS SHOWN DO |
| | NOT MEET THE CRITERIA SET FOR THE FBC-R 413 NAND 315. |
| | SMOKE DETECTORS ARE REQUIRED TO BE INSTALLED INSIDE AND |
| | OUTSIDE OF THE SLEEPING ROOMS. THE PLAN PROVIDED |
| | INDICATES SMOKE DETECTORS TO BE INSTALLED ON THE INSIDE |
| | ONLY. |
| | |
| | 3.) N.E.C. 210.63, AND N.E.C. 210.8 (A) (3). LOCATION |
| | OF GFCI PROTECTED OUTLET WITHIN 25' OF A.C. CONDENSOR. |
| | CODE REFFERENCES: |
| | (A) NEC 210.63 ONE 125VOLT, SINGLE-PHASE, 15 OR 20AMP |
| | GFI RECEPTACLE OUTLET SHALL BE INSTALLED AT AN |
| | ACCESSIBLE LOCATION FOR THE SERVICING OF HEATING, |
| | AIR-CONDITIONING, AND REFRIGERATION EQUIPMENT. THE |
| | RECEPTACLE SHALL BE LOCATED ON THE SAME LEVEL AND |
| | WITHIN 25FT OF THE HEATING, AIR-CONDITIONING, AND |
| | REFRIGERATION EQUIPMENT. THE RECEPTACLE OUTLET SHALL |
| | NOT BE CONNECTED TO THE LOAD SIDE OF THE EQUIPMENT |
| | DISCONNECTING MEANS. NEC 210.63 SEE ALSO NEC |
| | 210.8(A)(3), |
| | (B) NEC 210.8 GROUND-FAULT CIRCUIT-INTERRUPTER |
| | PROTECTION FOR PERSONNEL. (A) DWELLING UNITS. ALL |
| | 125-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE RECEPTACLES |
| | INSTALLED IN THE LOCATIONS SPECIFIED IN (1) THROUGH (8) |
| | SHALL HAVE GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION |
| | FOR PERSONNEL. |
| | (C) NEC 406.8(B)(1) ALL 15 AND 20AMP 125V AND 250V |
| | RECEPTACLES INSTALLED IN IN A WET LOCATION SHALL HAVE |
| | AN ENCLOSURE THAT IS WEATHERPROOF WHETHER OR NOT THE |
| | ATTACHMENT PLUG CAP IS INSERTED. ALL 15- AND 20-AMPERE, |
| | 125- AND 250-VOLT NON-LOCKING RECEPTACLES SHALL BE |
| | LISTED WEATHER-RESISTANT TYPE |
| | PLEASE INDICATE ON THE PLANS THAT THE REQUIRED |
| | RECEPTACLE IS EITHER CURRENTLY EXISTING TO REMAIN OR |
| | PROPOSED TO BE INSTALLED. |
| | |
| | 4.) TABLE NEC 310.16. OVERCURRENT PROTECTION FOR 3#6 |
| | FROM 150 AMP SERVICE EQUIPMENT ENCLOSURE TO 60 AMP |
| | PANEL. THE RISER DIAGRAM INDICATES THE INSTALATION OF A |
| | NEW 150AMP ELECTRICAL SERVICE FEEDING A 60AMP INDOOR |
| | MAIN LUG ONLY PANEL WITHOUT THE INDICATION OF ANY |
| | OVERCURRENT PROTECTIVE DEVICE AHEAD OF THE #6 WIRE |
| | SHOWN ON THE RISER DIAGRAM. A PANEL SCHEDULE IS |
| | REQUIRED TO INDICATE THE CORRECT OCPD IN THE NEW |
| | SERVICE EQUIPMENT TO PROTECT THE #6 FEEDER TO THE MAIN |
| | LUG PANEL IN THE HOUSE. |
| | 5. WIRE SIZE TO 5KW AHU. |
| | |
| | 5) ADDITIONALLY, A SEPARATE PERMIT APPLICATION |
| | ACCOMPANIED BY MANUFACTURERS EQUIPMENT SUBMITTALS, AND |
| | SHOP DRAWINGS FOR THE PROPOSED NEW CENTRAL AIR |
| | CONDITIONING SYSTEM. |
| | |