Plan Review Details - Permit 15031147
Plan Review Stops For Permit 15031147
Review Stop E ELECTRICAL
Rev No 4 Status P Date 2015-07-01 Cont ID  
Sent By albarran Date 2015-07-01 Time 17:26 Rev Time 0.00
Received By albarran Date 2015-07-01 Time 16:36 Sent To I
Notes
2015-07-01 17:26:41APPROVED W/PROVISO:
 1) FOR FINAL INSPECTION, ALL PANELS SHALL HAVE A
 CIRCUIT DETAIL AS REQUIRED BY NEC 408.5.
 2) ELECTRICAL INSPECTOR SHALL BE PROVIDED WITH AN
 ACCURATE & ACCEPTABLE RISER DIAGRAM & LOAD CALCS AS
 REQUIRED BY NEC 215.5
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2015-06-12 Cont ID  
Sent By dhayes Date 2015-06-12 Time 08:16 Rev Time 0.00
Received By dhayes Date 2015-06-12 Time 07:31 Sent To  
Notes
2015-06-12 08:01:136/12/2015
 PROJECT: HAVENBROOK RESIDENCE
 PERMIT#: 15031147
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 3RD ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 DUPLICATE COMMENTS!
  
 IMORTANT NOTICE:
 CHAPTER 553.80(2)(B) FLORIDA STATUTES STATES THAT A
 LOCAL GOVERNMENT SHALL IMPOSE A FEE OF FOUR TIMES THE
 FEE FOR PLAN REVIEW, IF PLANS ARE REJECTED (3) OR MORE
 TIMES FOR REPEATED FAILURE TO CORRECT A CODE VIOLATION.
  
 REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1.) FBC 107.2.1. SUBMITTED PLAN TO BE SIGNED BY
 DESIGNER. THE PLANS HAVE NOT BEEN SIGNED. THIS A
 REQUIREMENT OF THE FLORIDA BUILDING CODE AND ALSO IN
 OUR WEST PALM BEACH AMENDMENTS TO CHAPTER ONE. SECTION
 107.2.1 PLEASE PROVED TWO COPIES OF PLANS THAT HAVE
 BEEN SIGNED BY THE DESIGNER OF RECORD.
  
 2.) FBC SECTION 314 LOCATION OF SMOKE ALARMS. WHEN
 ALTERATIONS, REPAIRS, OR ADDITIONS REQUIRING A PERMIT
 OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE ADDED OR
 CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL DWELLING
 UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS LOCATED AS
 REQUIRED FOR NEW DWELLINGS. FBC-RESIDENTIAL 314 AND
 315. A PLAN HAS BEEN SUBMITTED THAT INDICATES SOME
 SMOKE DETECTORS UNFORTUNATELY THE LOCATIONS SHOWN DO
 NOT MEET THE CRITERIA SET FOR THE FBC-R 413 NAND 315.
 SMOKE DETECTORS ARE REQUIRED TO BE INSTALLED INSIDE AND
 OUTSIDE OF THE SLEEPING ROOMS. THE PLAN PROVIDED
 INDICATES SMOKE DETECTORS TO BE INSTALLED ON THE INSIDE
 ONLY.
  
 3.) TABLE NEC 310.16. OVERCURRENT PROTECTION FOR 3#6
 FROM 150 AMP SERVICE EQUIPMENT ENCLOSURE TO 60 AMP
 PANEL. THE RISER DIAGRAM INDICATES THE INSTALATION OF A
 NEW 150AMP ELECTRICAL SERVICE FEEDING A 150 AMP INDOOR
 MAIN LUG PANEL ONLY. REVISE THE RISER DIAGRAM TO
 INCLUDE THE SUB-PANEL INDICATING THE CONDUIT AND WIRE
 SIZES FROM THE MAIN SERVICE TO THE SUB-PANEL.
  
 4) NEC 408.4 PROVIDE A PANEL SCHEDULE FOR THE
 SUB-PANEL. INCLUDE ALL CIRCUIT NAMES AND NUMBERS AS
 WELL AS ALL CIRCUIT OCPD'S AND WIRE SIZES.
  
 5) REVISE PANEL SCHEDULE. AHU AND CU FOR A/C ARE
 240VOLT 2POLE CIRCUITS BUT SHOWN IN THE PANEL SCHEDULE
 SUBMITTED AS SINGLE POLE 120 VOLT CIRCUITS.
 ADDITIONALLY, INCLUDE A CIRCUIT FOR THE WATER HEATER.
  
 6) A MINIMUM OF TWO RECEPTACLES ARE REQUIRED IN THE
 KITCHEN. THERE IS ONLY ONE SHOWN.
  
 7) ADDITIONALLY, A SEPARATE PERMIT APPLICATION
 ACCOMPANIED BY MANUFACTURERS EQUIPMENT SUBMITTALS, AND
 SHOP DRAWINGS FOR THE PROPOSED NEW CENTRAL AIR
 CONDITIONING SYSTEM.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-04-20 Cont ID  
Sent By dhayes Date 2015-04-20 Time 08:31 Rev Time 0.00
Received By dhayes Date 2015-04-20 Time 08:27 Sent To  
Notes
2015-04-20 10:42:24SECOND REVIEW: DUPLICATE COMMENTS
 PLEASE PROVIDE PLANS AND INFORMATION TO ADDRESS THE
 FOLLOWING ELECTRICAL REVIEW COMMENTS AS PREVIOUSLY
 REQUESTED.
  
 1.) FBC 107.2.1. SUBMITTED PLAN TO BE SIGNED BY
 DESIGNER. THE PLANS HAVE NOT BEEN SIGNED. THIS A
 REQUIREMENT OF THE FLORIDA BUILDING CODE AND ALSO IN
 OUR WEST PALM BEACH AMENDMENTS TO CHAPTER ONE. SECTION
 107.2.1 PLEASE PROVED TWO COPIES OF PLANS THAT HAVE
 BEEN SIGNED BY THE DESIGNER OF RECORD.
  
 2.) FBC SECTION 314 LOCATION OF SMOKE ALARMS. WHEN
 ALTERATIONS, REPAIRS, OR ADDITIONS REQUIRING A PERMIT
 OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE ADDED OR
 CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL DWELLING
 UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS LOCATED AS
 REQUIRED FOR NEW DWELLINGS. FBC-RESIDENTIAL 314 AND
 315. A PLAN HAS BEEN SUBMITTED THAT INDICATES SOME
 SMOKE DETECTORS UNFORTUNATELY THE LOCATIONS SHOWN DO
 NOT MEET THE CRITERIA SET FOR THE FBC-R 413 NAND 315.
 SMOKE DETECTORS ARE REQUIRED TO BE INSTALLED INSIDE AND
 OUTSIDE OF THE SLEEPING ROOMS. THE PLAN PROVIDED
 INDICATES SMOKE DETECTORS TO BE INSTALLED ON THE INSIDE
 ONLY.
  
 3.) N.E.C. 210.63, AND N.E.C. 210.8 (A) (3). LOCATION
 OF GFCI PROTECTED OUTLET WITHIN 25' OF A.C. CONDENSOR.
 CODE REFFERENCES:
 (A) NEC 210.63 ONE 125VOLT, SINGLE-PHASE, 15 OR 20AMP
 GFI RECEPTACLE OUTLET SHALL BE INSTALLED AT AN
 ACCESSIBLE LOCATION FOR THE SERVICING OF HEATING,
 AIR-CONDITIONING, AND REFRIGERATION EQUIPMENT. THE
 RECEPTACLE SHALL BE LOCATED ON THE SAME LEVEL AND
 WITHIN 25FT OF THE HEATING, AIR-CONDITIONING, AND
 REFRIGERATION EQUIPMENT. THE RECEPTACLE OUTLET SHALL
 NOT BE CONNECTED TO THE LOAD SIDE OF THE EQUIPMENT
 DISCONNECTING MEANS. NEC 210.63 SEE ALSO NEC
 210.8(A)(3),
 (B) NEC 210.8 GROUND-FAULT CIRCUIT-INTERRUPTER
 PROTECTION FOR PERSONNEL. (A) DWELLING UNITS. ALL
 125-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE RECEPTACLES
 INSTALLED IN THE LOCATIONS SPECIFIED IN (1) THROUGH (8)
 SHALL HAVE GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION
 FOR PERSONNEL.
 (C) NEC 406.8(B)(1) ALL 15 AND 20AMP 125V AND 250V
 RECEPTACLES INSTALLED IN IN A WET LOCATION SHALL HAVE
 AN ENCLOSURE THAT IS WEATHERPROOF WHETHER OR NOT THE
 ATTACHMENT PLUG CAP IS INSERTED. ALL 15- AND 20-AMPERE,
 125- AND 250-VOLT NON-LOCKING RECEPTACLES SHALL BE
 LISTED WEATHER-RESISTANT TYPE
 PLEASE INDICATE ON THE PLANS THAT THE REQUIRED
 RECEPTACLE IS EITHER CURRENTLY EXISTING TO REMAIN OR
 PROPOSED TO BE INSTALLED.
  
 4.) TABLE NEC 310.16. OVERCURRENT PROTECTION FOR 3#6
 FROM 150 AMP SERVICE EQUIPMENT ENCLOSURE TO 60 AMP
 PANEL. THE RISER DIAGRAM INDICATES THE INSTALATION OF A
 NEW 150AMP ELECTRICAL SERVICE FEEDING A 60AMP INDOOR
 MAIN LUG ONLY PANEL WITHOUT THE INDICATION OF ANY
 OVERCURRENT PROTECTIVE DEVICE AHEAD OF THE #6 WIRE
 SHOWN ON THE RISER DIAGRAM. A PANEL SCHEDULE IS
 REQUIRED TO INDICATE THE CORRECT OCPD IN THE NEW
 SERVICE EQUIPMENT TO PROTECT THE #6 FEEDER TO THE MAIN
 LUG PANEL IN THE HOUSE.
 5. WIRE SIZE TO 5KW AHU.
  
 5) ADDITIONALLY, A SEPARATE PERMIT APPLICATION
 ACCOMPANIED BY MANUFACTURERS EQUIPMENT SUBMITTALS, AND
 SHOP DRAWINGS FOR THE PROPOSED NEW CENTRAL AIR
 CONDITIONING SYSTEM.
  
2015-04-13 16:46:09TO SCIARDELO DESK

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-03-26 Cont ID  
Sent By sciard Date 2015-03-26 Time 11:12 Rev Time 0.00
Received By sciard Date 2015-03-26 Time 11:12 Sent To  
Notes
2015-03-26 11:25:531. FBC 107.2.1. SUBMITTED PLAN TO BE SIGNED BY
 DESIGNER.
 2. FBC SECTION 314 LOCATION OF SMOKE ALARMS.
 3. N.E.C. 210.63,210.8 (A) (3). LOCATION OF GFCI
 PROTECTED OUTLET WITHIN 25' OF A.C. CONDENSOR
 4.TABLE 310.16. OVERCURRENT PROTECTION FOR 3#6 FROM 150
 AMP SERVICE EQUIPMENT ENCLOSURE TO 60 AMP PANEL.
 5. WIRE SIZE TO 5KW AHU.
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-07-01 Cont ID  
Sent By albarran Date 2015-07-01 Time 17:27 Rev Time 0.00
Received By albarran Date 2015-06-30 Time 11:29 Sent To  
Notes
2015-07-01 17:31:00PASSED ELECTRICAL REVIEW, BUT HAS NOT YET PASSED
 MECHANICAL. AMP/CONTRACTOR NOTIFIED VIA EMAIL. SENT TO
 SMALL DENIED BIN "A". MA

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-06-12 Cont ID  
Sent By dhayes Date 2015-06-12 Time 08:36 Rev Time 0.00
Received By dhayes Date 2015-06-11 Time 11:51 Sent To  
Notes
2015-06-11 11:52:19ROUTED TO D. HAYES DESK,

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-04-20 Cont ID  
Sent By dhayes Date 2015-04-20 Time 10:42 Rev Time 0.00
Received By dhayes Date 2015-04-13 Time   Sent To  
Notes
2015-03-25 11:43:34ELECTRICAL LESS THAN 5K

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2015-06-30 Cont ID  
Sent By ccole Date 2015-06-30 Time 11:30 Rev Time 0.00
Received By ccole Date 2015-06-30 Time 11:30 Sent To  
Notes
2015-07-07 10:40:11MECHANICAL CONTRACTOR CAME IN ON 7/01/15 AND MADE
 APPLICATION AS REQUESTED. THE MECHANICAL PERMIT
 APPLICATION NUMBER IS:15070038.
 AS A RESULT. I AM CHANGING THE FAILED MECHANICAL REVIEW
 TO A NOT APPLICABLE. SEE APPLICATION NUMBER: 15070038
 FOR MECHANICAL REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
2015-06-30 11:32:321ST REVIEW: FBC 2010 MECHANICAL
  
 1) THE ELECTRICAL PLAN AND SCOPE OF WORK NOTE #7
 INDICATE A NEW AC SYSTEM IS TO BE INSTALLED, HOWEVER A
 PERMIT APPLICATION AND PLANS FOR THE NEW SYSTEM HAVE
 NOT BEEN SUBMITTED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  