Plan Review Details - Permit 15031068
Plan Review Stops For Permit 15031068
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-06-08 Cont ID  
Sent By rmcdouga Date 2015-06-08 Time 09:59 Rev Time 0.00
Received By rmcdouga Date 2015-06-08 Time 09:33 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-03-30 Cont ID  
Sent By rmcdouga Date 2015-03-30 Time 17:49 Rev Time 0.00
Received By rmcdouga Date 2015-03-30 Time 16:53 Sent To  
Notes
2015-03-30 17:49:12PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) R806.1 VENTILATION REQUIRED.
 ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE
 CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF
 RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE
 SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE
 ENTRANCE OF RAIN. VENTILATION OPENINGS SHALL HAVE A
 LEAST DIMENSION OF 1/16 INCH (1.6 MM) MINIMUM AND 1/4
 INCH (6.4 MM) MAXIMUM. VENTILATION OPENINGS HAVING A
 LEAST DIMENSION LARGER THAN 1/4 INCH (6.4 MM) SHALL BE
 PROVIDED WITH CORROSION-RESISTANT WIRE CLOTH SCREENING,
 HARDWARE CLOTH, OR SIMILAR MATERIAL WITH OPENINGS
 HAVING A LEAST DIMENSION OF 1/16 INCH (1.6 MM) MINIMUM
 AND 1/4 INCH (6.4 MM) MAXIMUM. OPENINGS IN ROOF FRAMING
 MEMBERS SHALL CONFORM TO THE REQUIREMENTS OF SECTION
 R802.7.
 EXCEPTION: ATTIC SPACES, DESIGNED BY A PROFESSIONAL
 ENGINEER OR ARCHITECT LICENSED TO PRACTICE IN THE
 STATE, DESIGNED TO ELIMINATE THE ATTIC VENTING.
 FLAT ROOFS ARE NOT EXEMPT FROM VENTING REQUIREMENTS,
 UNLESS DESIGNED AS REQUIRED BY THE EXCEPTION. SUBMIT
 TWO SETS OF A SIGNED AND SEALED DRAWINGS WITH A WALL
 SECTION SHOWING THE LOCATION OF THE INSULATION.
 UNVENTED ATTICS ARE PART OF THE CONDITIONED SPACE. THE
 APPROVED DRAWINGS SPECIFY SPRAY FOAM INSULATION APPLIED
 TO THE UNDERSIDE OF THE ROOF DECK.
  
 2) SUBMIT TWO SETS OF SIGNED AND SEALED DRAWINGS FOR
 THE STRUCTURAL ROOF FRAMING AT THE SKYLIGHT OPENING.
 SHOW ALL CONNECTORS AND HANGERS. SPECIFY THE SIZE AND
 LOCATION OF THE SKYLIGHT OPENING ON THE PLANS. FBC
 107.2.1 & 301.1
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-03-31 Cont ID  
Sent By rmcdouga Date 2015-03-31 Time 08:43 Rev Time 0.00
Received By rmcdouga Date 2015-03-30 Time 17:49 Sent To  
Notes
2015-03-31 08:43:06APPROVED WITH EXCEPTION. THIS PLAN HAS BEEN APPROVED
 PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES IN THIS PLAN PRIOR TO INSPECTION WILL
 RESULT IN FAILED INSPECTION(S) AND ASSESSMENT OF
 RE-INSPECTION FEE(S).
  
 THE RISER DIAGRAM SHOWS THE NEUTRAL CONDUCTOR IS
 SMALLER THAN THE UNGROUNDED CONDUCTORS FOR THE METER TO
 THE PANEL. PROVIDE THE UNBALANCED LOAD CALCULATIONS
 REQUIRED BY NEC 220.61 TO THE FIELD INSPECTOR.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2015-06-08 Time   Rev Time 0.00
Received By shill Date 2015-05-14 Time 07:40 Sent To  
Notes
2015-05-15 07:39:34TO RM DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-03-31 Cont ID  
Sent By rmcdouga Date 2015-03-31 Time 08:43 Rev Time 0.00
Received By rmcdouga Date 2015-03-24 Time 17:47 Sent To  
Notes
2015-03-24 17:47:37REVISION SENT TO ROBERT MCDOUGAL FOR REVIEW. JG.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-06-08 Cont ID  
Sent By rmcdouga Date 2015-06-08 Time 08:36 Rev Time 0.00
Received By rmcdouga Date 2015-06-08 Time 08:36 Sent To  
Notes
2015-06-08 08:38:50APPROVED WITH EXCEPTION. THIS PLAN HAS BEEN APPROVED
 PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES IN THIS PLAN PRIOR TO INSPECTION WILL
 RESULT IN FAILED INSPECTION(S) AND ASSESSMENT OF
 RE-INSPECTION FEE(S).
 M1602.4 BALANCED RETURN AIR. ALL SUPPLY AIR INTO THE
 MASTER SUITE SHALL BE INCLUDED.
 THE TRANSFER GRILL AT THE MASTER BEDROOM IS TOO SMALL.
 THE AIR SUPPLY TO THE MASTER BATHROOM WAS NOT
 CONSIDERED.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-03-30 Cont ID  
Sent By rmcdouga Date 2015-03-30 Time 16:52 Rev Time 0.00
Received By rmcdouga Date 2015-03-30 Time 16:44 Sent To  
Notes
2015-03-30 16:52:22PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC-R - M1401.3 SIZING. HEATING AND COOLING
 EQUIPMENT SHALL BE SIZED BASED ON BUILDING LOADS
 CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR OTHER
 APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES.
 PROVIDE EQUIPMENT SIZING CALCULATIONS.
  
 2) FBC 107.2.1 PROVIDE THE MODEL NUMBERS AND
 SPECIFICATIONS OF THE HEATING AND COOLING EQUIPMENT IN
 AN EQUIPMENT SCHEDULE ON THE MECHANICAL PLAN THAT
 CORRESPONDS WITH THE EQUIPMENT SIZING CALCULATIONS.
  
 3) SPECIFY THE CFMS AT EACH SUPPLY GRILL. FBC-R - M
 1602.4 PROVIDE BALANCED AIR RETURN AT BEDROOMS. M1602.4
 BALANCED RETURN AIR.
 RESTRICTED RETURN AIR OCCURS IN BUILDINGS WHEN RETURNS
 ARE LOCATED IN CENTRAL ZONES AND CLOSED INTERIOR DOORS
 IMPEDE AIR FLOW TO THE RETURN GRILL OR WHEN CEILING
 SPACES ARE USED AS RETURN PLENUMS AND FIRE WALLS
 RESTRICT AIR MOVEMENT FROM ONE PORTION OF THE RETURN
 PLENUM TO ANOTHER. PROVISIONS SHALL BE MADE IN BOTH
 RESIDENTIAL AND COMMERCIAL BUILDINGS TO AVOID
 UNBALANCED AIR FLOWS AND PRESSURE DIFFERENTIALS CAUSED
 BY RESTRICTED RETURN AIR. PRESSURE DIFFERENTIALS ACROSS
 CLOSED DOORS WHERE RETURNS ARE CENTRALLY LOCATED SHALL
 BE LIMITED TO 0.01 INCH WC (2.5 PASCALS) OR LESS.
 PRESSURE DIFFERENTIALS ACROSS FIRE WALLS IN CEILING
 SPACE PLENUMS SHALL BE LIMITED TO 0.01 INCH WC (2.5
 PASCALS) BY PROVIDING AIR DUCT PATHWAYS OR AIR TRANSFER
 PATHWAYS FROM THE HIGH PRESSURE ZONE TO THE LOW ZONE.
  
 EXCEPTIONS:
  
 1. TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE
 RETURN TRANSFER 1-1/2 TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT ENTERING THE ROOM OR
 SPACE IT IS SERVING AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCH UNDERCUT TO ACHIEVE PROPER RETURN
 AIR BALANCE.
  
 2. TRANSFER GRILLES SHALL USE 50 SQUARE INCHES (OF
 GRILLE AREA) TO 100 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND USING AN
 UNRESTRICTED 1 INCH UNDERCUTTING OF DOORS TO ACHIEVE
 PROPER RETURN AIR BALANCE.
  
 3. HABITABLE ROOMS ONLY SHALL BE REQUIRED TO MEET THESE
 REQUIREMENTS FOR PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND LAUNDRY ROOMS,
 EXCEPT THAT ALL SUPPLY AIR INTO THE MASTER SUITE SHALL
 BE INCLUDED.
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-03-30 Cont ID  
Sent By rmcdouga Date 2015-03-30 Time 16:43 Rev Time 0.00
Received By rmcdouga Date 2015-03-30 Time 16:43 Sent To  
Notes
***NONE***