Plan Review Details - Permit 15031038
Plan Review Stops For Permit 15031038
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-04-13 Cont ID  
Sent By scaldero Date 2015-04-13 Time 12:19 Rev Time 0.00
Received By scaldero Date 2015-04-13 Time 12:19 Sent To I
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-04-01 Cont ID  
Sent By scaldero Date 2015-04-01 Time 17:40 Rev Time 0.00
Received By scaldero Date 2015-04-01 Time 17:40 Sent To M
Notes
2015-04-01 17:43:02PERMIT # 15031038
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FAILED COMMENTS:
  
 1) THE ADDRESS PROVIDED ON THE PLANS DOES NOT MATCH THE
 ADDRESS PROVIDED ON THE PERMIT APPLICATION
  
 2) PROVIDE HYDRAULIC CALCULATIONS SUPPORTING THE USE OF
 THE FLEXIBLE SPRINKLER DROPS AND THE ADDITIONAL
 FRICTION LOSS ASSOCIATED WITH THESE PRODUCTS.
  
 PROVIDE A FLEXIBLE DROP DETAIL INDICATING THE MAXIMUM
 NUMBER OF BENDS PERMITTED AND THE MINIMUM BEND RADIUS
 PERMITTED IN THE LISTING DATA.
  
 SUBMIT PRODUCT DATA FOR THE FLEXIBLE SPRINKLER DROPS
 PROPOSED TO BE INSTALLED. INDICATE IF THE DROPS ARE
 BRAIDED OR UNBRAIDED.
  
 INDICATE THE MAXIMUM LENGTH OF FLEXIBLE DROP TO BE
 USED.
  
  
  
 SUE ELLEN CALDERON
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 644-7326
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-04-06 Cont ID  
Sent By hmoser Date 2015-04-06 Time 11:09 Rev Time 0.00
Received By hmoser Date 2015-03-24 Time 17:53 Sent To  
Notes
2015-03-24 17:53:32REVISION SENT TO FIRE SHELF FOR REVIEW. JG.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-04-06 Cont ID  
Sent By hmoser Date 2015-04-06 Time 13:34 Rev Time 0.00
Received By hmoser Date 2015-04-06 Time 13:34 Sent To FIRE
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-04-06 Cont ID  
Sent By SKENNEDY Date 2015-04-06 Time 11:06 Rev Time 0.00
Received By hmoser Date 2015-04-06 Time 11:06 Sent To  
Notes
2015-04-06 11:09:11PLAN DENIED
 ADDRESS ON PLAN AND APPLICATION DO NOT MATCH.
 PER SECTION 107 FBC 2010
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676