Plan Review Details - Permit 15030956
Plan Review Stops For Permit 15030956
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-06-22 Cont ID  
Sent By rmcdouga Date 2015-06-22 Time 10:44 Rev Time 0.00
Received By rmcdouga Date 2015-06-20 Time 11:52 Sent To  
Notes
2015-06-22 10:44:14APPROVED WITH EXCEPTION. THIS PLAN HAS BEEN APPROVED
 PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES IN THIS PLAN PRIOR TO INSPECTION WILL
 RESULT IN FAILED INSPECTION(S) AND ASSESSMENT OF
 RE-INSPECTION FEE(S).
 1) REVISE THE TRUSS ANCHOR FOR MARK C ON SHEET S-2. THE
 ALLOWABLE UPLIFT LOAD FOR THE DOUBLE SIMPSON HETA
 ANCHOR IS 2500. THE ANCHOR SCHEDULE SPECIFIES THE
 ALLOWABLE UPLIFT FOR (2) HETA 16 ANCHORS AS 3620.
 2) SUBMIT TWO CURRENT SETS OF PRODUCT APPROVALS FOR THE
 ASPHALT ROOF SHINGLES THAT HAVE BEEN APPROVED IN
 WRITING BY THE DESIGNER OF RECORD. THE ONE THAT WAS
 SUBMITTED, NOA NO. 06-0914.04, EXPIRED ON 11/16/2011.
 3) SPECIFY THE ROOFING ASSEMBLY AND MAXIMUM DESIGN
 PRESSURE FOR THE CERTAINTEED MODIFIED BITUMEN ROOF
 SYSTEM THAT WILL BE INSTALLED. THE FLAT ROOF CORNER
 AREAS REQUIRE A DESIGN PRESSURE OF -104.8 PSF PER THE
 WINDLOAD TABLE ON SHEET S-2.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-04-30 Cont ID  
Sent By rmcdouga Date 2015-04-30 Time 07:10 Rev Time 0.00
Received By rmcdouga Date 2015-04-29 Time 07:38 Sent To  
Notes
2015-04-29 19:01:16PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE OWNER/AGENT IS REQUIRED TO SIGN THE ENERGY FORM.
 FBC ENERGY CONSERVATION - SECT. 103.2.3.2
  
 2) THE ENERGY FORM LISTS A SLAB ON GRADE FLOOR TYPE FOR
 THE ADDITION AND THE PLANS SPECIFY A WOOD FRAME FLOOR
 SYSTEM WITH R-14 INSULATION. PLEASE CORRECT. FBC ENERGY
 CONSERVATION - SECT. 101.4.3
  
 3) SHOW COMPLIANCE WITH FBC-R318.1 FOR TERMITE
 PROTECTION.
  
 4) SPECIFY THE CLEARANCE BETWEEN THE WOOD FLOOR FRAMING
 AND THE GROUND. R317.1 PROTECTION OF WOOD AND WOOD
 BASED PRODUCTS FROM DECAY SHALL BE PROVIDED IN THE
 FOLLOWING LOCATIONS BY THE USE OF NATURALLY DURABLE
 WOOD OR WOOD THAT IS PRESERVATIVE-TREATED IN ACCORDANCE
 WITH AWPA U1 FOR THE SPECIES, PRODUCT, PRESERVATIVE AND
 END USE. PRESERVATIVES SHALL BE LISTED IN SECTION 4 OF
 AWPA U1.
 1. WOOD JOISTS OR THE BOTTOM OF A WOOD STRUCTURAL FLOOR
 WHEN CLOSER THAN 18 INCHES (457 MM) OR WOOD GIRDERS
 WHEN CLOSER THAN 12 INCHES (305 MM) TO THE EXPOSED
 GROUND IN CRAWL SPACES OR UNEXCAVATED AREA LOCATED
 WITHIN THE PERIPHERY OF THE BUILDING FOUNDATION.
  
 5) SHOW COMPLIANCE WITH R408.1 VENTILATION.
 THE UNDER-FLOOR SPACE BETWEEN THE BOTTOM OF THE FLOOR
 JOISTS AND THE EARTH UNDER ANY BUILDING (EXCEPT SPACE
 OCCUPIED BY A BASEMENT) SHALL HAVE VENTILATION OPENINGS
 THROUGH FOUNDATION WALLS OR EXTERIOR WALLS. THE MINIMUM
 NET AREA OF VENTILATION OPENINGS SHALL NOT BE LESS THAN
 1 SQUARE FOOT (0.0929 M2) FOR EACH 150 SQUARE FEET (14
 M2) OF UNDER-FLOOR SPACE AREA, UNLESS THE GROUND
 SURFACE IS COVERED BY A CLASS 1 VAPOR RETARDER
 MATERIAL. WHEN A CLASS 1 VAPOR RETARDER MATERIAL IS
 USED, THE MINIMUM NET AREA OF VENTILATION OPENINGS
 SHALL NOT BE LESS THAN 1 SQUARE FOOT (0.0929 M2) FOR
 EACH 1,500 SQUARE FEET (140 M2) OF UNDER-FLOOR SPACE
 AREA. ONE SUCH VENTILATING OPENING SHALL BE WITHIN 3
 FEET (914 MM) OF EACH CORNER OF THE BUILDING.
  
 6) SHOW COMPLIANCE WITH R408.4 ACCESS.
 ACCESS SHALL BE PROVIDED TO ALL UNDER-FLOOR SPACES.
 ACCESS OPENINGS THROUGH THE FLOOR SHALL BE A MINIMUM OF
 18 INCHES BY 24 INCHES (457 MM BY 610 MM). OPENINGS
 THROUGH A PERIMETER WALL SHALL BE NOT LESS THAN 16
 INCHES BY 24 INCHES (407 MM BY 610 MM). WHEN ANY
 PORTION OF THE THROUGH-WALL ACCESS IS BELOW GRADE, AN
 AREA-WAY NOT LESS THAN 16 INCHES BY 24 INCHES (407 MM
 BY 610 MM) SHALL BE PROVIDED. THE BOTTOM OF THE AREAWAY
 SHALL BE BELOW THE THRESHOLD OF THE ACCESS OPENING.
 THROUGH WALL ACCESS OPENINGS SHALL NOT BE LOCATED UNDER
 A DOOR TO THE RESIDENCE. SEE SECTION M1305.1.4 FOR
 ACCESS REQUIREMENTS WHERE MECHANICAL EQUIPMENT IS
 LOCATED UNDER FLOORS.
  
 7) THERE ARE ERRORS IN THE TRUSS ANCHOR SCHEDULE ON
 S-2. THE MANUFACTURER IS SIMPSON, NOT SYMPSON. THE
 DETAL 20 CONNECTOR IS LISTED AS "DETAIL" 20. THE MARK C
 CONNECTOR WITH A 3965 UPLIFT RATING IS INCORRECTLY
 SPECIFIED AS A META 16 CONNECTOR. PLEASE CORRECT. FBC
 107.2.1
  
 8) ON SHEET A-1 THE OUTSWING ENTRY AND GARAGE DOORS
 HAVE THE LETTER J AS AN ID MARK. THERE ARE NO LETTER J
 MARK IN THE DOOR SCHEDULE. THERE IS A NUMBER 2 MARK FOR
 DOORS. THAT HAS NO CORRESPONDING ID MARK ON THE PLANS.
 IT APPEARS THAT THIS SHOULD BE THE J MARK. PLEASE
 CLARIFY. FBC 107.2.1
  
 9) THE COMPONENT AND CLADDING PRESSURES FOR THE
 OUTSWING SIDE GARAGE DOOR ARE NOT SPECIFIED ON THE
 PLANS. FBC-R301.2.1
  
 10) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. PROVIDE TWO COMPLETE PRODUCT
 APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION
 INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR EACH OF
 THE DIFFERENT ROOFING MATERIALS. SUBMIT TWO COPIES OF
 THE PRODUCT APPROVALS FOR THE BORAL PEEL & STICK
 UNDERLAYMENT AND ASPHALT SHINGLES ( SLOPED ROOF ), AS
 WELL AS, THE MODIFIED HOT MOP ROOFING ( FLAT ROOF )
 THAT ARE SPECIFIED ON SHEET A-1.
  
 11) IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE
 CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER
 INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN
 ADDRESSED.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-04-28 Cont ID  
Sent By rlecky Date 2015-04-28 Time 11:31 Rev Time 0.00
Received By rlecky Date 2015-04-28 Time 10:22 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2015-04-29 Cont ID  
Sent By rmcdouga Date 2015-04-29 Time 08:30 Rev Time 0.00
Received By rmcdouga Date 2015-04-29 Time 08:30 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2015-03-30 Cont ID  
Sent By fmittner Date 2015-03-30 Time 16:44 Rev Time 0.00
Received By fmittner Date 2015-03-30 Time 16:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-06-22 Cont ID  
Sent By rmcdouga Date 2015-06-22 Time 10:44 Rev Time 0.00
Received By rmcdouga Date 2015-05-14 Time 07:54 Sent To  
Notes
2015-05-15 07:56:57TO RM DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-04-30 Cont ID  
Sent By rmcdouga Date 2015-04-30 Time 07:10 Rev Time 0.00
Received By rmcdouga Date 2015-03-23 Time 11:50 Sent To  
Notes
2015-04-01 11:51:27SENT TO R14 SHELF FOR REVIEW. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2015-06-20 Cont ID  
Sent By rmcdouga Date 2015-06-20 Time 11:52 Rev Time 0.00
Received By rmcdouga Date 2015-06-20 Time 11:53 Sent To  
Notes
2015-06-20 11:53:58MU 2015 - 11515

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-04-29 Cont ID  
Sent By rmcdouga Date 2015-04-29 Time 07:44 Rev Time 0.00
Received By rmcdouga Date 2015-04-29 Time 07:44 Sent To  
Notes
2015-04-29 07:44:26BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2015-04-29 Cont ID  
Sent By rmcdouga Date 2015-04-29 Time 10:13 Rev Time 0.00
Received By rmcdouga Date 2015-04-29 Time 09:17 Sent To  
Notes
2015-04-29 10:13:33APPROVED WITH EXCEPTION. THIS PLAN HAS BEEN APPROVED
 PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES IN THIS PLAN PRIOR TO INSPECTION WILL
 RESULT IN FAILED INSPECTION(S) AND ASSESSMENT OF
 RE-INSPECTION FEE(S).
 1) FBC-R - M1305.1.3 APPLIANCES IN ATTICS.
 ATTICS CONTAINING APPLIANCES SHALL BE PROVIDED WITH AN
 OPENING AND A CLEAR AND UNOBSTRUCTED PASSAGEWAY LARGE
 ENOUGH TO ALLOW REMOVAL OF THE LARGEST APPLIANCE, BUT
 NOT LESS THAN 30 INCHES (762 MM) HIGH AND 22 INCHES
 (559 MM) WIDE AND NOT MORE THAN 6 FEET (1829 MM) LONG
 MEASURED ALONG THE CENTERLINE OF THE PASSAGEWAY FROM
 THE OPENING TO THE APPLIANCE. THE PASSAGEWAY SHALL HAVE
 CONTINUOUS SOLID FLOORING IN ACCORDANCE WITH CHAPTER 5
 NOT LESS THAN 24 INCHES (610 MM) WIDE. A LEVEL SERVICE
 SPACE AT LEAST 30 INCHES (762 MM) DEEP AND 30 INCHES
 (762 MM) WIDE SHALL BE PRESENT ALONG ALL SIDES OF THE
 APPLIANCE WHERE ACCESS IS REQUIRED. THE CLEAR ACCESS
 OPENING DIMENSIONS SHALL BE A MINIMUM OF 20 INCHES BY
 30 INCHES (508 MM BY 762 MM), AND LARGE ENOUGH TO ALLOW
 REMOVAL OF THE LARGEST APPLIANCE.
 2) FBC-R - M1305.1.3.1 ELECTRICAL REQUIREMENTS.
 A LUMINAIRE CONTROLLED BY A SWITCH LOCATED AT THE
 REQUIRED PASSAGEWAY OPENING AND A RECEPTACLE OUTLET
 SHALL BE INSTALLED AT OR NEAR THE APPLIANCE LOCATION IN
 ACCORDANCE WITH CHAPTER 34.
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-04-29 Cont ID  
Sent By rmcdouga Date 2015-04-29 Time 08:54 Rev Time 0.00
Received By rmcdouga Date 2015-04-29 Time 08:54 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2015-08-27 Cont ID  
Sent By rmcdouga Date 2015-08-27 Time 17:15 Rev Time 0.00
Received By rmcdouga Date 2015-08-27 Time 17:15 Sent To  
Notes
2015-08-27 17:22:20ROOFING MATERIALS (PROVISO WAS ADDRESSED FOR ROOFING
 MATERIAL)
 - CERTAINTEED ASPHALT SHINGLES, NOA NO.14-0828.04
 - CERTAINTEED FLINTASTIC MODIFIED BITUMEN ROOF SYSTEM,
 FL16709-R2

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2015-06-22 Cont ID  
Sent By rmcdouga Date 2015-06-22 Time 13:00 Rev Time 0.00
Received By rmcdouga Date 2015-06-22 Time 13:00 Sent To  
Notes
2015-06-22 13:00:501) CERTAINTEED ASPHALT SHINGLES NOA NO 06-0914.04
 (EXPIRED - SEE BUILDING PROVISO)
 2) CERTAINTEED FLINTLASTIC MODIFIED BITUMEN ROOF SYSTEM
 FL2533 - R12 ( SEE BUILDING PROVISO)
 3) ATLAS ACFOAM ROOFING INSULATION FL6796

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2015-04-29 Cont ID  
Sent By rmcdouga Date 2015-04-29 Time 18:15 Rev Time 0.00
Received By rmcdouga Date 2015-04-29 Time 18:15 Sent To  
Notes
2015-04-29 18:16:58NO PRODUCT APPROVALS WERE SUBMITTED FOR ROOFING
 MATERIALS FOR THE SLOPED OR FLAT ROOFS.

Review Stop Z ZONING
Rev No 1 Status P Date 2015-03-30 Cont ID  
Sent By fmittner Date 2015-03-30 Time 16:41 Rev Time 0.00
Received By fmittner Date 2015-03-30 Time 16:41 Sent To B
Notes
***NONE***