Plan Review Details - Permit 15030938
Plan Review Stops For Permit 15030938
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-04-08 Cont ID  
Sent By shill Date 2015-04-08 Time 14:03 Rev Time 0.00
Received By shill Date 2015-04-08 Time 14:03 Sent To  
Notes
2015-04-08 14:04:58****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. REVISE THE FLOOR PLAN TO SHOW ROOM DESIGNATIONS.
  
 2. FOR BEDROOM WINDOWS WHICH ARE LESS THAN 51" IN
 HEIGHT, NOTE EXISTING CONDITIONS (TYPE OF WINDOW) AND
 OPENING SIZE FOR BEDROOMS, FBC R310, FBC EB 604.1. THE
 CLEAR OPENING CANNOT BE REDUCED BY MORE THAN 5%.
  
 TO PROVIDE FURTHER CLARIFICATION REGARDING INFORMATION
 NEEDED FOR BEDROOM WINDOWS WHICH ARE LESS THAN 51" IN
 HEIGHT:
  
 STATE WHAT TYPE OF WINDOW IS THERE NOW IN THE BEDROOMS
 - AWNING, CASEMENT, SINGLE HUNG?
  
 STATE WHAT THE EXISTING CLEAR OPENING DIMENSIONS ARE.
 CLEAR OPENING IS THE OPENING WHICH EXISTS WHEN THE
 WINDOW IS FULLY OPEN.
  
 STATE WHAT THE PROPOSED CLEAR OPENING DIMENSIONS ARE.
 THIS CAN BE OBTAINED FROM THE MANUFACTURER.
  
  
  
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2015-03-23 Cont ID  
Sent By fmittner Date 2015-03-23 Time 11:30 Rev Time 0.00
Received By fmittner Date 2015-03-23 Time 11:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status P Date 2015-03-23 Cont ID  
Sent By ndaniels Date 2015-03-23 Time 11:37 Rev Time  
Received By ndaniels Date   Time   Sent To  
Notes
2015-03-23 11:37:23ROUTED TO BUILDING OVER $5K