Plan Review Details - Permit 15030907
Plan Review Stops For Permit 15030907
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-03-26 Cont ID  
Sent By rmcdouga Date 2015-03-26 Time 09:30 Rev Time 0.00
Received By rmcdouga Date 2015-03-26 Time 07:00 Sent To  
Notes
2015-03-26 09:29:41PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT TWO COPIES OF THE PRODUCT APPROVALS (
 FL5822-R2 ) AND THE ICC EVALUATION REPORT ( ESR- 2074)
 FOR THE SMART VENTS.
  
 2) R322.2.1 ELEVATION REQUIREMENTS. EXCEPTION: ENCLOSED
 AREAS BELOW THE DESIGN FLOOD ELEVATION, INCLUDING
 BASEMENTS WHOSE FLOORS ARE NOT BELOW GRADE ON ALL
 SIDES, SHALL MEET THE REQUIREMENTS OF SECTION R322.2.2.
 R322.2.2 ENCLOSED AREA BELOW DESIGN FLOOD ELEVATION.
 ENCLOSED AREAS, INCLUDING CRAWL SPACES, THAT ARE BELOW
 THE DESIGN FLOOD ELEVATION SHALL:
 2.1. THERE SHALL BE A MINIMUM OF TWO OPENINGS ON
 DIFFERENT SIDES OF EACH ENCLOSED AREA; IF A BUILDING
 HAS MORE THAN ONE ENCLOSED AREA BELOW THE DESIGN FLOOD
 ELEVATION, EACH AREA SHALL HAVE OPENINGS ON EXTERIOR
 WALLS.
 2.2. THE TOTAL NET AREA OF ALL OPENINGS SHALL BE AT
 LEAST 1 SQUARE INCH (645 MM2) FOR EACH SQUARE FOOT
 (0.093 M2) OF ENCLOSED AREA, OR THE OPENINGS SHALL BE
 DESIGNED AND THE CONSTRUCTION DOCUMENTS SHALL INCLUDE A
 STATEMENT BY A REGISTERED DESIGN PROFESSIONAL THAT THE
 DESIGN OF THE OPENINGS WILL PROVIDE FOR EQUALIZATION OF
 HYDROSTATIC FLOOD FORCES ON EXTERIOR WALLS BY ALLOWING
 FOR THE AUTOMATIC ENTRY AND EXIT OF FLOODWATERS AS
 SPECIFIED IN SECTION 2.6.2.2 OF ASCE 24.
  
 3) FEMA TECHNICAL BULLETIN 1 / AUGUST 2008, OPENINGS IN
 FOUNDATION WALLS AND WALLS OF ENCLOSURES, NOTES THAT
 ONLY THE PORTIONS OF OPENINGS THAT ARE BELOW THE BFE
 CAN BE COUNTED TOWARDS THE REQUIRED NET OPEN AREA. IN
 THIS CASE THE GARAGE FLOOR IS AT BFE, SO THE AREA OF
 THE SMART VENTS THAT ARE BELOW THE REQUIRED 6"
 FREEBOARD CAN BE COUNTED TOWARDS THE REQUIRED NET OPEN
 AREA. SUBMIT SIGNED AND SEALED CALCULATIONS TO SHOW
 COMPLIANCE.
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-03-26 Cont ID  
Sent By rmcdouga Date 2015-03-26 Time 09:31 Rev Time  
Received By rmcdouga Date 2015-03-23 Time   Sent To  
Notes
2015-03-23 14:43:44INCOMING SENT TO R. MCDOUGALS' DESK.